.........T [DEV-1998] fixed typos and changed README files for Power templates
Diffstat (limited to 'templates')
-rw-r--r--templates/power/apc/apc_ups_galaxy_3500_snmp/README.md38
-rw-r--r--templates/power/apc/apc_ups_galaxy_3500_snmp/template_power_apc_ups_galaxy_3500_snmp.yaml4
-rw-r--r--templates/power/apc/apc_ups_smart_2200_rm_snmp/README.md38
-rw-r--r--templates/power/apc/apc_ups_smart_2200_rm_snmp/template_power_apc_ups_smart_2200_rm_snmp.yaml4
-rw-r--r--templates/power/apc/apc_ups_smart_3000_xlm_snmp/README.md38
-rw-r--r--templates/power/apc/apc_ups_smart_3000_xlm_snmp/template_power_apc_ups_smart_3000_xlm_snmp.yaml4
-rw-r--r--templates/power/apc/apc_ups_smart_rt_1000_rm_xl_snmp/README.md38
-rw-r--r--templates/power/apc/apc_ups_smart_rt_1000_rm_xl_snmp/template_power_apc_ups_smart_rt_1000_rm_xl_snmp.yaml4
-rw-r--r--templates/power/apc/apc_ups_smart_rt_1000_xl_snmp/README.md38
-rw-r--r--templates/power/apc/apc_ups_smart_rt_1000_xl_snmp/template_power_apc_ups_smart_rt_1000_xl_snmp.yaml4
-rw-r--r--templates/power/apc/apc_ups_smart_srt_5000_snmp/README.md38
-rw-r--r--templates/power/apc/apc_ups_smart_srt_5000_snmp/template_power_apc_ups_smart_srt_5000_snmp.yaml4
-rw-r--r--templates/power/apc/apc_ups_smart_srt_8000_snmp/README.md38
-rw-r--r--templates/power/apc/apc_ups_smart_srt_8000_snmp/template_power_apc_ups_smart_srt_8000_snmp.yaml4
-rw-r--r--templates/power/apc/apc_ups_snmp/README.md38
-rw-r--r--templates/power/apc/apc_ups_snmp/template_power_apc_ups_snmp.yaml14
-rw-r--r--templates/power/apc/apc_ups_symmetra_lx_snmp/README.md38
-rw-r--r--templates/power/apc/apc_ups_symmetra_lx_snmp/template_power_apc_ups_symmetra_lx_snmp.yaml4
-rw-r--r--templates/power/apc/apc_ups_symmetra_rm_snmp/README.md38
-rw-r--r--templates/power/apc/apc_ups_symmetra_rm_snmp/template_power_apc_ups_symmetra_rm_snmp.yaml4
-rw-r--r--templates/power/apc/apc_ups_symmetra_rx_snmp/README.md38
-rw-r--r--templates/power/apc/apc_ups_symmetra_rx_snmp/template_power_apc_ups_symmetra_rx_snmp.yaml4
22 files changed, 231 insertions, 241 deletions
diff --git a/templates/power/apc/apc_ups_galaxy_3500_snmp/README.md b/templates/power/apc/apc_ups_galaxy_3500_snmp/README.md
index e273767e224..6e4f55ccb20 100644
--- a/templates/power/apc/apc_ups_galaxy_3500_snmp/README.md
+++ b/templates/power/apc/apc_ups_galaxy_3500_snmp/README.md
@@ -53,7 +53,7 @@ There are no template links in this template.
|----|-----------|----|----|
|Input phases discovery |<p>The input phase identifier. OID upsPhaseInputPhaseIndex.1.1</p> |SNMP |input.phases.discovery |
|Output phases discovery |<p>The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1</p> |SNMP |output.phases.discovery |
-|External battery packs discovery | |SNMP |battery.packs.discovery<p>**Filter**:</p>AND <p>- A: {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`</p> |
+|External battery packs discovery |<p>-</p> |SNMP |battery.packs.discovery<p>**Filter**:</p>AND <p>- {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`</p> |
|External bad battery packs discovery |<p>Discovery of the number of external defective battery packs.</p> |SNMP |battery.packs.bad.discovery |
|External sensor port 1 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor1.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR1_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
|External sensor port 2 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor2.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR2_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
@@ -112,29 +112,29 @@ There are no template links in this template.
|System name has changed (new name: {ITEM.VALUE}) |<p>System name has changed. Ack to close.</p> |`last(/APC UPS Galaxy 3500 SNMP/system.name[sysName.0],#1)<>last(/APC UPS Galaxy 3500 SNMP/system.name[sysName.0],#2) and length(last(/APC UPS Galaxy 3500 SNMP/system.name[sysName.0]))>0` |INFO |<p>Manual close: YES</p> |
|Battery has an internal error condition |<p>A battery installed has an internal error condition.</p> |`last(/APC UPS Galaxy 3500 SNMP/battery.status[upsBasicBatteryStatus])=4` |AVERAGE | |
|Battery is Low |<p>The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.</p> |`last(/APC UPS Galaxy 3500 SNMP/battery.status[upsBasicBatteryStatus])=3` |AVERAGE | |
-|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) | |`last(/APC UPS Galaxy 3500 SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
+|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) |<p>-</p> |`last(/APC UPS Galaxy 3500 SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
|Battery needs replacement |<p>A battery installed has an internal error condition.</p> |`last(/APC UPS Galaxy 3500 SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2` |HIGH | |
-|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC UPS Galaxy 3500 SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
-|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC UPS Galaxy 3500 SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC UPS Galaxy 3500 SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Galaxy 3500 SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
-|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) | |`min(/APC UPS Galaxy 3500 SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC UPS Galaxy 3500 SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC UPS Galaxy 3500 SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
+|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) |<p>-</p> |`min(/APC UPS Galaxy 3500 SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) |<p>-</p> |`min(/APC UPS Galaxy 3500 SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC UPS Galaxy 3500 SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Galaxy 3500 SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
+|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) |<p>-</p> |`min(/APC UPS Galaxy 3500 SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC UPS Galaxy 3500 SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC UPS Galaxy 3500 SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
|Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD}) |<p>A battery installed has an internal error condition.</p> |`min(/APC UPS Galaxy 3500 SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}` |HIGH | |
-|UPS is Timed Sleeping | |`last(/APC UPS Galaxy 3500 SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | |
-|UPS is Switched Bypass | |`last(/APC UPS Galaxy 3500 SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | |
-|UPS is Software Bypass | |`last(/APC UPS Galaxy 3500 SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | |
-|UPS is Sleeping Until Power Return | |`last(/APC UPS Galaxy 3500 SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | |
-|UPS is Rebooting | |`last(/APC UPS Galaxy 3500 SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | |
-|UPS is On Smart Trim | |`last(/APC UPS Galaxy 3500 SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | |
-|UPS is on Smart Boost | |`last(/APC UPS Galaxy 3500 SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | |
-|UPS is on battery | |`last(/APC UPS Galaxy 3500 SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | |
-|UPS is Off | |`last(/APC UPS Galaxy 3500 SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | |
-|UPS is Emergency Static Bypass | |`last(/APC UPS Galaxy 3500 SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | |
-|UPS is Hardware Failure Bypass | |`last(/APC UPS Galaxy 3500 SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | |
+|UPS is Timed Sleeping |<p>-</p> |`last(/APC UPS Galaxy 3500 SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | |
+|UPS is Switched Bypass |<p>-</p> |`last(/APC UPS Galaxy 3500 SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | |
+|UPS is Software Bypass |<p>-</p> |`last(/APC UPS Galaxy 3500 SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | |
+|UPS is Sleeping Until Power Return |<p>-</p> |`last(/APC UPS Galaxy 3500 SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | |
+|UPS is Rebooting |<p>-</p> |`last(/APC UPS Galaxy 3500 SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | |
+|UPS is On Smart Trim |<p>-</p> |`last(/APC UPS Galaxy 3500 SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | |
+|UPS is on Smart Boost |<p>-</p> |`last(/APC UPS Galaxy 3500 SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | |
+|UPS is on battery |<p>-</p> |`last(/APC UPS Galaxy 3500 SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | |
+|UPS is Off |<p>-</p> |`last(/APC UPS Galaxy 3500 SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | |
+|UPS is Emergency Static Bypass |<p>-</p> |`last(/APC UPS Galaxy 3500 SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | |
+|UPS is Hardware Failure Bypass |<p>-</p> |`last(/APC UPS Galaxy 3500 SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | |
|{HOST.NAME} has been restarted (uptime < 10m) |<p>Uptime is less than 10 minutes</p> |`last(/APC UPS Galaxy 3500 SNMP/system.uptime[sysUpTime.0])<10m` |WARNING |<p>Manual close: YES</p><p>**Depends on**:</p><p>- No SNMP data collection</p> |
|No SNMP data collection |<p>SNMP is not available for polling. Please check device connectivity and SNMP settings.</p> |`max(/APC UPS Galaxy 3500 SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0` |WARNING | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC UPS Galaxy 3500 SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Galaxy 3500 SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC UPS Galaxy 3500 SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Galaxy 3500 SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) |<p>-</p> |`min(/APC UPS Galaxy 3500 SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Galaxy 3500 SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) |<p>-</p> |`min(/APC UPS Galaxy 3500 SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Galaxy 3500 SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |<p>The battery cartridge status:</p><p>bit 0 Disconnected</p><p>bit 1 Overvoltage</p><p>bit 2 NeedsReplacement</p><p>bit 3 OvertemperatureCritical</p><p>bit 4 Charger</p><p>bit 5 TemperatureSensor</p><p>bit 6 BusSoftStart</p><p>bit 7 OvertemperatureWarning</p><p>bit 8 GeneralError</p><p>bit 9 Communication</p><p>bit 10 DisconnectedFrame</p><p>bit 11 FirmwareMismatch</p> |`find(/APC UPS Galaxy 3500 SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0` |WARNING | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC UPS Galaxy 3500 SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) |<p>-</p> |`min(/APC UPS Galaxy 3500 SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |<p>The battery cartridge health.</p><p> bit 0 Battery lifetime okay</p><p> bit 1 Battery lifetime near end, order replacement cartridge</p><p> bit 2 Battery lifetime exceeded, replace battery</p><p> bit 3 Battery lifetime near end acknowledged, order replacement cartridge</p><p> bit 4 Battery lifetime exceeded acknowledged, replace battery</p><p> bit 5 Battery measured lifetime near end, order replacement cartridge</p><p> bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge</p> |`find(/APC UPS Galaxy 3500 SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1` |WARNING | |
|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`last(/APC UPS Galaxy 3500 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4` |INFO | |
|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`last(/APC UPS Galaxy 3500 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2` |AVERAGE | |
diff --git a/templates/power/apc/apc_ups_galaxy_3500_snmp/template_power_apc_ups_galaxy_3500_snmp.yaml b/templates/power/apc/apc_ups_galaxy_3500_snmp/template_power_apc_ups_galaxy_3500_snmp.yaml
index 6d0c768f72d..a3d7a30ce48 100644
--- a/templates/power/apc/apc_ups_galaxy_3500_snmp/template_power_apc_ups_galaxy_3500_snmp.yaml
+++ b/templates/power/apc/apc_ups_galaxy_3500_snmp/template_power_apc_ups_galaxy_3500_snmp.yaml
@@ -1,6 +1,6 @@
zabbix_export:
version: '5.4'
- date: '2021-10-28T06:44:01Z'
+ date: '2021-12-20T07:09:57Z'
groups:
-
uuid: 3dcd5bbe90534f9e8eb5c2d53756af63
@@ -19,7 +19,7 @@ zabbix_export:
You can discuss this template or leave feedback on our forum https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups
- Template tooling version used: 0.39
+ Template tooling version used: 0.40
groups:
-
name: Templates/Power
diff --git a/templates/power/apc/apc_ups_smart_2200_rm_snmp/README.md b/templates/power/apc/apc_ups_smart_2200_rm_snmp/README.md
index 97131c01d87..221c05d3378 100644
--- a/templates/power/apc/apc_ups_smart_2200_rm_snmp/README.md
+++ b/templates/power/apc/apc_ups_smart_2200_rm_snmp/README.md
@@ -53,7 +53,7 @@ There are no template links in this template.
