-rw-r--r--templates/power/apc/apc_ups_galaxy_3500_snmp/README.md78
-rw-r--r--templates/power/apc/apc_ups_galaxy_3500_snmp/template_power_apc_ups_galaxy_3500_snmp.yaml148
-rw-r--r--templates/power/apc/apc_ups_smart_2200_rm_snmp/README.md78
-rw-r--r--templates/power/apc/apc_ups_smart_2200_rm_snmp/template_power_apc_ups_smart_2200_rm_snmp.yaml148
-rw-r--r--templates/power/apc/apc_ups_smart_3000_xlm_snmp/README.md78
-rw-r--r--templates/power/apc/apc_ups_smart_3000_xlm_snmp/template_power_apc_ups_smart_3000_xlm_snmp.yaml148
-rw-r--r--templates/power/apc/apc_ups_smart_rt_1000_rm_xl_snmp/README.md78
-rw-r--r--templates/power/apc/apc_ups_smart_rt_1000_rm_xl_snmp/template_power_apc_ups_smart_rt_1000_rm_xl_snmp.yaml148
-rw-r--r--templates/power/apc/apc_ups_smart_rt_1000_xl_snmp/README.md78
-rw-r--r--templates/power/apc/apc_ups_smart_rt_1000_xl_snmp/template_power_apc_ups_smart_rt_1000_xl_snmp.yaml148
-rw-r--r--templates/power/apc/apc_ups_smart_srt_5000_snmp/README.md78
-rw-r--r--templates/power/apc/apc_ups_smart_srt_5000_snmp/template_power_apc_ups_smart_srt_5000_snmp.yaml194
-rw-r--r--templates/power/apc/apc_ups_smart_srt_8000_snmp/README.md78
-rw-r--r--templates/power/apc/apc_ups_smart_srt_8000_snmp/template_power_apc_ups_smart_srt_8000_snmp.yaml148
-rw-r--r--templates/power/apc/apc_ups_snmp/README.md78
-rw-r--r--templates/power/apc/apc_ups_snmp/template_power_apc_ups_snmp.yaml148
-rw-r--r--templates/power/apc/apc_ups_symmetra_lx_snmp/README.md78
-rw-r--r--templates/power/apc/apc_ups_symmetra_lx_snmp/template_power_apc_ups_symmetra_lx_snmp.yaml148
-rw-r--r--templates/power/apc/apc_ups_symmetra_rm_snmp/README.md78
-rw-r--r--templates/power/apc/apc_ups_symmetra_rm_snmp/template_power_apc_ups_symmetra_rm_snmp.yaml148
-rw-r--r--templates/power/apc/apc_ups_symmetra_rx_snmp/README.md78
-rw-r--r--templates/power/apc/apc_ups_symmetra_rx_snmp/template_power_apc_ups_symmetra_rx_snmp.yaml148
22 files changed, 1423 insertions, 1109 deletions
diff --git a/templates/power/apc/apc_ups_galaxy_3500_snmp/README.md b/templates/power/apc/apc_ups_galaxy_3500_snmp/README.md
index 2418a3bbe2c..f021287b278 100644
--- a/templates/power/apc/apc_ups_galaxy_3500_snmp/README.md
+++ b/templates/power/apc/apc_ups_galaxy_3500_snmp/README.md
@@ -55,8 +55,8 @@ There are no template links in this template.
|Output phases discovery |<p>The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1</p> |SNMP |output.phases.discovery |
|External battery packs discovery | |SNMP |battery.packs.discovery<p>**Filter**:</p>AND <p>- A: {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`</p> |
|External bad battery packs discovery |<p>Discovery of the number of external defective battery packs.</p> |SNMP |battery.packs.bad.discovery |
-|External sensor port 1 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor1.discovery |
-|External sensor port 2 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor2.discovery |
+|External sensor port 1 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor1.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR1_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
+|External sensor port 2 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor2.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR2_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
## Items collected
@@ -64,12 +64,12 @@ There are no template links in this template.
