-rw-r--r--templates/power/apc/apc_ups_smart_3000_xlm_snmp/template_power_apc_ups_smart_3000_xlm_snmp.yaml94
1 files changed, 93 insertions, 1 deletions
diff --git a/templates/power/apc/apc_ups_smart_3000_xlm_snmp/template_power_apc_ups_smart_3000_xlm_snmp.yaml b/templates/power/apc/apc_ups_smart_3000_xlm_snmp/template_power_apc_ups_smart_3000_xlm_snmp.yaml
index 443f36de7c7..cb0be87946d 100644
--- a/templates/power/apc/apc_ups_smart_3000_xlm_snmp/template_power_apc_ups_smart_3000_xlm_snmp.yaml
+++ b/templates/power/apc/apc_ups_smart_3000_xlm_snmp/template_power_apc_ups_smart_3000_xlm_snmp.yaml
@@ -1,11 +1,13 @@
zabbix_export:
version: '5.4'
- date: '2021-05-09T00:00:00Z'
+ date: '2021-05-10T19:41:06Z'
groups:
-
+ uuid: 3dcd5bbe90534f9e8eb5c2d53756af63
name: Templates/Power
templates:
-
+ uuid: eafd78764fde4110b9e46ae184f327ba
template: 'APC Smart-UPS 3000 XLM SNMP'
name: 'APC Smart-UPS 3000 XLM SNMP'
description: |
@@ -23,6 +25,7 @@ zabbix_export:
name: Templates/Power
items:
-
+ uuid: 6e8ed2c349d744a1a07928b32cf574c3
name: 'Battery capacity'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.3.1.0
@@ -48,11 +51,13 @@ zabbix_export:
tag: Status
triggers:
-
+ uuid: 13fe1336e40c4bafb8dbd409497abf8f
expression: 'last(/APC Smart-UPS 3000 XLM SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}'
name: 'Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%)'
opdata: 'Current capacity: {ITEM.LASTVALUE1}'
priority: HIGH
-
+ uuid: 86780568c0594469bc7324c68440cbec
name: 'External battery packs count'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.2.5.0
@@ -73,6 +78,7 @@ zabbix_export:
-
tag: Status
-
+ uuid: 1928e58e65a34b188916086bad5b8725
name: 'Battery last replace date'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.1.3.0
@@ -97,6 +103,7 @@ zabbix_export:
-
tag: Status
-
+ uuid: b50a17ab043c404990dd088ac9f74078
name: 'Battery replace indicator'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.2.4.0
@@ -117,11 +124,13 @@ zabbix_export:
tag: Status
triggers:
-
+ uuid: 4590ac935e044c19978fe01d117e2995
expression: 'last(/APC Smart-UPS 3000 XLM SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2'
name: 'Battery needs replacement'
priority: HIGH
description: 'A battery installed has an internal error condition.'
-
+ uuid: d15c36fb66754791b1014f52171efe1c
name: 'Battery runtime remaining'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.2.3.0
@@ -146,6 +155,7 @@ zabbix_export:
-
tag: Status
-
+ uuid: 9fa77fdcbd7343ca904c6282efcb7c72
name: 'Battery status'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.1.1.0
@@ -172,16 +182,19 @@ zabbix_export:
tag: Status
triggers:
-
+ uuid: e98ba83e63d246408aeeda76da62d5a4
expression: 'last(/APC Smart-UPS 3000 XLM SNMP/battery.status[upsBasicBatteryStatus])=4'
name: 'Battery has an internal error condition'
priority: AVERAGE
description: 'A battery installed has an internal error condition.'
-
+ uuid: 51e3281c49454cf997561c857a34a803
expression: 'last(/APC Smart-UPS 3000 XLM SNMP/battery.status[upsBasicBatteryStatus])=3'
name: 'Battery is Low'
priority: AVERAGE
description: 'The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.'