|----|-----------|----|----|
|Input phases discovery |<p>The input phase identifier. OID upsPhaseInputPhaseIndex.1.1</p> |SNMP |input.phases.discovery |
|Output phases discovery |<p>The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1</p> |SNMP |output.phases.discovery |
-|External battery packs discovery | |SNMP |battery.packs.discovery<p>**Filter**:</p>AND <p>- A: {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`</p> |
+|External battery packs discovery |<p>-</p> |SNMP |battery.packs.discovery<p>**Filter**:</p>AND <p>- {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`</p> |
|External bad battery packs discovery |<p>Discovery of the number of external defective battery packs.</p> |SNMP |battery.packs.bad.discovery |
|External sensor port 1 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor1.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR1_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
|External sensor port 2 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor2.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR2_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
@@ -112,29 +112,29 @@ There are no template links in this template.
|System name has changed (new name: {ITEM.VALUE}) |<p>System name has changed. Ack to close.</p> |`last(/APC Smart-UPS 2200 RM SNMP/system.name[sysName.0],#1)<>last(/APC Smart-UPS 2200 RM SNMP/system.name[sysName.0],#2) and length(last(/APC Smart-UPS 2200 RM SNMP/system.name[sysName.0]))>0` |INFO |<p>Manual close: YES</p> |
|Battery has an internal error condition |<p>A battery installed has an internal error condition.</p> |`last(/APC Smart-UPS 2200 RM SNMP/battery.status[upsBasicBatteryStatus])=4` |AVERAGE | |
|Battery is Low |<p>The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.</p> |`last(/APC Smart-UPS 2200 RM SNMP/battery.status[upsBasicBatteryStatus])=3` |AVERAGE | |
-|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) | |`last(/APC Smart-UPS 2200 RM SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
+|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) |<p>-</p> |`last(/APC Smart-UPS 2200 RM SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
|Battery needs replacement |<p>A battery installed has an internal error condition.</p> |`last(/APC Smart-UPS 2200 RM SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2` |HIGH | |
-|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC Smart-UPS 2200 RM SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
-|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS 2200 RM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS 2200 RM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS 2200 RM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
-|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) | |`min(/APC Smart-UPS 2200 RM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS 2200 RM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC Smart-UPS 2200 RM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
+|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS 2200 RM SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS 2200 RM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS 2200 RM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS 2200 RM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
+|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS 2200 RM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS 2200 RM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC Smart-UPS 2200 RM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
|Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD}) |<p>A battery installed has an internal error condition.</p> |`min(/APC Smart-UPS 2200 RM SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}` |HIGH | |
-|UPS is Timed Sleeping | |`last(/APC Smart-UPS 2200 RM SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | |
-|UPS is Switched Bypass | |`last(/APC Smart-UPS 2200 RM SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | |
-|UPS is Software Bypass | |`last(/APC Smart-UPS 2200 RM SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | |
-|UPS is Sleeping Until Power Return | |`last(/APC Smart-UPS 2200 RM SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | |
-|UPS is Rebooting | |`last(/APC Smart-UPS 2200 RM SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | |
-|UPS is On Smart Trim | |`last(/APC Smart-UPS 2200 RM SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | |
-|UPS is on Smart Boost | |`last(/APC Smart-UPS 2200 RM SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | |
-|UPS is on battery | |`last(/APC Smart-UPS 2200 RM SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | |
-|UPS is Off | |`last(/APC Smart-UPS 2200 RM SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | |
-|UPS is Emergency Static Bypass | |`last(/APC Smart-UPS 2200 RM SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | |
-|UPS is Hardware Failure Bypass | |`last(/APC Smart-UPS 2200 RM SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | |
+|UPS is Timed Sleeping |<p>-</p> |`last(/APC Smart-UPS 2200 RM SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | |
+|UPS is Switched Bypass |<p>-</p> |`last(/APC Smart-UPS 2200 RM SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | |
+|UPS is Software Bypass |<p>-</p> |`last(/APC Smart-UPS 2200 RM SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | |
+|UPS is Sleeping Until Power Return |<p>-</p> |`last(/APC Smart-UPS 2200 RM SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | |
+|UPS is Rebooting |<p>-</p> |`last(/APC Smart-UPS 2200 RM SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | |
+|UPS is On Smart Trim |<p>-</p> |`last(/APC Smart-UPS 2200 RM SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | |
+|UPS is on Smart Boost |<p>-</p> |`last(/APC Smart-UPS 2200 RM SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | |
+|UPS is on battery |<p>-</p> |`last(/APC Smart-UPS 2200 RM SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | |
+|UPS is Off |<p>-</p> |`last(/APC Smart-UPS 2200 RM SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | |
+|UPS is Emergency Static Bypass |<p>-</p> |`last(/APC Smart-UPS 2200 RM SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | |
+|UPS is Hardware Failure Bypass |<p>-</p> |`last(/APC Smart-UPS 2200 RM SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | |
|{HOST.NAME} has been restarted (uptime < 10m) |<p>Uptime is less than 10 minutes</p> |`last(/APC Smart-UPS 2200 RM SNMP/system.uptime[sysUpTime.0])<10m` |WARNING |<p>Manual close: YES</p><p>**Depends on**:</p><p>- No SNMP data collection</p> |
|No SNMP data collection |<p>SNMP is not available for polling. Please check device connectivity and SNMP settings.</p> |`max(/APC Smart-UPS 2200 RM SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0` |WARNING | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS 2200 RM SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS 2200 RM SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS 2200 RM SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS 2200 RM SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS 2200 RM SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS 2200 RM SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS 2200 RM SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS 2200 RM SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |<p>The battery cartridge status:</p><p>bit 0 Disconnected</p><p>bit 1 Overvoltage</p><p>bit 2 NeedsReplacement</p><p>bit 3 OvertemperatureCritical</p><p>bit 4 Charger</p><p>bit 5 TemperatureSensor</p><p>bit 6 BusSoftStart</p><p>bit 7 OvertemperatureWarning</p><p>bit 8 GeneralError</p><p>bit 9 Communication</p><p>bit 10 DisconnectedFrame</p><p>bit 11 FirmwareMismatch</p> |`find(/APC Smart-UPS 2200 RM SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0` |WARNING | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC Smart-UPS 2200 RM SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS 2200 RM SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |<p>The battery cartridge health.</p><p> bit 0 Battery lifetime okay</p><p> bit 1 Battery lifetime near end, order replacement cartridge</p><p> bit 2 Battery lifetime exceeded, replace battery</p><p> bit 3 Battery lifetime near end acknowledged, order replacement cartridge</p><p> bit 4 Battery lifetime exceeded acknowledged, replace battery</p><p> bit 5 Battery measured lifetime near end, order replacement cartridge</p><p> bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge</p> |`find(/APC Smart-UPS 2200 RM SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1` |WARNING | |
|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`last(/APC Smart-UPS 2200 RM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4` |INFO | |
|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`last(/APC Smart-UPS 2200 RM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2` |AVERAGE | |
diff --git a/templates/power/apc/apc_ups_smart_2200_rm_snmp/template_power_apc_ups_smart_2200_rm_snmp.yaml b/templates/power/apc/apc_ups_smart_2200_rm_snmp/template_power_apc_ups_smart_2200_rm_snmp.yaml
index 449e59f7570..f55b41a23c4 100644
--- a/templates/power/apc/apc_ups_smart_2200_rm_snmp/template_power_apc_ups_smart_2200_rm_snmp.yaml
+++ b/templates/power/apc/apc_ups_smart_2200_rm_snmp/template_power_apc_ups_smart_2200_rm_snmp.yaml
@@ -1,6 +1,6 @@
zabbix_export:
version: '5.4'
- date: '2021-10-28T06:44:04Z'
+ date: '2021-12-20T07:09:58Z'
groups:
-
uuid: 3dcd5bbe90534f9e8eb5c2d53756af63
@@ -19,7 +19,7 @@ zabbix_export:
You can discuss this template or leave feedback on our forum https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups
- Template tooling version used: 0.39
+ Template tooling version used: 0.40
groups:
-
name: Templates/Power
diff --git a/templates/power/apc/apc_ups_smart_3000_xlm_snmp/README.md b/templates/power/apc/apc_ups_smart_3000_xlm_snmp/README.md
index 99fc491b771..81cddf61696 100644
--- a/templates/power/apc/apc_ups_smart_3000_xlm_snmp/README.md
+++ b/templates/power/apc/apc_ups_smart_3000_xlm_snmp/README.md
@@ -53,7 +53,7 @@ There are no template links in this template.
|----|-----------|----|----|
|Input phases discovery |<p>The input phase identifier. OID upsPhaseInputPhaseIndex.1.1</p> |SNMP |input.phases.discovery |
|Output phases discovery |<p>The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1</p> |SNMP |output.phases.discovery |
-|External battery packs discovery | |SNMP |battery.packs.discovery<p>**Filter**:</p>AND <p>- A: {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`</p> |
+|External battery packs discovery |<p>-</p> |SNMP |battery.packs.discovery<p>**Filter**:</p>AND <p>- {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`</p> |
|External bad battery packs discovery |<p>Discovery of the number of external defective battery packs.</p> |SNMP |battery.packs.bad.discovery |
|External sensor port 1 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor1.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR1_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
|External sensor port 2 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor2.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR2_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
@@ -112,29 +112,29 @@ There are no template links in this template.