|-----|----|-----------|----|---------------------|
|General |Model |<p>MIB: PowerNet-MIB</p><p>The UPS model name (e.g. 'APC Smart-UPS 600').</p> |SNMP |system.model[upsBasicIdentModel]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|General |Serial number |<p>MIB: PowerNet-MIB</p><p>An 8-character string identifying the serial number of</p><p> the UPS internal microprocessor. This number is set at</p><p> the factory. NOTE: This number does NOT correspond to</p><p> the serial number on the rear of the UPS.</p> |SNMP |system.sn[upsAdvIdentSerialNumber]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
-|General |SNMP traps (fallback) |<p>Item is used to collect all SNMP traps unmatched by other snmptrap items</p> |SNMP_TRAP |snmptrap.fallback |
+|General |SNMP traps (fallback) |<p>The item is used to collect all SNMP traps unmatched by other snmptrap items</p> |SNMP_TRAP |snmptrap.fallback |
|General |System location |<p>MIB: SNMPv2-MIB</p><p>The physical location of this node (e.g., `telephone closet,</p><p>3rd floor'). If the location is unknown, the value is the zero-length string.</p> |SNMP |system.location[sysLocation.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
-|General |System contact details |<p>MIB: SNMPv2-MIB</p><p>The textual identification of the contact person for this managed</p><p>node, together with information on how to contact this person. If no contact</p><p>information is known, the value is the zero-length string.</p> |SNMP |system.contact[sysContact.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `1d`</p> |
+|General |System contact details |<p>MIB: SNMPv2-MIB</p><p>The textual identification of the contact person for this managed</p><p>node, together with information on how to contact this person. If no contact</p><p>information is known, the value is the zero-length string.</p> |SNMP |system.contact[sysContact.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `12h`</p> |
|General |System object ID |<p>MIB: SNMPv2-MIB</p><p>The vendor's authoritative identification of the network management</p><p>subsystem contained in the entity. This value is allocated within the SMI enterprises</p><p>subtree (1.3.6.1.4.1) and provides an easy and unambiguous means for determining`what</p><p>kind of box' is being managed. For example, if vendor`Flintstones, Inc.' was</p><p>assigned the subtree1.3.6.1.4.1.4242, it could assign the identifier 1.3.6.1.4.1.4242.1.1</p><p>to its `Fred Router'.</p> |SNMP |system.objectid[sysObjectID.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|General |System name |<p>MIB: SNMPv2-MIB</p><p>An administratively-assigned name for this managed node.By</p><p>convention, this is the node's fully-qualified domain name. If the name is unknown,</p><p>the value is the zero-length string.</p> |SNMP |system.name[sysName.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
-|General |System description |<p>MIB: SNMPv2-MIB</p><p>A textual description of the entity. This value should</p><p>include the full name and version identification of the system's hardware type, software operating-system, and</p><p>networking software.</p> |SNMP |system.descr[sysDescr.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `1d`</p> |
+|General |System description |<p>MIB: SNMPv2-MIB</p><p>A textual description of the entity. This value should</p><p>include the full name and version identification of the system's hardware type, software operating-system, and</p><p>networking software.</p> |SNMP |system.descr[sysDescr.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `12h`</p> |
|General |{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Serial number |<p>MIB: PowerNet-MIB</p><p>The battery pack serial number.</p> |SNMP |system.sn[upsHighPrecBatteryPackSerialNumber.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Battery status |<p>MIB: PowerNet-MIB</p><p>The status of the UPS batteries. A batteryLow(3) value</p><p> indicates the UPS will be unable to sustain the current</p><p> load, and its services will be lost if power is not restored.</p><p> The amount of run time in reserve at the time of low battery</p><p> can be configured by the upsAdvConfigLowBatteryRunTime.</p><p> A batteryInFaultCondition(4)value indicates that a battery</p><p> installed has an internal error condition.</p> |SNMP |battery.status[upsBasicBatteryStatus]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Battery capacity |<p>MIB: PowerNet-MIB</p><p>The remaining battery capacity expressed as</p><p> percentage of full capacity.</p> |SNMP |battery.capacity[upsHighPrecBatteryCapacity]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
@@ -87,7 +87,7 @@ There are no template links in this template.