-
+ uuid: bded43c8a4eb4d1b9cf5403d3f3027cd
name: 'Battery temperature'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.3.2.0
@@ -207,11 +220,13 @@ zabbix_export:
tag: Status
triggers:
-
+ uuid: f2f6665f9ff44befa3d8bf1a975dcc82
expression: 'min(/APC Smart-UPS 3000 XLM SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}'
name: 'Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD})'
opdata: 'Current temperature: {ITEM.LASTVALUE1}'
priority: HIGH
-
+ uuid: e478bdaa89674f6792e39ff1a2d9a413
name: 'Battery voltage'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.3.4.0
@@ -235,6 +250,7 @@ zabbix_export:
-
tag: Status
-
+ uuid: 7b7d6fdeea2e49c9bb74eb301ecca93a
name: 'Input fail cause'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.4.1.318.1.1.1.3.2.5.0
@@ -277,6 +293,7 @@ zabbix_export:
-
tag: Status
-
+ uuid: ab28b72c192e48b5819079bd386ba8ea
name: 'Input frequency'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.4.1.318.1.1.1.3.3.4.0
@@ -301,11 +318,13 @@ zabbix_export:
tag: Status
triggers:
-
+ uuid: c1cae8ba959d47a1bb7a483d81b3a3e3
expression: 'min(/APC Smart-UPS 3000 XLM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS 3000 XLM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC Smart-UPS 3000 XLM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})'
name: 'Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD})'
opdata: 'Current frequency: {ITEM.LASTVALUE1}'
priority: HIGH
-
+ uuid: e90dbc034cc447afb4ac1c8ced484882
name: 'Input voltage'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.4.1.318.1.1.1.3.3.1.0
@@ -330,11 +349,13 @@ zabbix_export:
tag: Status
triggers:
-
+ uuid: 7af69178dbe24ed28e3cbe5f4b2dc0ee
expression: 'min(/APC Smart-UPS 3000 XLM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS 3000 XLM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS 3000 XLM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})'
name: 'Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})'
opdata: 'Current voltage: {ITEM.LASTVALUE1}'
priority: HIGH
-
+ uuid: a8d017e0fa5d4eca838ad068f0dffcd9
name: 'Output current'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.4.1.318.1.1.1.4.3.4.0
@@ -358,6 +379,7 @@ zabbix_export:
-
tag: Status
-
+ uuid: a2613c8d71864594a0c94064d99e059e
name: 'Output load'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.4.1.318.1.1.1.4.3.3.0
@@ -383,12 +405,14 @@ zabbix_export:
tag: Status
triggers:
-
+ uuid: ae08950d9865489e98db66640942d1da
expression: 'min(/APC Smart-UPS 3000 XLM SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}'
name: 'Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD})'
opdata: 'Current load: {ITEM.LASTVALUE1}'
priority: HIGH
description: 'A battery installed has an internal error condition.'
-
+ uuid: 107461ac37984a708acf7f55ae248d67
name: 'Output status'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.4.1.318.1.1.1.4.1.1.0
@@ -415,50 +439,62 @@ zabbix_export:
tag: Status
triggers:
-
+ uuid: 80e30d37b1724c6ba1d58cedbcf6307f
expression: 'last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=16'
name: 'UPS is Emergency Static Bypass'
priority: AVERAGE
-
+ uuid: 9bb143ada4194c0084eb70af7bb2c5dc
expression: 'last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=10'
name: 'UPS is Hardware Failure Bypass'
priority: AVERAGE
-
+ uuid: 7132f256542540acadb0caf90144a29c
expression: 'last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=7'
name: 'UPS is Off'
priority: AVERAGE
-
+ uuid: 737693e5e4274823a9a21ff92a6ca98a
expression: 'last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=3'
name: 'UPS is on battery'
priority: AVERAGE
-
+ uuid: c2fd31cfe3b8474f80b52a2340108b6a
expression: 'last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=4'
name: 'UPS is on Smart Boost'
priority: AVERAGE
-
+ uuid: 2c3a2e962c1e45f6858e5c1aaecee4a3
expression: 'last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=12'
name: 'UPS is On Smart Trim'
priority: AVERAGE
-
+ uuid: 59d415b15bbf43de85453f5b2ffb73d7
expression: 'last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=8'
name: 'UPS is Rebooting'