|System name has changed (new name: {ITEM.VALUE}) |<p>System name has changed. Ack to close.</p> |`last(/APC Smart-UPS 3000 XLM SNMP/system.name[sysName.0],#1)<>last(/APC Smart-UPS 3000 XLM SNMP/system.name[sysName.0],#2) and length(last(/APC Smart-UPS 3000 XLM SNMP/system.name[sysName.0]))>0` |INFO |<p>Manual close: YES</p> |
|Battery has an internal error condition |<p>A battery installed has an internal error condition.</p> |`last(/APC Smart-UPS 3000 XLM SNMP/battery.status[upsBasicBatteryStatus])=4` |AVERAGE | |
|Battery is Low |<p>The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.</p> |`last(/APC Smart-UPS 3000 XLM SNMP/battery.status[upsBasicBatteryStatus])=3` |AVERAGE | |
-|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) | |`last(/APC Smart-UPS 3000 XLM SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
+|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) |<p>-</p> |`last(/APC Smart-UPS 3000 XLM SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
|Battery needs replacement |<p>A battery installed has an internal error condition.</p> |`last(/APC Smart-UPS 3000 XLM SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2` |HIGH | |
-|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC Smart-UPS 3000 XLM SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
-|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS 3000 XLM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS 3000 XLM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS 3000 XLM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
-|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) | |`min(/APC Smart-UPS 3000 XLM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS 3000 XLM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC Smart-UPS 3000 XLM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
+|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS 3000 XLM SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS 3000 XLM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS 3000 XLM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS 3000 XLM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
+|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS 3000 XLM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS 3000 XLM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC Smart-UPS 3000 XLM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
|Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD}) |<p>A battery installed has an internal error condition.</p> |`min(/APC Smart-UPS 3000 XLM SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}` |HIGH | |
-|UPS is Timed Sleeping | |`last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | |
-|UPS is Switched Bypass | |`last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | |
-|UPS is Software Bypass | |`last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | |
-|UPS is Sleeping Until Power Return | |`last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | |
-|UPS is Rebooting | |`last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | |
-|UPS is On Smart Trim | |`last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | |
-|UPS is on Smart Boost | |`last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | |
-|UPS is on battery | |`last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | |
-|UPS is Off | |`last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | |
-|UPS is Emergency Static Bypass | |`last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | |
-|UPS is Hardware Failure Bypass | |`last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | |
+|UPS is Timed Sleeping |<p>-</p> |`last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | |
+|UPS is Switched Bypass |<p>-</p> |`last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | |
+|UPS is Software Bypass |<p>-</p> |`last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | |
+|UPS is Sleeping Until Power Return |<p>-</p> |`last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | |
+|UPS is Rebooting |<p>-</p> |`last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | |
+|UPS is On Smart Trim |<p>-</p> |`last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | |
+|UPS is on Smart Boost |<p>-</p> |`last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | |
+|UPS is on battery |<p>-</p> |`last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | |
+|UPS is Off |<p>-</p> |`last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | |
+|UPS is Emergency Static Bypass |<p>-</p> |`last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | |
+|UPS is Hardware Failure Bypass |<p>-</p> |`last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | |
|{HOST.NAME} has been restarted (uptime < 10m) |<p>Uptime is less than 10 minutes</p> |`last(/APC Smart-UPS 3000 XLM SNMP/system.uptime[sysUpTime.0])<10m` |WARNING |<p>Manual close: YES</p><p>**Depends on**:</p><p>- No SNMP data collection</p> |
|No SNMP data collection |<p>SNMP is not available for polling. Please check device connectivity and SNMP settings.</p> |`max(/APC Smart-UPS 3000 XLM SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0` |WARNING | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS 3000 XLM SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS 3000 XLM SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS 3000 XLM SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS 3000 XLM SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS 3000 XLM SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS 3000 XLM SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS 3000 XLM SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS 3000 XLM SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |<p>The battery cartridge status:</p><p>bit 0 Disconnected</p><p>bit 1 Overvoltage</p><p>bit 2 NeedsReplacement</p><p>bit 3 OvertemperatureCritical</p><p>bit 4 Charger</p><p>bit 5 TemperatureSensor</p><p>bit 6 BusSoftStart</p><p>bit 7 OvertemperatureWarning</p><p>bit 8 GeneralError</p><p>bit 9 Communication</p><p>bit 10 DisconnectedFrame</p><p>bit 11 FirmwareMismatch</p> |`find(/APC Smart-UPS 3000 XLM SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0` |WARNING | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC Smart-UPS 3000 XLM SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS 3000 XLM SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |<p>The battery cartridge health.</p><p> bit 0 Battery lifetime okay</p><p> bit 1 Battery lifetime near end, order replacement cartridge</p><p> bit 2 Battery lifetime exceeded, replace battery</p><p> bit 3 Battery lifetime near end acknowledged, order replacement cartridge</p><p> bit 4 Battery lifetime exceeded acknowledged, replace battery</p><p> bit 5 Battery measured lifetime near end, order replacement cartridge</p><p> bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge</p> |`find(/APC Smart-UPS 3000 XLM SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1` |WARNING | |
|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`last(/APC Smart-UPS 3000 XLM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4` |INFO | |
|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`last(/APC Smart-UPS 3000 XLM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2` |AVERAGE | |
diff --git a/templates/power/apc/apc_ups_smart_3000_xlm_snmp/template_power_apc_ups_smart_3000_xlm_snmp.yaml b/templates/power/apc/apc_ups_smart_3000_xlm_snmp/template_power_apc_ups_smart_3000_xlm_snmp.yaml
index c7cce325dfc..ed0882741da 100644
--- a/templates/power/apc/apc_ups_smart_3000_xlm_snmp/template_power_apc_ups_smart_3000_xlm_snmp.yaml
+++ b/templates/power/apc/apc_ups_smart_3000_xlm_snmp/template_power_apc_ups_smart_3000_xlm_snmp.yaml
@@ -1,6 +1,6 @@
zabbix_export:
version: '5.4'
- date: '2021-10-28T06:43:57Z'
+ date: '2021-12-20T07:09:59Z'
groups:
-
uuid: 3dcd5bbe90534f9e8eb5c2d53756af63
@@ -19,7 +19,7 @@ zabbix_export:
You can discuss this template or leave feedback on our forum https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups
- Template tooling version used: 0.39
+ Template tooling version used: 0.40
groups:
-
name: Templates/Power
diff --git a/templates/power/apc/apc_ups_smart_rt_1000_rm_xl_snmp/README.md b/templates/power/apc/apc_ups_smart_rt_1000_rm_xl_snmp/README.md
index f7b7935cd73..14f57d92efc 100644
--- a/templates/power/apc/apc_ups_smart_rt_1000_rm_xl_snmp/README.md
+++ b/templates/power/apc/apc_ups_smart_rt_1000_rm_xl_snmp/README.md
@@ -53,7 +53,7 @@ There are no template links in this template.
|----|-----------|----|----|
|Input phases discovery |<p>The input phase identifier. OID upsPhaseInputPhaseIndex.1.1</p> |SNMP |input.phases.discovery |
|Output phases discovery |<p>The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1</p> |SNMP |output.phases.discovery |
-|External battery packs discovery | |SNMP |battery.packs.discovery<p>**Filter**:</p>AND <p>- A: {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`</p> |
+|External battery packs discovery |<p>-</p> |SNMP |battery.packs.discovery<p>**Filter**:</p>AND <p>- {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`</p> |
|External bad battery packs discovery |<p>Discovery of the number of external defective battery packs.</p> |SNMP |battery.packs.bad.discovery |
|External sensor port 1 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor1.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR1_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
|External sensor port 2 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor2.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR2_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
@@ -112,29 +112,29 @@ There are no template links in this template.
|System name has changed (new name: {ITEM.VALUE}) |<p>System name has changed. Ack to close.</p> |`last(/APC Smart-UPS RT 1000 RM XL SNMP/system.name[sysName.0],#1)<>last(/APC Smart-UPS RT 1000 RM XL SNMP/system.name[sysName.0],#2) and length(last(/APC Smart-UPS RT 1000 RM XL SNMP/system.name[sysName.0]))>0` |INFO |<p>Manual close: YES</p> |
|Battery has an internal error condition |<p>A battery installed has an internal error condition.</p> |`last(/APC Smart-UPS RT 1000 RM XL SNMP/battery.status[upsBasicBatteryStatus])=4` |AVERAGE | |
|Battery is Low |<p>The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.</p> |`last(/APC Smart-UPS RT 1000 RM XL SNMP/battery.status[upsBasicBatteryStatus])=3` |AVERAGE | |
-|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) | |`last(/APC Smart-UPS RT 1000 RM XL SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
+|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) |<p>-</p> |`last(/APC Smart-UPS RT 1000 RM XL SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
|Battery needs replacement |<p>A battery installed has an internal error condition.</p> |`last(/APC Smart-UPS RT 1000 RM XL SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2` |HIGH | |
-|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC Smart-UPS RT 1000 RM XL SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
-|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS RT 1000 RM XL SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS RT 1000 RM XL SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS RT 1000 RM XL SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
-|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) | |`min(/APC Smart-UPS RT 1000 RM XL SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS RT 1000 RM XL SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC Smart-UPS RT 1000 RM XL SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
+|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS RT 1000 RM XL SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS RT 1000 RM XL SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS RT 1000 RM XL SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS RT 1000 RM XL SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
+|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS RT 1000 RM XL SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS RT 1000 RM XL SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC Smart-UPS RT 1000 RM XL SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
|Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD}) |<p>A battery installed has an internal error condition.</p> |`min(/APC Smart-UPS RT 1000 RM XL SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}` |HIGH | |
-|UPS is Timed Sleeping | |`last(/APC Smart-UPS RT 1000 RM XL SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | |
-|UPS is Switched Bypass | |`last(/APC Smart-UPS RT 1000 RM XL SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | |
-|UPS is Software Bypass | |`last(/APC Smart-UPS RT 1000 RM XL SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | |
-|UPS is Sleeping Until Power Return | |`last(/APC Smart-UPS RT 1000 RM XL SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | |
-|UPS is Rebooting | |`last(/APC Smart-UPS RT 1000 RM XL SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | |
-|UPS is On Smart Trim | |`last(/APC Smart-UPS RT 1000 RM XL SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | |
-|UPS is on Smart Boost | |`last(/APC Smart-UPS RT 1000 RM XL SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | |
-|UPS is on battery | |`last(/APC Smart-UPS RT 1000 RM XL SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | |
-|UPS is Off | |`last(/APC Smart-UPS RT 1000 RM XL SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | |
-|UPS is Emergency Static Bypass | |`last(/APC Smart-UPS RT 1000 RM XL SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | |
-|UPS is Hardware Failure Bypass | |`last(/APC Smart-UPS RT 1000 RM XL SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | |
+|UPS is Timed Sleeping |<p>-</p> |`last(/APC Smart-UPS RT 1000 RM XL SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | |
+|UPS is Switched Bypass |<p>-</p> |`last(/APC Smart-UPS RT 1000 RM XL SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | |
+|UPS is Software Bypass |<p>-</p> |`last(/APC Smart-UPS RT 1000 RM XL SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | |
+|UPS is Sleeping Until Power Return |<p>-</p> |`last(/APC Smart-UPS RT 1000 RM XL SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | |
+|UPS is Rebooting |<p>-</p> |`last(/APC Smart-UPS RT 1000 RM XL SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | |
+|UPS is On Smart Trim |<p>-</p> |`last(/APC Smart-UPS RT 1000 RM XL SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | |
+|UPS is on Smart Boost |<p>-</p> |`last(/APC Smart-UPS RT 1000 RM XL SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | |
+|UPS is on battery |<p>-</p> |`last(/APC Smart-UPS RT 1000 RM XL SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | |
+|UPS is Off |<p>-</p> |`last(/APC Smart-UPS RT 1000 RM XL SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | |
+|UPS is Emergency Static Bypass |<p>-</p> |`last(/APC Smart-UPS RT 1000 RM XL SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | |
+|UPS is Hardware Failure Bypass |<p>-</p> |`last(/APC Smart-UPS RT 1000 RM XL SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | |
|{HOST.NAME} has been restarted (uptime < 10m) |<p>Uptime is less than 10 minutes</p> |`last(/APC Smart-UPS RT 1000 RM XL SNMP/system.uptime[sysUpTime.0])<10m` |WARNING |<p>Manual close: YES</p><p>**Depends on**:</p><p>- No SNMP data collection</p> |
|No SNMP data collection |<p>SNMP is not available for polling. Please check device connectivity and SNMP settings.</p> |`max(/APC Smart-UPS RT 1000 RM XL SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0` |WARNING | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS RT 1000 RM XL SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS RT 1000 RM XL SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS RT 1000 RM XL SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS RT 1000 RM XL SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS RT 1000 RM XL SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS RT 1000 RM XL SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS RT 1000 RM XL SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS RT 1000 RM XL SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |<p>The battery cartridge status:</p><p>bit 0 Disconnected</p><p>bit 1 Overvoltage</p><p>bit 2 NeedsReplacement</p><p>bit 3 OvertemperatureCritical</p><p>bit 4 Charger</p><p>bit 5 TemperatureSensor</p><p>bit 6 BusSoftStart</p><p>bit 7 OvertemperatureWarning</p><p>bit 8 GeneralError</p><p>bit 9 Communication</p><p>bit 10 DisconnectedFrame</p><p>bit 11 FirmwareMismatch</p> |`find(/APC Smart-UPS RT 1000 RM XL SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0` |WARNING | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC Smart-UPS RT 1000 RM XL SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS RT 1000 RM XL SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |<p>The battery cartridge health.</p><p> bit 0 Battery lifetime okay</p><p> bit 1 Battery lifetime near end, order replacement cartridge</p><p> bit 2 Battery lifetime exceeded, replace battery</p><p> bit 3 Battery lifetime near end acknowledged, order replacement cartridge</p><p> bit 4 Battery lifetime exceeded acknowledged, replace battery</p><p> bit 5 Battery measured lifetime near end, order replacement cartridge</p><p> bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge</p> |`find(/APC Smart-UPS RT 1000 RM XL SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1` |WARNING | |
|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`last(/APC Smart-UPS RT 1000 RM XL SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4` |INFO | |
|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`last(/APC Smart-UPS RT 1000 RM XL SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2` |AVERAGE | |
diff --git a/templates/power/apc/apc_ups_smart_rt_1000_rm_xl_snmp/template_power_apc_ups_smart_rt_1000_rm_xl_snmp.yaml b/templates/power/apc/apc_ups_smart_rt_1000_rm_xl_snmp/template_power_apc_ups_smart_rt_1000_rm_xl_snmp.yaml
index cb715efaf9b..42d84a83d80 100644
--- a/templates/power/apc/apc_ups_smart_rt_1000_rm_xl_snmp/template_power_apc_ups_smart_rt_1000_rm_xl_snmp.yaml
+++ b/templates/power/apc/apc_ups_smart_rt_1000_rm_xl_snmp/template_power_apc_ups_smart_rt_1000_rm_xl_snmp.yaml
@@ -1,6 +1,6 @@
zabbix_export:
version: '5.4'
- date: '2021-10-28T06:44:04Z'
+ date: '2021-12-20T07:10:00Z'
groups:
-
uuid: 3dcd5bbe90534f9e8eb5c2d53756af63
@@ -19,7 +19,7 @@ zabbix_export:
You can discuss this template or leave feedback on our forum https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups
- Template tooling version used: 0.39
+ Template tooling version used: 0.40
groups:
-
name: Templates/Power
diff --git a/templates/power/apc/apc_ups_smart_rt_1000_xl_snmp/README.md b/templates/power/apc/apc_ups_smart_rt_1000_xl_snmp/README.md
index 7f922b0bcb8..b5f81d772a4 100644
--- a/templates/power/apc/apc_ups_smart_rt_1000_xl_snmp/README.md
+++ b/templates/power/apc/apc_ups_smart_rt_1000_xl_snmp/README.md
@@ -53,7 +53,7 @@ There are no template links in this template.
|----|-----------|----|----|
|Input phases discovery |<p>The input phase identifier. OID upsPhaseInputPhaseIndex.1.1</p> |SNMP |input.phases.discovery |
|Output phases discovery |<p>The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1</p> |SNMP |output.phases.discovery |
-|External battery packs discovery | |SNMP |battery.packs.discovery<p>**Filter**:</p>AND <p>- A: {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`</p> |
+|External battery packs discovery |<p>-</p> |SNMP |battery.packs.discovery<p>**Filter**:</p>AND <p>- {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`</p> |
|External bad battery packs discovery |<p>Discovery of the number of external defective battery packs.</p> |SNMP |battery.packs.bad.discovery |
|External sensor port 1 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor1.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR1_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
|External sensor port 2 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor2.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR2_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
@@ -112,29 +112,29 @@ There are no template links in this template.
|System name has changed (new name: {ITEM.VALUE}) |<p>System name has changed. Ack to close.</p> |`last(/APC Smart-UPS RT 1000 XL SNMP/system.name[sysName.0],#1)<>last(/APC Smart-UPS RT 1000 XL SNMP/system.name[sysName.0],#2) and length(last(/APC Smart-UPS RT 1000 XL SNMP/system.name[sysName.0]))>0` |INFO |<p>Manual close: YES</p> |
|Battery has an internal error condition |<p>A battery installed has an internal error condition.</p> |`last(/APC Smart-UPS RT 1000 XL SNMP/battery.status[upsBasicBatteryStatus])=4` |AVERAGE | |
|Battery is Low |<p>The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.</p> |`last(/APC Smart-UPS RT 1000 XL SNMP/battery.status[upsBasicBatteryStatus])=3` |AVERAGE | |
-|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) | |`last(/APC Smart-UPS RT 1000 XL SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
+|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) |<p>-</p> |`last(/APC Smart-UPS RT 1000 XL SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
|Battery needs replacement |<p>A battery installed has an internal error condition.</p> |`last(/APC Smart-UPS RT 1000 XL SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2` |HIGH | |
-|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC Smart-UPS RT 1000 XL SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
-|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS RT 1000 XL SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS RT 1000 XL SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS RT 1000 XL SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
-|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) | |`min(/APC Smart-UPS RT 1000 XL SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS RT 1000 XL SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC Smart-UPS RT 1000 XL SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
+|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS RT 1000 XL SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS RT 1000 XL SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS RT 1000 XL SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS RT 1000 XL SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
+|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS RT 1000 XL SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS RT 1000 XL SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC Smart-UPS RT 1000 XL SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
|Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD}) |<p>A battery installed has an internal error condition.</p> |`min(/APC Smart-UPS RT 1000 XL SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}` |HIGH | |
-|UPS is Timed Sleeping | |`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | |
-|UPS is Switched Bypass | |`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | |
-|UPS is Software Bypass | |`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | |
-|UPS is Sleeping Until Power Return | |`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | |
-|UPS is Rebooting | |`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | |
-|UPS is On Smart Trim | |`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | |
-|UPS is on Smart Boost | |`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | |
-|UPS is on battery | |`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | |
-|UPS is Off | |`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | |
-|UPS is Emergency Static Bypass | |`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | |
-|UPS is Hardware Failure Bypass | |`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | |
+|UPS is Timed Sleeping |<p>-</p> |`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | |
+|UPS is Switched Bypass |<p>-</p> |`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | |
+|UPS is Software Bypass |<p>-</p> |`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | |
+|UPS is Sleeping Until Power Return |<p>-</p> |`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | |
+|UPS is Rebooting |<p>-</p> |`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | |
+|UPS is On Smart Trim |<p>-</p> |`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | |
+|UPS is on Smart Boost |<p>-</p> |`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | |
+|UPS is on battery |<p>-</p> |`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | |
+|UPS is Off |<p>-</p> |`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | |
+|UPS is Emergency Static Bypass |<p>-</p> |`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | |
+|UPS is Hardware Failure Bypass |<p>-</p> |`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | |
|{HOST.NAME} has been restarted (uptime < 10m) |<p>Uptime is less than 10 minutes</p> |`last(/APC Smart-UPS RT 1000 XL SNMP/system.uptime[sysUpTime.0])<10m` |WARNING |<p>Manual close: YES</p><p>**Depends on**:</p><p>- No SNMP data collection</p> |
|No SNMP data collection |<p>SNMP is not available for polling. Please check device connectivity and SNMP settings.</p> |`max(/APC Smart-UPS RT 1000 XL SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0` |WARNING | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS RT 1000 XL SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS RT 1000 XL SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS RT 1000 XL SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS RT 1000 XL SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS RT 1000 XL SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS RT 1000 XL SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS RT 1000 XL SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS RT 1000 XL SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |<p>The battery cartridge status:</p><p>bit 0 Disconnected</p><p>bit 1 Overvoltage</p><p>bit 2 NeedsReplacement</p><p>bit 3 OvertemperatureCritical</p><p>bit 4 Charger</p><p>bit 5 TemperatureSensor</p><p>bit 6 BusSoftStart</p><p>bit 7 OvertemperatureWarning</p><p>bit 8 GeneralError</p><p>bit 9 Communication</p><p>bit 10 DisconnectedFrame</p><p>bit 11 FirmwareMismatch</p> |`find(/APC Smart-UPS RT 1000 XL SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0` |WARNING | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC Smart-UPS RT 1000 XL SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS RT 1000 XL SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |<p>The battery cartridge health.</p><p> bit 0 Battery lifetime okay</p><p> bit 1 Battery lifetime near end, order replacement cartridge</p><p> bit 2 Battery lifetime exceeded, replace battery</p><p> bit 3 Battery lifetime near end acknowledged, order replacement cartridge</p><p> bit 4 Battery lifetime exceeded acknowledged, replace battery</p><p> bit 5 Battery measured lifetime near end, order replacement cartridge</p><p> bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge</p> |`find(/APC Smart-UPS RT 1000 XL SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1` |WARNING | |
|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`last(/APC Smart-UPS RT 1000 XL SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4` |INFO | |
|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`last(/APC Smart-UPS RT 1000 XL SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2` |AVERAGE | |
diff --git a/templates/power/apc/apc_ups_smart_rt_1000_xl_snmp/template_power_apc_ups_smart_rt_1000_xl_snmp.yaml b/templates/power/apc/apc_ups_smart_rt_1000_xl_snmp/template_power_apc_ups_smart_rt_1000_xl_snmp.yaml
index a324ef3e1d6..e4b163b263a 100644
--- a/templates/power/apc/apc_ups_smart_rt_1000_xl_snmp/template_power_apc_ups_smart_rt_1000_xl_snmp.yaml
+++ b/templates/power/apc/apc_ups_smart_rt_1000_xl_snmp/template_power_apc_ups_smart_rt_1000_xl_snmp.yaml
@@ -1,6 +1,6 @@
zabbix_export:
version: '5.4'
- date: '2021-10-28T06:44:01Z'
+ date: '2021-12-20T07:10:01Z'
groups:
-
uuid: 3dcd5bbe90534f9e8eb5c2d53756af63
@@ -19,7 +19,7 @@ zabbix_export:
You can discuss this template or leave feedback on our forum https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups
- Template tooling version used: 0.39
+ Template tooling version used: 0.40
groups:
-
name: Templates/Power
diff --git a/templates/power/apc/apc_ups_smart_srt_5000_snmp/README.md b/templates/power/apc/apc_ups_smart_srt_5000_snmp/README.md
index 9f2955669a5..64d5132f0cd 100644
--- a/templates/power/apc/apc_ups_smart_srt_5000_snmp/README.md
+++ b/templates/power/apc/apc_ups_smart_srt_5000_snmp/README.md
@@ -53,7 +53,7 @@ There are no template links in this template.