|Status |Output current |<p>MIB: PowerNet-MIB</p><p>The current in amperes drawn by the load on the UPS.</p> |SNMP |output.current[upsHighPrecOutputCurrent]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Output status |<p>MIB: PowerNet-MIB</p><p>The current state of the UPS. If the UPS is unable to</p><p> determine the state of the UPS this variable is set</p><p> to unknown(1).</p><p>During self-test most UPSes report onBattery(3) but</p><p> some that support it will report onBatteryTest(15).</p><p> To determine self-test status across all UPSes, refer</p><p> to the upsBasicStateOutputState OID.</p> |SNMP |output.status[upsBasicOutputStatus]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Uptime |<p>MIB: SNMPv2-MIB</p><p>The time (in hundredths of a second) since the network management</p><p>portion of the system was last re-initialized.</p> |SNMP |system.uptime[sysUpTime.0]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.01`</p> |
-|Status |SNMP agent availability |<p>-</p> |INTERNAL |zabbix[host,snmp,available]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
+|Status |SNMP agent availability |<p>Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list.</p><p>Possible value:</p><p>0 - not available</p><p>1 - available</p><p>2 - unknown</p> |INTERNAL |zabbix[host,snmp,available]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |{#PHASEINDEX}: Phase input voltage |<p>MIB: PowerNet-MIB</p><p>The input voltage in VAC, or -1 if it's unsupported</p><p> by this UPS.</p> |SNMP |phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |{#PHASEINDEX}: Phase input current |<p>MIB: PowerNet-MIB</p><p>The input current in 0.1 amperes, or -0.1 if it's</p><p> unsupported by this UPS.</p> |SNMP |phase.input.current[upsPhaseInputCurrent.1.1.{#PHASEINDEX}]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |{#PHASEINDEX}: Phase output voltage |<p>MIB: PowerNet-MIB</p><p>The output voltage in VAC, or -1 if it's unsupported</p><p> by this UPS.</p> |SNMP |phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
@@ -109,39 +109,39 @@ There are no template links in this template.
|Name|Description|Expression|Severity|Dependencies and additional info|
|----|-----------|----|----|----|
-|System name has changed (new name: {ITEM.VALUE}) |<p>System name has changed. Ack to close.</p> |`{TEMPLATE_NAME:system.name[sysName.0].diff()}=1 and {TEMPLATE_NAME:system.name[sysName.0].strlen()}>0` |INFO |<p>Manual close: YES</p> |
-|Battery has an internal error condition |<p>A battery installed has an internal error condition.</p> |`{TEMPLATE_NAME:battery.status[upsBasicBatteryStatus].last()}=4` |AVERAGE | |
-|Battery is Low |<p>The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.</p> |`{TEMPLATE_NAME:battery.status[upsBasicBatteryStatus].last()}=3` |AVERAGE | |
-|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) | |`{TEMPLATE_NAME:battery.capacity[upsHighPrecBatteryCapacity].last()} < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
-|Battery needs replacement |<p>A battery installed has an internal error condition.</p> |`{TEMPLATE_NAME:battery.replace_indicator[upsAdvBatteryReplaceIndicator].last()}=2` |HIGH | |
-|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:battery.temperature[upsHighPrecBatteryTemperature].min({$TIME.PERIOD})} > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
-|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:input.voltage[upsHighPrecInputLineVoltage].min({$TIME.PERIOD})} > 0 and ({TEMPLATE_NAME:input.voltage[upsHighPrecInputLineVoltage].min({$TIME.PERIOD})} > {$UPS.INPUT_VOLT.MAX.WARN} or {TEMPLATE_NAME:input.voltage[upsHighPrecInputLineVoltage].max({$TIME.PERIOD})} < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
-|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:input.frequency[upsHighPrecInputFrequency].min({$TIME.PERIOD})} > 0 and ({TEMPLATE_NAME:input.frequency[upsHighPrecInputFrequency].min({$TIME.PERIOD})} > {$UPS.INPUT_FREQ.MAX.WARN} or {TEMPLATE_NAME:input.frequency[upsHighPrecInputFrequency].max({$TIME.PERIOD})} < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