priority: AVERAGE
-
+ uuid: 6811d34cec57401089af9accfd66ca8f
expression: 'last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=11'
name: 'UPS is Sleeping Until Power Return'
priority: AVERAGE
-
+ uuid: 3c96ce14f54a4a59a2568f1f62117e7b
expression: 'last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=6'
name: 'UPS is Software Bypass'
priority: AVERAGE
-
+ uuid: 60e83c77157741cbb3d24920e87d7d59
expression: 'last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=9'
name: 'UPS is Switched Bypass'
priority: AVERAGE
-
+ uuid: da442de0e8874736aaab88f009aabe76
expression: 'last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=5'
name: 'UPS is Timed Sleeping'
priority: AVERAGE
-
+ uuid: ebf71f0afed5460ba4c7f66bb162de9f
name: 'Output voltage'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.4.1.318.1.1.1.4.3.1.0
@@ -482,6 +518,7 @@ zabbix_export:
-
tag: Status
-
+ uuid: 92c2ef138bf148199cdb6d9684b6fa23
name: 'SNMP traps (fallback)'
type: SNMP_TRAP
key: snmptrap.fallback
@@ -494,6 +531,7 @@ zabbix_export:
-
tag: General
-
+ uuid: fbcbe2cffc8c4bb6b11276cdd03376c3
name: 'System contact details'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.2.1.1.4.0
@@ -517,6 +555,7 @@ zabbix_export:
-
tag: General
-
+ uuid: a312df9175ca45528375398f56fa3b3b
name: 'System description'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.2.1.1.1.0
@@ -539,6 +578,7 @@ zabbix_export:
-
tag: General
-
+ uuid: a5c6c4c44132439abd0e5fd88e3c90cf
name: 'System location'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.2.1.1.6.0
@@ -561,6 +601,7 @@ zabbix_export:
-
tag: General
-
+ uuid: 272883d0a1cd4bb585a6ede50336c873
name: Model
type: SNMP_AGENT
snmp_oid: 1.3.6.1.4.1.318.1.1.1.1.1.1.0
@@ -581,6 +622,7 @@ zabbix_export:
-
tag: General
-
+ uuid: 1f591627fea54a9ebdd8f10cbf39b9ed
name: 'System name'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.2.1.1.5.0
@@ -605,12 +647,14 @@ zabbix_export:
tag: General
triggers:
-
+ uuid: 391d9d9d89ce4c4a977d4cb5203b93d8
expression: '(last(/APC Smart-UPS 3000 XLM SNMP/system.name[sysName.0],#1)<>last(/APC Smart-UPS 3000 XLM SNMP/system.name[sysName.0],#2))=1 and length(last(/APC Smart-UPS 3000 XLM SNMP/system.name[sysName.0]))>0'
name: 'System name has changed (new name: {ITEM.VALUE})'
priority: INFO
description: 'System name has changed. Ack to close.'
manual_close: 'YES'
-
+ uuid: f6922cd0f93a4a4288a978ff8336226b
name: 'System object ID'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.2.1.1.2.0
@@ -636,6 +680,7 @@ zabbix_export:
-
tag: General
-
+ uuid: 0c36d0bb59a44db2b80ae4a4ff2d7c1b
name: 'Serial number'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.4.1.318.1.1.1.1.2.3.0
@@ -659,6 +704,7 @@ zabbix_export:
-
tag: General
-
+ uuid: 39dd6b9b815a4a838a43d2ebf3fcc8f9
name: Uptime
type: SNMP_AGENT
snmp_oid: 1.3.6.1.2.1.1.3.0
@@ -681,6 +727,7 @@ zabbix_export:
tag: Status
triggers:
-
+ uuid: 15764a5819174d3fadc75436f42650fb
expression: 'last(/APC Smart-UPS 3000 XLM SNMP/system.uptime[sysUpTime.0])<10m'
name: '{HOST.NAME} has been restarted (uptime < 10m)'
priority: WARNING
@@ -691,6 +738,7 @@ zabbix_export:
name: 'No SNMP data collection'
expression: 'max(/APC Smart-UPS 3000 XLM SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0'
-
+ uuid: edb39f7236d74c6783e0d4b832e0b94b
name: 'SNMP agent availability'
type: INTERNAL
key: 'zabbix[host,snmp,available]'
@@ -707,6 +755,7 @@ zabbix_export:
tag: Status
triggers:
-
+ uuid: 8aa7674108df47088a4d12ea09c32242
expression: 'max(/APC Smart-UPS 3000 XLM SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0'
name: 'No SNMP data collection'
opdata: 'Current state: {ITEM.LASTVALUE1}'
@@ -714,6 +763,7 @@ zabbix_export:
description: 'SNMP is not available for polling. Please check device connectivity and SNMP settings.'
discovery_rules:
-
+ uuid: 2edf8773186845499a991288d1a7a55b
name: 'External bad battery packs discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#EXTERNAL_PACKS},1.3.6.1.4.1.318.1.1.1.2.2.6]'
@@ -722,6 +772,7 @@ zabbix_export:
description: 'Discovery of the number of external defective battery packs.'