|----|-----------|----|----|
|Input phases discovery |<p>The input phase identifier. OID upsPhaseInputPhaseIndex.1.1</p> |SNMP |input.phases.discovery |
|Output phases discovery |<p>The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1</p> |SNMP |output.phases.discovery |
-|External battery packs discovery | |SNMP |battery.packs.discovery<p>**Filter**:</p>AND <p>- A: {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`</p> |
+|External battery packs discovery |<p>-</p> |SNMP |battery.packs.discovery<p>**Filter**:</p>AND <p>- {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`</p> |
|External bad battery packs discovery |<p>Discovery of the number of external defective battery packs.</p> |SNMP |battery.packs.bad.discovery |
|External sensor port 1 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor1.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR1_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
|External sensor port 2 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor2.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR2_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
@@ -112,29 +112,29 @@ There are no template links in this template.
|System name has changed (new name: {ITEM.VALUE}) |<p>System name has changed. Ack to close.</p> |`last(/APC Smart-UPS SRT 5000 SNMP/system.name[sysName.0],#1)<>last(/APC Smart-UPS SRT 5000 SNMP/system.name[sysName.0],#2) and length(last(/APC Smart-UPS SRT 5000 SNMP/system.name[sysName.0]))>0` |INFO |<p>Manual close: YES</p> |
|Battery has an internal error condition |<p>A battery installed has an internal error condition.</p> |`last(/APC Smart-UPS SRT 5000 SNMP/battery.status[upsBasicBatteryStatus])=4` |AVERAGE | |
|Battery is Low |<p>The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.</p> |`last(/APC Smart-UPS SRT 5000 SNMP/battery.status[upsBasicBatteryStatus])=3` |AVERAGE | |
-|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) | |`last(/APC Smart-UPS SRT 5000 SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
+|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) |<p>-</p> |`last(/APC Smart-UPS SRT 5000 SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
|Battery needs replacement |<p>A battery installed has an internal error condition.</p> |`last(/APC Smart-UPS SRT 5000 SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2` |HIGH | |
-|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC Smart-UPS SRT 5000 SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
-|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS SRT 5000 SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and ((min(/APC Smart-UPS SRT 5000 SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS SRT 5000 SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}))` |HIGH | |
-|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) | |`min(/APC Smart-UPS SRT 5000 SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and ((min(/APC Smart-UPS SRT 5000 SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC Smart-UPS SRT 5000 SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN}))` |HIGH | |
+|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS SRT 5000 SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS SRT 5000 SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and ((min(/APC Smart-UPS SRT 5000 SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS SRT 5000 SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}))` |HIGH | |
+|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS SRT 5000 SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and ((min(/APC Smart-UPS SRT 5000 SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC Smart-UPS SRT 5000 SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN}))` |HIGH | |
|Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD}) |<p>A battery installed has an internal error condition.</p> |`min(/APC Smart-UPS SRT 5000 SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}` |HIGH | |
-|UPS is Timed Sleeping | |`last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | |
-|UPS is Switched Bypass | |`last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | |
-|UPS is Software Bypass | |`last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | |
-|UPS is Sleeping Until Power Return | |`last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | |
-|UPS is Rebooting | |`last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | |
-|UPS is On Smart Trim | |`last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | |
-|UPS is on Smart Boost | |`last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | |
-|UPS is on battery | |`last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | |
-|UPS is Off | |`last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | |
-|UPS is Emergency Static Bypass | |`last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | |
-|UPS is Hardware Failure Bypass | |`last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | |
+|UPS is Timed Sleeping |<p>-</p> |`last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | |
+|UPS is Switched Bypass |<p>-</p> |`last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | |
+|UPS is Software Bypass |<p>-</p> |`last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | |
+|UPS is Sleeping Until Power Return |<p>-</p> |`last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | |
+|UPS is Rebooting |<p>-</p> |`last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | |
+|UPS is On Smart Trim |<p>-</p> |`last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | |
+|UPS is on Smart Boost |<p>-</p> |`last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | |
+|UPS is on battery |<p>-</p> |`last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | |
+|UPS is Off |<p>-</p> |`last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | |
+|UPS is Emergency Static Bypass |<p>-</p> |`last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | |
+|UPS is Hardware Failure Bypass |<p>-</p> |`last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | |
|{HOST.NAME} has been restarted (uptime < 10m) |<p>Uptime is less than 10 minutes</p> |`last(/APC Smart-UPS SRT 5000 SNMP/system.uptime[sysUpTime.0])<10m` |WARNING |<p>Manual close: YES</p><p>**Depends on**:</p><p>- No SNMP data collection</p> |
|No SNMP data collection |<p>SNMP is not available for polling. Please check device connectivity and SNMP settings.</p> |`max(/APC Smart-UPS SRT 5000 SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0` |WARNING | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS SRT 5000 SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS SRT 5000 SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS SRT 5000 SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS SRT 5000 SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS SRT 5000 SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS SRT 5000 SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS SRT 5000 SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS SRT 5000 SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |<p>The battery cartridge status:</p><p>bit 0 Disconnected</p><p>bit 1 Overvoltage</p><p>bit 2 NeedsReplacement</p><p>bit 3 OvertemperatureCritical</p><p>bit 4 Charger</p><p>bit 5 TemperatureSensor</p><p>bit 6 BusSoftStart</p><p>bit 7 OvertemperatureWarning</p><p>bit 8 GeneralError</p><p>bit 9 Communication</p><p>bit 10 DisconnectedFrame</p><p>bit 11 FirmwareMismatch</p> |`find(/APC Smart-UPS SRT 5000 SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0` |WARNING | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC Smart-UPS SRT 5000 SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS SRT 5000 SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |<p>The battery cartridge health.</p><p> bit 0 Battery lifetime okay</p><p> bit 1 Battery lifetime near end, order replacement cartridge</p><p> bit 2 Battery lifetime exceeded, replace battery</p><p> bit 3 Battery lifetime near end acknowledged, order replacement cartridge</p><p> bit 4 Battery lifetime exceeded acknowledged, replace battery</p><p> bit 5 Battery measured lifetime near end, order replacement cartridge</p><p> bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge</p> |`find(/APC Smart-UPS SRT 5000 SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1` |WARNING | |
|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`last(/APC Smart-UPS SRT 5000 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4` |INFO | |
|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`last(/APC Smart-UPS SRT 5000 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2` |AVERAGE | |
diff --git a/templates/power/apc/apc_ups_smart_srt_5000_snmp/template_power_apc_ups_smart_srt_5000_snmp.yaml b/templates/power/apc/apc_ups_smart_srt_5000_snmp/template_power_apc_ups_smart_srt_5000_snmp.yaml
index 46e73a985c3..84752ddd8f8 100644
--- a/templates/power/apc/apc_ups_smart_srt_5000_snmp/template_power_apc_ups_smart_srt_5000_snmp.yaml
+++ b/templates/power/apc/apc_ups_smart_srt_5000_snmp/template_power_apc_ups_smart_srt_5000_snmp.yaml
@@ -1,6 +1,6 @@
zabbix_export:
version: '5.4'
- date: '2021-10-28T06:44:02Z'
+ date: '2021-12-20T07:10:02Z'
groups:
-
uuid: 3dcd5bbe90534f9e8eb5c2d53756af63
@@ -19,7 +19,7 @@ zabbix_export:
You can discuss this template or leave feedback on our forum https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups
- Template tooling version used: 0.39
+ Template tooling version used: 0.40
groups:
-
name: Templates/Power
diff --git a/templates/power/apc/apc_ups_smart_srt_8000_snmp/README.md b/templates/power/apc/apc_ups_smart_srt_8000_snmp/README.md
index 676fc995a6f..811ba8f3c16 100644
--- a/templates/power/apc/apc_ups_smart_srt_8000_snmp/README.md
+++ b/templates/power/apc/apc_ups_smart_srt_8000_snmp/README.md
@@ -53,7 +53,7 @@ There are no template links in this template.
|----|-----------|----|----|
|Input phases discovery |<p>The input phase identifier. OID upsPhaseInputPhaseIndex.1.1</p> |SNMP |input.phases.discovery |
|Output phases discovery |<p>The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1</p> |SNMP |output.phases.discovery |
-|External battery packs discovery | |SNMP |battery.packs.discovery<p>**Filter**:</p>AND <p>- A: {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`</p> |
+|External battery packs discovery |<p>-</p> |SNMP |battery.packs.discovery<p>**Filter**:</p>AND <p>- {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`</p> |
|External bad battery packs discovery |<p>Discovery of the number of external defective battery packs.</p> |SNMP |battery.packs.bad.discovery |
|External sensor port 1 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor1.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR1_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
|External sensor port 2 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor2.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR2_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
@@ -112,29 +112,29 @@ There are no template links in this template.