-|Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD}) |<p>A battery installed has an internal error condition.</p> |`{TEMPLATE_NAME:output.load[upsHighPrecOutputLoad].min({$TIME.PERIOD})} > {$UPS.OUTPUT.MAX.WARN}` |HIGH | |
-|UPS is Timed Sleeping | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=5` |AVERAGE | |
-|UPS is Switched Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=9` |AVERAGE | |
-|UPS is Software Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=6` |AVERAGE | |
-|UPS is Sleeping Until Power Return | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=11` |AVERAGE | |
-|UPS is Rebooting | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=8` |AVERAGE | |
-|UPS is On Smart Trim | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=12` |AVERAGE | |
-|UPS is on Smart Boost | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=4` |AVERAGE | |
-|UPS is on battery | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=3` |AVERAGE | |
-|UPS is Off | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=7` |AVERAGE | |
-|UPS is Emergency Static Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=16` |AVERAGE | |
-|UPS is Hardware Failure Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=10` |AVERAGE | |
-|{HOST.NAME} has been restarted (uptime < 10m) |<p>Uptime is less than 10 minutes</p> |`{TEMPLATE_NAME:system.uptime[sysUpTime.0].last()}<10m` |WARNING |<p>Manual close: YES</p><p>**Depends on**:</p><p>- No SNMP data collection</p> |
-|No SNMP data collection |<p>SNMP is not available for polling. Please check device connectivity and SNMP settings.</p> |`{TEMPLATE_NAME:zabbix[host,snmp,available].max({$SNMP.TIMEOUT})}=0` |WARNING | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}].min({$TIME.PERIOD})} > {$UPS.INPUT_VOLT.MAX.WARN} or {TEMPLATE_NAME:phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}].max({$TIME.PERIOD})} < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}].min({$TIME.PERIOD})} > {$UPS.INPUT_VOLT.MAX.WARN} or {TEMPLATE_NAME:phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}].max({$TIME.PERIOD})} < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |<p>The battery cartridge status:</p><p>bit 0 Disconnected</p><p>bit 1 Overvoltage</p><p>bit 2 NeedsReplacement</p><p>bit 3 OvertemperatureCritical</p><p>bit 4 Charger</p><p>bit 5 TemperatureSensor</p><p>bit 6 BusSoftStart</p><p>bit 7 OvertemperatureWarning</p><p>bit 8 GeneralError</p><p>bit 9 Communication</p><p>bit 10 DisconnectedFrame</p><p>bit 11 FirmwareMismatch</p> |`{TEMPLATE_NAME:battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}].regexp("^(0{16})$")}=0` |WARNING | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}].min({$TIME.PERIOD})} > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |<p>The battery cartridge health.</p><p> bit 0 Battery lifetime okay</p><p> bit 1 Battery lifetime near end, order replacement cartridge</p><p> bit 2 Battery lifetime exceeded, replace battery</p><p> bit 3 Battery lifetime near end acknowledged, order replacement cartridge</p><p> bit 4 Battery lifetime exceeded acknowledged, replace battery</p><p> bit 5 Battery measured lifetime near end, order replacement cartridge</p><p> bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge</p> |`{TEMPLATE_NAME:battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}].regexp("^(0)[0|1]{15}$")}=1` |WARNING | |
-|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}].last()}=4` |INFO | |
-|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}].last()}=2` |AVERAGE | |
-|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}].last()}=3` |HIGH | |
-|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}].last()}=4` |INFO | |
-|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}].last()}=2` |AVERAGE | |
-|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}].last()}=3` |HIGH | |
+|System name has changed (new name: {ITEM.VALUE}) |<p>System name has changed. Ack to close.</p> |`last(/APC UPS Galaxy 3500 SNMP/system.name[sysName.0],#1)<>last(/APC UPS Galaxy 3500 SNMP/system.name[sysName.0],#2) and length(last(/APC UPS Galaxy 3500 SNMP/system.name[sysName.0]))>0` |INFO |<p>Manual close: YES</p> |