item_prototypes:
-
+ uuid: 7ff04c0f873c4c0f9af5aca2bd447cce
name: '{#SNMPINDEX}: External battery packs bad'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.2.6.0
@@ -742,6 +793,7 @@ zabbix_export:
-
tag: Status
-
+ uuid: a0d8d681bfb54c1d9792beaf3f708d69
name: 'External battery packs discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#CARTRIDGE_STATUS},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.7,{#BATTERY_PACK},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.1,{#CARTRIDGE_INDEX},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.2]'
@@ -757,6 +809,7 @@ zabbix_export:
formulaid: A
item_prototypes:
-
+ uuid: 35e7da4783e245a2bfff75f3ae79ff5e
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery estimated replace date'
type: SNMP_AGENT
snmp_oid: '1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.8.{#SNMPINDEX}'
@@ -777,6 +830,7 @@ zabbix_export:
-
tag: Status
-
+ uuid: b86ac9ee81fe40c8995618c387775270
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery pack cartridge health'
type: SNMP_AGENT
snmp_oid: '1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.7.{#SNMPINDEX}'
@@ -804,6 +858,7 @@ zabbix_export:
tag: Status
trigger_prototypes:
-
+ uuid: 054c08a5f48e4bebb9aafbbd82d6f4a5
expression: 'find(/APC Smart-UPS 3000 XLM SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1'
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay'
opdata: 'Current bit set: {ITEM.LASTVALUE1}'
@@ -818,6 +873,7 @@ zabbix_export:
bit 5 Battery measured lifetime near end, order replacement cartridge
bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge
-
+ uuid: db78c715c220433cb338199d43cb84a0
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status'
type: SNMP_AGENT
snmp_oid: '1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.10.{#SNMPINDEX}'
@@ -850,6 +906,7 @@ zabbix_export:
tag: Status
trigger_prototypes:
-
+ uuid: 63a8d0bd2efd42f090755b0df714c249
expression: 'find(/APC Smart-UPS 3000 XLM SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0'
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay'
opdata: 'Current bit set: {ITEM.LASTVALUE1}'
@@ -869,6 +926,7 @@ zabbix_export:
bit 10 DisconnectedFrame
bit 11 FirmwareMismatch
-
+ uuid: bab950aa54ca425db4593049a64cf56f
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery temperature'
type: SNMP_AGENT
snmp_oid: '1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.5.{#SNMPINDEX}'
@@ -893,11 +951,13 @@ zabbix_export:
tag: Status
trigger_prototypes:
-
+ uuid: b72814e3e25d405e96e640b97ee3664d
expression: 'min(/APC Smart-UPS 3000 XLM SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}'
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD})'
opdata: 'Current temperature: {ITEM.LASTVALUE1}'
priority: HIGH
-
+ uuid: d2983b402dfd4435a4790d560da8f6f6
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Serial number'
type: SNMP_AGENT
snmp_oid: '1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.4.{#SNMPINDEX}'
@@ -918,6 +978,7 @@ zabbix_export:
-
tag: General
-
+ uuid: 88f5bc98004740fe886f5b1144de2c35
name: 'External sensor port 1 discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#EXTERNAL_SENSOR1_NAME},1.3.6.1.4.1.318.1.1.25.1.2.1.3]'
@@ -926,6 +987,7 @@ zabbix_export:
description: uioSensorStatusTable
item_prototypes:
-
+ uuid: 34e5f00097f4448eadf16071cfa234e9
name: '{#EXTERNAL_SENSOR1_NAME}: Humidity sensor'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.1.7.1.1
@@ -947,6 +1009,7 @@ zabbix_export:
-
tag: Status
-
+ uuid: 04425d6cc153491d9cb710b875f8c9cb
name: '{#EXTERNAL_SENSOR1_NAME}: Sensor alarm status'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.1.9.1.1
@@ -971,21 +1034,25 @@ zabbix_export:
tag: Status
trigger_prototypes:
-
+ uuid: 9ba51ee0398444e1bd12cb805c1f7452
expression: 'last(/APC Smart-UPS 3000 XLM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=3'
name: '{#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical'
priority: HIGH
description: 'The external sensor has returned a value greater than the critical threshold.'