|System name has changed (new name: {ITEM.VALUE}) |<p>System name has changed. Ack to close.</p> |`last(/APC Smart-UPS SRT 8000 SNMP/system.name[sysName.0],#1)<>last(/APC Smart-UPS SRT 8000 SNMP/system.name[sysName.0],#2) and length(last(/APC Smart-UPS SRT 8000 SNMP/system.name[sysName.0]))>0` |INFO |<p>Manual close: YES</p> |
|Battery has an internal error condition |<p>A battery installed has an internal error condition.</p> |`last(/APC Smart-UPS SRT 8000 SNMP/battery.status[upsBasicBatteryStatus])=4` |AVERAGE | |
|Battery is Low |<p>The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.</p> |`last(/APC Smart-UPS SRT 8000 SNMP/battery.status[upsBasicBatteryStatus])=3` |AVERAGE | |
-|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) | |`last(/APC Smart-UPS SRT 8000 SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
+|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) |<p>-</p> |`last(/APC Smart-UPS SRT 8000 SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
|Battery needs replacement |<p>A battery installed has an internal error condition.</p> |`last(/APC Smart-UPS SRT 8000 SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2` |HIGH | |
-|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC Smart-UPS SRT 8000 SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
-|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS SRT 8000 SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS SRT 8000 SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS SRT 8000 SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
-|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) | |`min(/APC Smart-UPS SRT 8000 SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS SRT 8000 SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC Smart-UPS SRT 8000 SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
+|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS SRT 8000 SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS SRT 8000 SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS SRT 8000 SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS SRT 8000 SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
+|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS SRT 8000 SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS SRT 8000 SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC Smart-UPS SRT 8000 SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
|Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD}) |<p>A battery installed has an internal error condition.</p> |`min(/APC Smart-UPS SRT 8000 SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}` |HIGH | |
-|UPS is Timed Sleeping | |`last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | |
-|UPS is Switched Bypass | |`last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | |
-|UPS is Software Bypass | |`last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | |
-|UPS is Sleeping Until Power Return | |`last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | |
-|UPS is Rebooting | |`last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | |
-|UPS is On Smart Trim | |`last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | |
-|UPS is on Smart Boost | |`last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | |
-|UPS is on battery | |`last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | |
-|UPS is Off | |`last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | |
-|UPS is Emergency Static Bypass | |`last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | |
-|UPS is Hardware Failure Bypass | |`last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | |
+|UPS is Timed Sleeping |<p>-</p> |`last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | |
+|UPS is Switched Bypass |<p>-</p> |`last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | |
+|UPS is Software Bypass |<p>-</p> |`last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | |
+|UPS is Sleeping Until Power Return |<p>-</p> |`last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | |
+|UPS is Rebooting |<p>-</p> |`last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | |
+|UPS is On Smart Trim |<p>-</p> |`last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | |
+|UPS is on Smart Boost |<p>-</p> |`last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | |
+|UPS is on battery |<p>-</p> |`last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | |
+|UPS is Off |<p>-</p> |`last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | |
+|UPS is Emergency Static Bypass |<p>-</p> |`last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | |
+|UPS is Hardware Failure Bypass |<p>-</p> |`last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | |
|{HOST.NAME} has been restarted (uptime < 10m) |<p>Uptime is less than 10 minutes</p> |`last(/APC Smart-UPS SRT 8000 SNMP/system.uptime[sysUpTime.0])<10m` |WARNING |<p>Manual close: YES</p><p>**Depends on**:</p><p>- No SNMP data collection</p> |
|No SNMP data collection |<p>SNMP is not available for polling. Please check device connectivity and SNMP settings.</p> |`max(/APC Smart-UPS SRT 8000 SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0` |WARNING | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS SRT 8000 SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS SRT 8000 SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS SRT 8000 SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS SRT 8000 SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS SRT 8000 SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS SRT 8000 SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS SRT 8000 SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS SRT 8000 SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |<p>The battery cartridge status:</p><p>bit 0 Disconnected</p><p>bit 1 Overvoltage</p><p>bit 2 NeedsReplacement</p><p>bit 3 OvertemperatureCritical</p><p>bit 4 Charger</p><p>bit 5 TemperatureSensor</p><p>bit 6 BusSoftStart</p><p>bit 7 OvertemperatureWarning</p><p>bit 8 GeneralError</p><p>bit 9 Communication</p><p>bit 10 DisconnectedFrame</p><p>bit 11 FirmwareMismatch</p> |`find(/APC Smart-UPS SRT 8000 SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0` |WARNING | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC Smart-UPS SRT 8000 SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) |<p>-</p> |`min(/APC Smart-UPS SRT 8000 SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |<p>The battery cartridge health.</p><p> bit 0 Battery lifetime okay</p><p> bit 1 Battery lifetime near end, order replacement cartridge</p><p> bit 2 Battery lifetime exceeded, replace battery</p><p> bit 3 Battery lifetime near end acknowledged, order replacement cartridge</p><p> bit 4 Battery lifetime exceeded acknowledged, replace battery</p><p> bit 5 Battery measured lifetime near end, order replacement cartridge</p><p> bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge</p> |`find(/APC Smart-UPS SRT 8000 SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1` |WARNING | |
|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`last(/APC Smart-UPS SRT 8000 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4` |INFO | |
|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`last(/APC Smart-UPS SRT 8000 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2` |AVERAGE | |
diff --git a/templates/power/apc/apc_ups_smart_srt_8000_snmp/template_power_apc_ups_smart_srt_8000_snmp.yaml b/templates/power/apc/apc_ups_smart_srt_8000_snmp/template_power_apc_ups_smart_srt_8000_snmp.yaml
index 59d59da772b..1103b4a1dce 100644
--- a/templates/power/apc/apc_ups_smart_srt_8000_snmp/template_power_apc_ups_smart_srt_8000_snmp.yaml
+++ b/templates/power/apc/apc_ups_smart_srt_8000_snmp/template_power_apc_ups_smart_srt_8000_snmp.yaml
@@ -1,6 +1,6 @@
zabbix_export:
version: '5.4'
- date: '2021-10-28T06:44:03Z'
+ date: '2021-12-20T07:10:03Z'
groups:
-
uuid: 3dcd5bbe90534f9e8eb5c2d53756af63
@@ -19,7 +19,7 @@ zabbix_export:
You can discuss this template or leave feedback on our forum https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups
- Template tooling version used: 0.39
+ Template tooling version used: 0.40
groups:
-
name: Templates/Power
diff --git a/templates/power/apc/apc_ups_snmp/README.md b/templates/power/apc/apc_ups_snmp/README.md
index 6237cd8b150..64d3f31cbcc 100644
--- a/templates/power/apc/apc_ups_snmp/README.md
+++ b/templates/power/apc/apc_ups_snmp/README.md
@@ -49,7 +49,7 @@ There are no template links in this template.
|----|-----------|----|----|
|Input phases discovery |<p>The input phase identifier. OID upsPhaseInputPhaseIndex.1.1</p> |SNMP |input.phases.discovery |
|Output phases discovery |<p>The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1</p> |SNMP |output.phases.discovery |
-|External battery packs discovery | |SNMP |battery.packs.discovery<p>**Filter**:</p>AND <p>- A: {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`</p> |
+|External battery packs discovery |<p>-</p> |SNMP |battery.packs.discovery<p>**Filter**:</p>AND <p>- {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`</p> |
|External bad battery packs discovery |<p>Discovery of the number of external defective battery packs.</p> |SNMP |battery.packs.bad.discovery |
|External sensor port 1 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor1.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR1_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
|External sensor port 2 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor2.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR2_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
@@ -108,29 +108,29 @@ There are no template links in this template.
|System name has changed (new name: {ITEM.VALUE}) |<p>System name has changed. Ack to close.</p> |`last(/APC UPS SNMP/system.name[sysName.0],#1)<>last(/APC UPS SNMP/system.name[sysName.0],#2) and length(last(/APC UPS SNMP/system.name[sysName.0]))>0` |INFO |<p>Manual close: YES</p> |
|Battery has an internal error condition |<p>A battery installed has an internal error condition.</p> |`last(/APC UPS SNMP/battery.status[upsBasicBatteryStatus])=4` |AVERAGE | |
|Battery is Low |<p>The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.</p> |`last(/APC UPS SNMP/battery.status[upsBasicBatteryStatus])=3` |AVERAGE | |
-|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) | |`last(/APC UPS SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
+|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) |<p>-</p> |`last(/APC UPS SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
|Battery needs replacement |<p>A battery installed has an internal error condition.</p> |`last(/APC UPS SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2` |HIGH | |
-|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC UPS SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
-|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC UPS SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC UPS SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
-|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) | |`min(/APC UPS SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC UPS SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC UPS SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
+|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) |<p>-</p> |`min(/APC UPS SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) |<p>-</p> |`min(/APC UPS SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC UPS SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
+|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) |<p>-</p> |`min(/APC UPS SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC UPS SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC UPS SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
|Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD}) |<p>A battery installed has an internal error condition.</p> |`min(/APC UPS SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}` |HIGH | |
-|UPS is Timed Sleeping | |`last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | |
-|UPS is Switched Bypass | |`last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | |
-|UPS is Software Bypass | |`last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | |
-|UPS is Sleeping Until Power Return | |`last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | |
-|UPS is Rebooting | |`last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | |
-|UPS is On Smart Trim | |`last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | |
-|UPS is on Smart Boost | |`last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | |
-|UPS is on battery | |`last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | |
-|UPS is Off | |`last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | |
-|UPS is Emergency Static Bypass | |`last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | |
-|UPS is Hardware Failure Bypass | |`last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | |
+|UPS is Timed Sleeping |<p>-</p> |`last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | |
+|UPS is Switched Bypass |<p>-</p> |`last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | |
+|UPS is Software Bypass |<p>-</p> |`last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | |
+|UPS is Sleeping Until Power Return |<p>-</p> |`last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | |
+|UPS is Rebooting |<p>-</p> |`last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | |
+|UPS is On Smart Trim |<p>-</p> |`last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | |
+|UPS is on Smart Boost |<p>-</p> |`last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | |
+|UPS is on battery |<p>-</p> |`last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | |
+|UPS is Off |<p>-</p> |`last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | |
+|UPS is Emergency Static Bypass |<p>-</p> |`last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | |
+|UPS is Hardware Failure Bypass |<p>-</p> |`last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | |
|{HOST.NAME} has been restarted (uptime < 10m) |<p>Uptime is less than 10 minutes</p> |`last(/APC UPS SNMP/system.uptime[sysUpTime.0])<10m` |WARNING |<p>Manual close: YES</p><p>**Depends on**:</p><p>- No SNMP data collection</p> |
|No SNMP data collection |<p>SNMP is not available for polling. Please check device connectivity and SNMP settings.</p> |`max(/APC UPS SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0` |WARNING | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC UPS SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC UPS SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) |<p>-</p> |`min(/APC UPS SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) |<p>-</p> |`min(/APC UPS SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |<p>The battery cartridge status:</p><p>bit 0 Disconnected</p><p>bit 1 Overvoltage</p><p>bit 2 NeedsReplacement</p><p>bit 3 OvertemperatureCritical</p><p>bit 4 Charger</p><p>bit 5 TemperatureSensor</p><p>bit 6 BusSoftStart</p><p>bit 7 OvertemperatureWarning</p><p>bit 8 GeneralError</p><p>bit 9 Communication</p><p>bit 10 DisconnectedFrame</p><p>bit 11 FirmwareMismatch</p> |`find(/APC UPS SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0` |WARNING | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC UPS SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) |<p>-</p> |`min(/APC UPS SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |<p>The battery cartridge health.</p><p> bit 0 Battery lifetime okay</p><p> bit 1 Battery lifetime near end, order replacement cartridge</p><p> bit 2 Battery lifetime exceeded, replace battery</p><p> bit 3 Battery lifetime near end acknowledged, order replacement cartridge</p><p> bit 4 Battery lifetime exceeded acknowledged, replace battery</p><p> bit 5 Battery measured lifetime near end, order replacement cartridge</p><p> bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge</p> |`find(/APC UPS SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1` |WARNING | |
|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`last(/APC UPS SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4` |INFO | |
|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`last(/APC UPS SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2` |AVERAGE | |
diff --git a/templates/power/apc/apc_ups_snmp/template_power_apc_ups_snmp.yaml b/templates/power/apc/apc_ups_snmp/template_power_apc_ups_snmp.yaml
index 61a9e49ba7c..644a302079b 100644
--- a/templates/power/apc/apc_ups_snmp/template_power_apc_ups_snmp.yaml
+++ b/templates/power/apc/apc_ups_snmp/template_power_apc_ups_snmp.yaml
@@ -1,6 +1,6 @@
zabbix_export:
version: '5.4'
- date: '2021-10-28T06:44:02Z'
+ date: '2021-12-20T07:10:04Z'
groups:
-
uuid: 3dcd5bbe90534f9e8eb5c2d53756af63
@@ -19,7 +19,7 @@ zabbix_export:
You can discuss this template or leave feedback on our forum https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups
- Template tooling version used: 0.39
+ Template tooling version used: 0.40
groups:
-
name: Templates/Power
@@ -1593,16 +1593,6 @@ zabbix_export:
value: '26'
newvalue: 'Charger Only'
-
- uuid: cbd3d7c999244cd6a44a8fc566533005
- name: 'Service state'
- mappings:
- -
- value: '0'
- newvalue: Down
- -
- value: '1'
- newvalue: Up
- -
uuid: 781c568d935d40f2a43951488cf2e046
name: zabbix.host.available
mappings:
diff --git a/templates/power/apc/apc_ups_symmetra_lx_snmp/README.md b/templates/power/apc/apc_ups_symmetra_lx_snmp/README.md
index 4e0530c46dd..cf9a96037d9 100644
--- a/templates/power/apc/apc_ups_symmetra_lx_snmp/README.md
+++ b/templates/power/apc/apc_ups_symmetra_lx_snmp/README.md
@@ -53,7 +53,7 @@ There are no template links in this template.