+|Battery has an internal error condition |<p>A battery installed has an internal error condition.</p> |`last(/APC UPS Galaxy 3500 SNMP/battery.status[upsBasicBatteryStatus])=4` |AVERAGE | |
+|Battery is Low |<p>The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.</p> |`last(/APC UPS Galaxy 3500 SNMP/battery.status[upsBasicBatteryStatus])=3` |AVERAGE | |
+|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) | |`last(/APC UPS Galaxy 3500 SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
+|Battery needs replacement |<p>A battery installed has an internal error condition.</p> |`last(/APC UPS Galaxy 3500 SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2` |HIGH | |
+|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC UPS Galaxy 3500 SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC UPS Galaxy 3500 SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC UPS Galaxy 3500 SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Galaxy 3500 SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
+|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) | |`min(/APC UPS Galaxy 3500 SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC UPS Galaxy 3500 SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC UPS Galaxy 3500 SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
+|Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD}) |<p>A battery installed has an internal error condition.</p> |`min(/APC UPS Galaxy 3500 SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}` |HIGH | |
+|UPS is Timed Sleeping | |`last(/APC UPS Galaxy 3500 SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | |
+|UPS is Switched Bypass | |`last(/APC UPS Galaxy 3500 SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | |
+|UPS is Software Bypass | |`last(/APC UPS Galaxy 3500 SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | |
+|UPS is Sleeping Until Power Return | |`last(/APC UPS Galaxy 3500 SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | |
+|UPS is Rebooting | |`last(/APC UPS Galaxy 3500 SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | |
+|UPS is On Smart Trim | |`last(/APC UPS Galaxy 3500 SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | |
+|UPS is on Smart Boost | |`last(/APC UPS Galaxy 3500 SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | |
+|UPS is on battery | |`last(/APC UPS Galaxy 3500 SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | |
+|UPS is Off | |`last(/APC UPS Galaxy 3500 SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | |
+|UPS is Emergency Static Bypass | |`last(/APC UPS Galaxy 3500 SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | |
+|UPS is Hardware Failure Bypass | |`last(/APC UPS Galaxy 3500 SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | |
+|{HOST.NAME} has been restarted (uptime < 10m) |<p>Uptime is less than 10 minutes</p> |`last(/APC UPS Galaxy 3500 SNMP/system.uptime[sysUpTime.0])<10m` |WARNING |<p>Manual close: YES</p><p>**Depends on**:</p><p>- No SNMP data collection</p> |
+|No SNMP data collection |<p>SNMP is not available for polling. Please check device connectivity and SNMP settings.</p> |`max(/APC UPS Galaxy 3500 SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0` |WARNING | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC UPS Galaxy 3500 SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Galaxy 3500 SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC UPS Galaxy 3500 SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Galaxy 3500 SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |<p>The battery cartridge status:</p><p>bit 0 Disconnected</p><p>bit 1 Overvoltage</p><p>bit 2 NeedsReplacement</p><p>bit 3 OvertemperatureCritical</p><p>bit 4 Charger</p><p>bit 5 TemperatureSensor</p><p>bit 6 BusSoftStart</p><p>bit 7 OvertemperatureWarning</p><p>bit 8 GeneralError</p><p>bit 9 Communication</p><p>bit 10 DisconnectedFrame</p><p>bit 11 FirmwareMismatch</p> |`find(/APC UPS Galaxy 3500 SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0` |WARNING | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC UPS Galaxy 3500 SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |<p>The battery cartridge health.</p><p> bit 0 Battery lifetime okay</p><p> bit 1 Battery lifetime near end, order replacement cartridge</p><p> bit 2 Battery lifetime exceeded, replace battery</p><p> bit 3 Battery lifetime near end acknowledged, order replacement cartridge</p><p> bit 4 Battery lifetime exceeded acknowledged, replace battery</p><p> bit 5 Battery measured lifetime near end, order replacement cartridge</p><p> bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge</p> |`find(/APC UPS Galaxy 3500 SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1` |WARNING | |