-
+ uuid: 490e952dfac944afb23eb0e72e081db3
expression: 'last(/APC Smart-UPS 3000 XLM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4'
name: '{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable'
priority: INFO
description: 'The external sensor does not work or is not connected.'
-
+ uuid: 8b740b88389b457eaa4d1d6c768ec8ae
expression: 'last(/APC Smart-UPS 3000 XLM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2'
name: '{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning'
priority: AVERAGE
description: 'The external sensor has returned a value greater than the warning threshold.'
-
+ uuid: 29cedff7a5f043caaaa8ff5798b3e925
name: '{#EXTERNAL_SENSOR1_NAME}: Temperature sensor'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.1.6.1.1
@@ -1023,6 +1090,7 @@ zabbix_export:
status: ENABLED
discover: NO_DISCOVER
-
+ uuid: c64b5cb02dec4873a2e041359da3cdf7
name: 'External sensor port 2 discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#EXTERNAL_SENSOR2_NAME},1.3.6.1.4.1.318.1.1.25.1.2.2.3]'
@@ -1031,6 +1099,7 @@ zabbix_export:
description: uioSensorStatusTable
item_prototypes:
-
+ uuid: 445fa35253b942cf8009460ea67701fd
name: '{#EXTERNAL_SENSOR2_NAME}: Humidity sensor'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.2.7.1.1
@@ -1052,6 +1121,7 @@ zabbix_export:
-
tag: Status
-
+ uuid: 58a2e39cd7fc4fe1bd825ce6086b4931
name: '{#EXTERNAL_SENSOR2_NAME}: Sensor alarm status'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.2.9.1.1
@@ -1076,21 +1146,25 @@ zabbix_export:
tag: Status
trigger_prototypes:
-
+ uuid: 944fd36a2ad14fd29dd063ad03197cd7
expression: 'last(/APC Smart-UPS 3000 XLM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=3'
name: '{#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical'
priority: HIGH
description: 'The external sensor has returned a value greater than the critical threshold.'
-
+ uuid: 1a4473a5e1bf4fbbb5761fdb141769c0
expression: 'last(/APC Smart-UPS 3000 XLM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=4'
name: '{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable'
priority: INFO
description: 'The external sensor does not work or is not connected.'
-
+ uuid: af8e01a221b84c73a3f67ab84ed9cfa0
expression: 'last(/APC Smart-UPS 3000 XLM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=2'
name: '{#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning'
priority: AVERAGE
description: 'The external sensor has returned a value greater than the warning threshold.'
-
+ uuid: c78cd23b59254174b333514d9c8d28e1
name: '{#EXTERNAL_SENSOR2_NAME}: Temperature sensor'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.2.6.1.1
@@ -1128,6 +1202,7 @@ zabbix_export:
status: ENABLED
discover: NO_DISCOVER
-
+ uuid: ecca1791b7744f30bfcc1018a10cf1fa
name: 'Input phases discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#PHASEINDEX},1.3.6.1.4.1.318.1.1.1.9.2.3.1.2.1.1]'
@@ -1136,6 +1211,7 @@ zabbix_export:
description: 'The input phase identifier. OID upsPhaseInputPhaseIndex.1.1'
item_prototypes:
-
+ uuid: a8ed43fa8a4543f8ab116c8886511aa3
name: '{#PHASEINDEX}: Phase input current'
type: SNMP_AGENT
snmp_oid: '1.3.6.1.4.1.318.1.1.1.9.2.3.1.6.1.1.{#PHASEINDEX}'
@@ -1160,6 +1236,7 @@ zabbix_export:
-
tag: Status
-
+ uuid: 593b355efb0a4e40bd3527c24994da0a
name: '{#PHASEINDEX}: Phase input voltage'
type: SNMP_AGENT
snmp_oid: '1.3.6.1.4.1.318.1.1.1.9.2.3.1.3.1.1.{#PHASEINDEX}'