|----|-----------|----|----|
|Input phases discovery |<p>The input phase identifier. OID upsPhaseInputPhaseIndex.1.1</p> |SNMP |input.phases.discovery |
|Output phases discovery |<p>The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1</p> |SNMP |output.phases.discovery |
-|External battery packs discovery | |SNMP |battery.packs.discovery<p>**Filter**:</p>AND <p>- A: {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`</p> |
+|External battery packs discovery |<p>-</p> |SNMP |battery.packs.discovery<p>**Filter**:</p>AND <p>- {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`</p> |
|External bad battery packs discovery |<p>Discovery of the number of external defective battery packs.</p> |SNMP |battery.packs.bad.discovery |
|External sensor port 1 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor1.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR1_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
|External sensor port 2 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor2.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR2_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
@@ -112,29 +112,29 @@ There are no template links in this template.
|System name has changed (new name: {ITEM.VALUE}) |<p>System name has changed. Ack to close.</p> |`last(/APC UPS Symmetra LX SNMP/system.name[sysName.0],#1)<>last(/APC UPS Symmetra LX SNMP/system.name[sysName.0],#2) and length(last(/APC UPS Symmetra LX SNMP/system.name[sysName.0]))>0` |INFO |<p>Manual close: YES</p> |
|Battery has an internal error condition |<p>A battery installed has an internal error condition.</p> |`last(/APC UPS Symmetra LX SNMP/battery.status[upsBasicBatteryStatus])=4` |AVERAGE | |
|Battery is Low |<p>The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.</p> |`last(/APC UPS Symmetra LX SNMP/battery.status[upsBasicBatteryStatus])=3` |AVERAGE | |
-|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) | |`last(/APC UPS Symmetra LX SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
+|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) |<p>-</p> |`last(/APC UPS Symmetra LX SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
|Battery needs replacement |<p>A battery installed has an internal error condition.</p> |`last(/APC UPS Symmetra LX SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2` |HIGH | |
-|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra LX SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
-|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra LX SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC UPS Symmetra LX SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra LX SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
-|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra LX SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC UPS Symmetra LX SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC UPS Symmetra LX SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
+|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) |<p>-</p> |`min(/APC UPS Symmetra LX SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) |<p>-</p> |`min(/APC UPS Symmetra LX SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC UPS Symmetra LX SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra LX SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
+|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) |<p>-</p> |`min(/APC UPS Symmetra LX SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC UPS Symmetra LX SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC UPS Symmetra LX SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
|Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD}) |<p>A battery installed has an internal error condition.</p> |`min(/APC UPS Symmetra LX SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}` |HIGH | |
-|UPS is Timed Sleeping | |`last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | |
-|UPS is Switched Bypass | |`last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | |
-|UPS is Software Bypass | |`last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | |
-|UPS is Sleeping Until Power Return | |`last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | |
-|UPS is Rebooting | |`last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | |
-|UPS is On Smart Trim | |`last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | |
-|UPS is on Smart Boost | |`last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | |
-|UPS is on battery | |`last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | |
-|UPS is Off | |`last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | |
-|UPS is Emergency Static Bypass | |`last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | |
-|UPS is Hardware Failure Bypass | |`last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | |
+|UPS is Timed Sleeping |<p>-</p> |`last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | |
+|UPS is Switched Bypass |<p>-</p> |`last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | |
+|UPS is Software Bypass |<p>-</p> |`last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | |
+|UPS is Sleeping Until Power Return |<p>-</p> |`last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | |
+|UPS is Rebooting |<p>-</p> |`last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | |
+|UPS is On Smart Trim |<p>-</p> |`last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | |
+|UPS is on Smart Boost |<p>-</p> |`last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | |
+|UPS is on battery |<p>-</p> |`last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | |
+|UPS is Off |<p>-</p> |`last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | |
+|UPS is Emergency Static Bypass |<p>-</p> |`last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | |
+|UPS is Hardware Failure Bypass |<p>-</p> |`last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | |
|{HOST.NAME} has been restarted (uptime < 10m) |<p>Uptime is less than 10 minutes</p> |`last(/APC UPS Symmetra LX SNMP/system.uptime[sysUpTime.0])<10m` |WARNING |<p>Manual close: YES</p><p>**Depends on**:</p><p>- No SNMP data collection</p> |
|No SNMP data collection |<p>SNMP is not available for polling. Please check device connectivity and SNMP settings.</p> |`max(/APC UPS Symmetra LX SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0` |WARNING | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra LX SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra LX SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra LX SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra LX SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) |<p>-</p> |`min(/APC UPS Symmetra LX SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra LX SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) |<p>-</p> |`min(/APC UPS Symmetra LX SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra LX SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |<p>The battery cartridge status:</p><p>bit 0 Disconnected</p><p>bit 1 Overvoltage</p><p>bit 2 NeedsReplacement</p><p>bit 3 OvertemperatureCritical</p><p>bit 4 Charger</p><p>bit 5 TemperatureSensor</p><p>bit 6 BusSoftStart</p><p>bit 7 OvertemperatureWarning</p><p>bit 8 GeneralError</p><p>bit 9 Communication</p><p>bit 10 DisconnectedFrame</p><p>bit 11 FirmwareMismatch</p> |`find(/APC UPS Symmetra LX SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0` |WARNING | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra LX SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) |<p>-</p> |`min(/APC UPS Symmetra LX SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |<p>The battery cartridge health.</p><p> bit 0 Battery lifetime okay</p><p> bit 1 Battery lifetime near end, order replacement cartridge</p><p> bit 2 Battery lifetime exceeded, replace battery</p><p> bit 3 Battery lifetime near end acknowledged, order replacement cartridge</p><p> bit 4 Battery lifetime exceeded acknowledged, replace battery</p><p> bit 5 Battery measured lifetime near end, order replacement cartridge</p><p> bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge</p> |`find(/APC UPS Symmetra LX SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1` |WARNING | |
|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`last(/APC UPS Symmetra LX SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4` |INFO | |
|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`last(/APC UPS Symmetra LX SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2` |AVERAGE | |
diff --git a/templates/power/apc/apc_ups_symmetra_lx_snmp/template_power_apc_ups_symmetra_lx_snmp.yaml b/templates/power/apc/apc_ups_symmetra_lx_snmp/template_power_apc_ups_symmetra_lx_snmp.yaml
index c7e6136706d..f8c16352091 100644
--- a/templates/power/apc/apc_ups_symmetra_lx_snmp/template_power_apc_ups_symmetra_lx_snmp.yaml
+++ b/templates/power/apc/apc_ups_symmetra_lx_snmp/template_power_apc_ups_symmetra_lx_snmp.yaml
@@ -1,6 +1,6 @@
zabbix_export:
version: '5.4'
- date: '2021-10-28T06:43:58Z'
+ date: '2021-12-20T07:10:05Z'
groups:
-
uuid: 3dcd5bbe90534f9e8eb5c2d53756af63
@@ -19,7 +19,7 @@ zabbix_export:
You can discuss this template or leave feedback on our forum https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups
- Template tooling version used: 0.39
+ Template tooling version used: 0.40
groups:
-
name: Templates/Power
diff --git a/templates/power/apc/apc_ups_symmetra_rm_snmp/README.md b/templates/power/apc/apc_ups_symmetra_rm_snmp/README.md
index abb301c76cc..6e3560ee5c5 100644
--- a/templates/power/apc/apc_ups_symmetra_rm_snmp/README.md
+++ b/templates/power/apc/apc_ups_symmetra_rm_snmp/README.md
@@ -53,7 +53,7 @@ There are no template links in this template.
|----|-----------|----|----|
|Input phases discovery |<p>The input phase identifier. OID upsPhaseInputPhaseIndex.1.1</p> |SNMP |input.phases.discovery |
|Output phases discovery |<p>The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1</p> |SNMP |output.phases.discovery |
-|External battery packs discovery | |SNMP |battery.packs.discovery<p>**Filter**:</p>AND <p>- A: {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`</p> |
+|External battery packs discovery |<p>-</p> |SNMP |battery.packs.discovery<p>**Filter**:</p>AND <p>- {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`</p> |
|External bad battery packs discovery |<p>Discovery of the number of external defective battery packs.</p> |SNMP |battery.packs.bad.discovery |
|External sensor port 1 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor1.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR1_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
|External sensor port 2 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor2.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR2_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
@@ -112,29 +112,29 @@ There are no template links in this template.
|System name has changed (new name: {ITEM.VALUE}) |<p>System name has changed. Ack to close.</p> |`last(/APC UPS Symmetra RM SNMP/system.name[sysName.0],#1)<>last(/APC UPS Symmetra RM SNMP/system.name[sysName.0],#2) and length(last(/APC UPS Symmetra RM SNMP/system.name[sysName.0]))>0` |INFO |<p>Manual close: YES</p> |
|Battery has an internal error condition |<p>A battery installed has an internal error condition.</p> |`last(/APC UPS Symmetra RM SNMP/battery.status[upsBasicBatteryStatus])=4` |AVERAGE | |
|Battery is Low |<p>The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.</p> |`last(/APC UPS Symmetra RM SNMP/battery.status[upsBasicBatteryStatus])=3` |AVERAGE | |
-|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) | |`last(/APC UPS Symmetra RM SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
+|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) |<p>-</p> |`last(/APC UPS Symmetra RM SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
|Battery needs replacement |<p>A battery installed has an internal error condition.</p> |`last(/APC UPS Symmetra RM SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2` |HIGH | |
-|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra RM SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
-|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra RM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC UPS Symmetra RM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra RM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
-|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra RM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC UPS Symmetra RM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC UPS Symmetra RM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
+|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) |<p>-</p> |`min(/APC UPS Symmetra RM SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) |<p>-</p> |`min(/APC UPS Symmetra RM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC UPS Symmetra RM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra RM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
+|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) |<p>-</p> |`min(/APC UPS Symmetra RM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC UPS Symmetra RM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC UPS Symmetra RM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
|Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD}) |<p>A battery installed has an internal error condition.</p> |`min(/APC UPS Symmetra RM SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}` |HIGH | |
-|UPS is Timed Sleeping | |`last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | |
-|UPS is Switched Bypass | |`last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | |
-|UPS is Software Bypass | |`last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | |
-|UPS is Sleeping Until Power Return | |`last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | |
-|UPS is Rebooting | |`last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | |
-|UPS is On Smart Trim | |`last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | |
-|UPS is on Smart Boost | |`last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | |
-|UPS is on battery | |`last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | |
-|UPS is Off | |`last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | |
-|UPS is Emergency Static Bypass | |`last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | |
-|UPS is Hardware Failure Bypass | |`last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | |
+|UPS is Timed Sleeping |<p>-</p> |`last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | |
+|UPS is Switched Bypass |<p>-</p> |`last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | |
+|UPS is Software Bypass |<p>-</p> |`last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | |
+|UPS is Sleeping Until Power Return |<p>-</p> |`last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | |
+|UPS is Rebooting |<p>-</p> |`last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | |
+|UPS is On Smart Trim |<p>-</p> |`last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | |
+|UPS is on Smart Boost |<p>-</p> |`last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | |
+|UPS is on battery |<p>-</p> |`last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | |
+|UPS is Off |<p>-</p> |`last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | |
+|UPS is Emergency Static Bypass |<p>-</p> |`last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | |
+|UPS is Hardware Failure Bypass |<p>-</p> |`last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | |
|{HOST.NAME} has been restarted (uptime < 10m) |<p>Uptime is less than 10 minutes</p> |`last(/APC UPS Symmetra RM SNMP/system.uptime[sysUpTime.0])<10m` |WARNING |<p>Manual close: YES</p><p>**Depends on**:</p><p>- No SNMP data collection</p> |
|No SNMP data collection |<p>SNMP is not available for polling. Please check device connectivity and SNMP settings.</p> |`max(/APC UPS Symmetra RM SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0` |WARNING | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra RM SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra RM SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra RM SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra RM SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) |<p>-</p> |`min(/APC UPS Symmetra RM SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra RM SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) |<p>-</p> |`min(/APC UPS Symmetra RM SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra RM SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |<p>The battery cartridge status:</p><p>bit 0 Disconnected</p><p>bit 1 Overvoltage</p><p>bit 2 NeedsReplacement</p><p>bit 3 OvertemperatureCritical</p><p>bit 4 Charger</p><p>bit 5 TemperatureSensor</p><p>bit 6 BusSoftStart</p><p>bit 7 OvertemperatureWarning</p><p>bit 8 GeneralError</p><p>bit 9 Communication</p><p>bit 10 DisconnectedFrame</p><p>bit 11 FirmwareMismatch</p> |`find(/APC UPS Symmetra RM SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0` |WARNING | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra RM SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) |<p>-</p> |`min(/APC UPS Symmetra RM SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |<p>The battery cartridge health.</p><p> bit 0 Battery lifetime okay</p><p> bit 1 Battery lifetime near end, order replacement cartridge</p><p> bit 2 Battery lifetime exceeded, replace battery</p><p> bit 3 Battery lifetime near end acknowledged, order replacement cartridge</p><p> bit 4 Battery lifetime exceeded acknowledged, replace battery</p><p> bit 5 Battery measured lifetime near end, order replacement cartridge</p><p> bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge</p> |`find(/APC UPS Symmetra RM SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1` |WARNING | |
|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`last(/APC UPS Symmetra RM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4` |INFO | |
|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`last(/APC UPS Symmetra RM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2` |AVERAGE | |
diff --git a/templates/power/apc/apc_ups_symmetra_rm_snmp/template_power_apc_ups_symmetra_rm_snmp.yaml b/templates/power/apc/apc_ups_symmetra_rm_snmp/template_power_apc_ups_symmetra_rm_snmp.yaml
index 5f6c3304033..6738c5298c8 100644
--- a/templates/power/apc/apc_ups_symmetra_rm_snmp/template_power_apc_ups_symmetra_rm_snmp.yaml
+++ b/templates/power/apc/apc_ups_symmetra_rm_snmp/template_power_apc_ups_symmetra_rm_snmp.yaml
@@ -1,6 +1,6 @@
zabbix_export:
version: '5.4'
- date: '2021-10-28T06:43:59Z'
+ date: '2021-12-20T07:10:06Z'
groups:
-
uuid: 3dcd5bbe90534f9e8eb5c2d53756af63
@@ -19,7 +19,7 @@ zabbix_export:
You can discuss this template or leave feedback on our forum https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups
- Template tooling version used: 0.39
+ Template tooling version used: 0.40
groups:
-
name: Templates/Power
diff --git a/templates/power/apc/apc_ups_symmetra_rx_snmp/README.md b/templates/power/apc/apc_ups_symmetra_rx_snmp/README.md
index ce7f306e234..05b45bec4ed 100644
--- a/templates/power/apc/apc_ups_symmetra_rx_snmp/README.md
+++ b/templates/power/apc/apc_ups_symmetra_rx_snmp/README.md
@@ -49,7 +49,7 @@ There are no template links in this template.
|----|-----------|----|----|
|Input phases discovery |<p>The input phase identifier. OID upsPhaseInputPhaseIndex.1.1</p> |SNMP |input.phases.discovery |
|Output phases discovery |<p>The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1</p> |SNMP |output.phases.discovery |
-|External battery packs discovery | |SNMP |battery.packs.discovery<p>**Filter**:</p>AND <p>- A: {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`</p> |
+|External battery packs discovery |<p>-</p> |SNMP |battery.packs.discovery<p>**Filter**:</p>AND <p>- {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`</p> |
|External bad battery packs discovery |<p>Discovery of the number of external defective battery packs.</p> |SNMP |battery.packs.bad.discovery |
|External sensor port 1 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor1.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR1_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
|External sensor port 2 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor2.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR2_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
@@ -108,29 +108,29 @@ There are no template links in this template.
|System name has changed (new name: {ITEM.VALUE}) |<p>System name has changed. Ack to close.</p> |`last(/APC UPS Symmetra RX SNMP/system.name[sysName.0],#1)<>last(/APC UPS Symmetra RX SNMP/system.name[sysName.0],#2) and length(last(/APC UPS Symmetra RX SNMP/system.name[sysName.0]))>0` |INFO |<p>Manual close: YES</p> |
|Battery has an internal error condition |<p>A battery installed has an internal error condition.</p> |`last(/APC UPS Symmetra RX SNMP/battery.status[upsBasicBatteryStatus])=4` |AVERAGE | |
|Battery is Low |<p>The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.</p> |`last(/APC UPS Symmetra RX SNMP/battery.status[upsBasicBatteryStatus])=3` |AVERAGE | |
-|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) | |`last(/APC UPS Symmetra RX SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
+|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) |<p>-</p> |`last(/APC UPS Symmetra RX SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
|Battery needs replacement |<p>A battery installed has an internal error condition.</p> |`last(/APC UPS Symmetra RX SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2` |HIGH | |
-|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra RX SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
-|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra RX SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC UPS Symmetra RX SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra RX SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
-|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra RX SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC UPS Symmetra RX SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC UPS Symmetra RX SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
+|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) |<p>-</p> |`min(/APC UPS Symmetra RX SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) |<p>-</p> |`min(/APC UPS Symmetra RX SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC UPS Symmetra RX SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra RX SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
+|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) |<p>-</p> |`min(/APC UPS Symmetra RX SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC UPS Symmetra RX SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC UPS Symmetra RX SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
|Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD}) |<p>A battery installed has an internal error condition.</p> |`min(/APC UPS Symmetra RX SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}` |HIGH | |
-|UPS is Timed Sleeping | |`last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | |
-|UPS is Switched Bypass | |`last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | |
-|UPS is Software Bypass | |`last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | |
-|UPS is Sleeping Until Power Return | |`last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | |
-|UPS is Rebooting | |`last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | |
-|UPS is On Smart Trim | |`last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | |
-|UPS is on Smart Boost | |`last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | |
-|UPS is on battery | |`last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | |
-|UPS is Off | |`last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | |
-|UPS is Emergency Static Bypass | |`last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | |
-|UPS is Hardware Failure Bypass | |`last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | |
+|UPS is Timed Sleeping |<p>-</p> |`last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | |
+|UPS is Switched Bypass |<p>-</p> |`last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | |
+|UPS is Software Bypass |<p>-</p> |`last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | |
+|UPS is Sleeping Until Power Return |<p>-</p> |`last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | |
+|UPS is Rebooting |<p>-</p> |`last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | |
+|UPS is On Smart Trim |<p>-</p> |`last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | |
+|UPS is on Smart Boost |<p>-</p> |`last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | |
+|UPS is on battery |<p>-</p> |`last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | |
+|UPS is Off |<p>-</p> |`last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | |
+|UPS is Emergency Static Bypass |<p>-</p> |`last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | |
+|UPS is Hardware Failure Bypass |<p>-</p> |`last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | |
|{HOST.NAME} has been restarted (uptime < 10m) |<p>Uptime is less than 10 minutes</p> |`last(/APC UPS Symmetra RX SNMP/system.uptime[sysUpTime.0])<10m` |WARNING |<p>Manual close: YES</p><p>**Depends on**:</p><p>- No SNMP data collection</p> |
|No SNMP data collection |<p>SNMP is not available for polling. Please check device connectivity and SNMP settings.</p> |`max(/APC UPS Symmetra RX SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0` |WARNING | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra RX SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra RX SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra RX SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra RX SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) |<p>-</p> |`min(/APC UPS Symmetra RX SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra RX SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) |<p>-</p> |`min(/APC UPS Symmetra RX SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra RX SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |<p>The battery cartridge status:</p><p>bit 0 Disconnected</p><p>bit 1 Overvoltage</p><p>bit 2 NeedsReplacement</p><p>bit 3 OvertemperatureCritical</p><p>bit 4 Charger</p><p>bit 5 TemperatureSensor</p><p>bit 6 BusSoftStart</p><p>bit 7 OvertemperatureWarning</p><p>bit 8 GeneralError</p><p>bit 9 Communication</p><p>bit 10 DisconnectedFrame</p><p>bit 11 FirmwareMismatch</p> |`find(/APC UPS Symmetra RX SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0` |WARNING | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra RX SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) |<p>-</p> |`min(/APC UPS Symmetra RX SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |<p>The battery cartridge health.</p><p> bit 0 Battery lifetime okay</p><p> bit 1 Battery lifetime near end, order replacement cartridge</p><p> bit 2 Battery lifetime exceeded, replace battery</p><p> bit 3 Battery lifetime near end acknowledged, order replacement cartridge</p><p> bit 4 Battery lifetime exceeded acknowledged, replace battery</p><p> bit 5 Battery measured lifetime near end, order replacement cartridge</p><p> bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge</p> |`find(/APC UPS Symmetra RX SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1` |WARNING | |
|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`last(/APC UPS Symmetra RX SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4` |INFO | |
|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`last(/APC UPS Symmetra RX SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2` |AVERAGE | |
diff --git a/templates/power/apc/apc_ups_symmetra_rx_snmp/template_power_apc_ups_symmetra_rx_snmp.yaml b/templates/power/apc/apc_ups_symmetra_rx_snmp/template_power_apc_ups_symmetra_rx_snmp.yaml
index ad4e81c1521..44d29ed4161 100644
--- a/templates/power/apc/apc_ups_symmetra_rx_snmp/template_power_apc_ups_symmetra_rx_snmp.yaml
+++ b/templates/power/apc/apc_ups_symmetra_rx_snmp/template_power_apc_ups_symmetra_rx_snmp.yaml
@@ -1,6 +1,6 @@
zabbix_export:
version: '5.4'
- date: '2021-10-28T06:43:58Z'
+ date: '2021-12-20T07:10:07Z'
groups:
-
uuid: 3dcd5bbe90534f9e8eb5c2d53756af63
@@ -19,7 +19,7 @@ zabbix_export:
You can discuss this template or leave feedback on our forum https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups
- Template tooling version used: 0.39
+ Template tooling version used: 0.40
groups:
-
name: Templates/Power