@@ -1181,11 +1258,13 @@ zabbix_export:
tag: Status
trigger_prototypes:
-
+ uuid: 9dbe9ef61ebe4cf2b3983c0efd43cebd
expression: 'min(/APC Smart-UPS 3000 XLM SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS 3000 XLM SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}'
name: '{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})'
opdata: 'Current phase {#PHASEINDEX} voltage: {ITEM.LASTVALUE1}'
priority: HIGH
-
+ uuid: c1771434bf6b476280c2f2d15bb52608
name: 'Output phases discovery'
type: SNMP_AGENT
snmp_oid: 'discovery[{#PHASEINDEX},1.3.6.1.4.1.318.1.1.1.9.3.3.1.2.1.1]'
@@ -1194,6 +1273,7 @@ zabbix_export:
description: 'The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1'
item_prototypes:
-
+ uuid: 582f567d83e84d64862183c3b1e248f8
name: '{#PHASEINDEX}: Phase output current'
type: SNMP_AGENT
snmp_oid: '1.3.6.1.4.1.318.1.1.1.9.3.3.1.4.1.1.{#PHASEINDEX}'
@@ -1219,6 +1299,7 @@ zabbix_export:
-
tag: Status
-
+ uuid: 32c88f722f074fd699d880a603aaa91b
name: '{#PHASEINDEX}: Phase output load, %'
type: SNMP_AGENT
snmp_oid: '1.3.6.1.4.1.318.1.1.1.9.3.3.1.10.1.1.{#PHASEINDEX}'
@@ -1240,6 +1321,7 @@ zabbix_export:
-
tag: Status
-
+ uuid: 0502345887e54bbc849a9a4e46a571da
name: '{#PHASEINDEX}: Phase output voltage'
type: SNMP_AGENT
snmp_oid: '1.3.6.1.4.1.318.1.1.1.9.3.3.1.3.1.1.{#PHASEINDEX}'
@@ -1261,6 +1343,7 @@ zabbix_export:
tag: Status
trigger_prototypes:
-
+ uuid: 41ed5de05e4b4043a2430424a1474812
expression: 'min(/APC Smart-UPS 3000 XLM SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS 3000 XLM SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}'
name: '{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})'
opdata: 'Current phase {#PHASEINDEX} voltage: {ITEM.LASTVALUE1}'
@@ -1304,6 +1387,7 @@ zabbix_export:
description: 'Maximum output load in % for trigger expression.'
valuemaps:
-
+ uuid: 55fecbd639c44c328b4199569a7305ef
name: 'PowerNet-MIB::uioSensorStatusAlarmStatus'
mappings:
-
@@ -1319,6 +1403,7 @@ zabbix_export:
value: '4'
newvalue: 'Not applicable'
-
+ uuid: 1ce6860b108948bda40d514fd4e3ed69
name: 'PowerNet-MIB::upsAdvBatteryReplaceIndicator'
mappings:
-
@@ -1328,6 +1413,7 @@ zabbix_export:
value: '2'
newvalue: 'battery Needs Replacing'
-
+ uuid: db1fa20d76c8416c83fa0b7fda536fa8
name: 'PowerNet-MIB::upsAdvInputLineFailCause'
mappings:
-
@@ -1361,6 +1447,7 @@ zabbix_export:
value: '10'
newvalue: 'Rate of Voltage Change'
-
+ uuid: 50b6ae187875406ea8ba1669add70899
name: 'PowerNet-MIB::upsBasicBatteryStatus'
mappings:
-
@@ -1376,6 +1463,7 @@ zabbix_export:
value: '4'
newvalue: 'In Fault Condition'
-
+ uuid: 9c5fd52c36f6451ea3f502a871e821d7
name: 'PowerNet-MIB::upsBasicOutputStatus'
mappings:
-
@@ -1457,6 +1545,7 @@ zabbix_export:
value: '26'
newvalue: 'Charger Only'
-
+ uuid: 89597d423b454a42aa80fa8f7a20f273
name: zabbix.host.available
mappings:
-
@@ -1470,6 +1559,7 @@ zabbix_export:
newvalue: unknown
graphs:
-
+ uuid: a7185c07025e46c6a3b86c29d9f749b0
name: 'Capacity of the UPS batteries'
type: PIE
graph_items:
@@ -1479,6 +1569,7 @@ zabbix_export:
host: 'APC Smart-UPS 3000 XLM SNMP'
key: 'battery.capacity[upsHighPrecBatteryCapacity]'
-
+ uuid: 3c778f0c837d4979abb39aabe0cb321e
name: Output
graph_items:
-
@@ -1493,6 +1584,7 @@ zabbix_export:
host: 'APC Smart-UPS 3000 XLM SNMP'
key: 'output.load[upsHighPrecOutputLoad]'
-
+ uuid: 5f44db14cfc94ae7adf98f8cf1f4b647
name: Voltage
graph_items:
-