+|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`last(/APC UPS Galaxy 3500 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4` |INFO | |
+|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`last(/APC UPS Galaxy 3500 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2` |AVERAGE | |
+|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`last(/APC UPS Galaxy 3500 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=3` |HIGH | |
+|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`last(/APC UPS Galaxy 3500 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=4` |INFO | |
+|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`last(/APC UPS Galaxy 3500 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=2` |AVERAGE | |
+|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`last(/APC UPS Galaxy 3500 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=3` |HIGH | |
## Feedback
diff --git a/templates/power/apc/apc_ups_galaxy_3500_snmp/template_power_apc_ups_galaxy_3500_snmp.yaml b/templates/power/apc/apc_ups_galaxy_3500_snmp/template_power_apc_ups_galaxy_3500_snmp.yaml
index 40298387c0f..e683a6a608e 100644
--- a/templates/power/apc/apc_ups_galaxy_3500_snmp/template_power_apc_ups_galaxy_3500_snmp.yaml
+++ b/templates/power/apc/apc_ups_galaxy_3500_snmp/template_power_apc_ups_galaxy_3500_snmp.yaml
@@ -1,6 +1,6 @@
zabbix_export:
- version: '5.4'
- date: '2021-05-11T08:04:59Z'
+ version: '6.0'
+ date: '2021-10-28T08:23:18Z'
groups:
-
uuid: 3dcd5bbe90534f9e8eb5c2d53756af63
@@ -19,7 +19,7 @@ zabbix_export:
You can discuss this template or leave feedback on our forum https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups
- Template tooling version used: 0.38
+ Template tooling version used: 0.39
groups:
-
name: Templates/Power
@@ -48,7 +48,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 1800690ba0504df9940a4e667c846132
@@ -76,7 +77,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 98af792142464656b925a452e5ebf1cc
name: 'Battery last replace date'
@@ -101,7 +103,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: b7614652ff6f4e0890f366b8e0831b80
name: 'Battery replace indicator'
@@ -121,7 +124,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: b4d10f8908f4473facde6d2db1520e0f
@@ -153,7 +157,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 22a95e447ad74d43a191f368346fde59
name: 'Battery status'
@@ -179,7 +184,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: d84ec0d0b8d84e3294cbe7ffaed0c83e
@@ -217,7 +223,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 0e1f47f0604d4b1b8769e497d7f328b9
@@ -248,7 +255,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 9069a1c0d9304e7fa5f2df133dbb46cd
name: 'Input fail cause'
@@ -291,7 +299,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 3a64740655ca455ab0280592b5f0055f
name: 'Input frequency'
@@ -315,7 +324,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 786d9928356e41ad9b6b2de3b4f3a96f
@@ -346,7 +356,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: de88ed3b64644d3f9ad1cc3f965757bc
@@ -377,7 +388,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 5774ead79e8b4d63a4a31bc091d1c52a
name: 'Output load'
@@ -402,7 +414,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: fb7ca4b92e714fda95152b698cf1aa92
@@ -436,7 +449,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: efed1ccf301740c1a29e71cd89e5659f
@@ -516,7 +530,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 7d20aa252c5143c98de837dbd2f0cd53
name: 'SNMP traps (fallback)'
@@ -525,18 +540,19 @@ zabbix_export:
history: 2w
trends: '0'
value_type: LOG
- description: 'Item is used to collect all SNMP traps unmatched by other snmptrap items'
+ description: 'The item is used to collect all SNMP traps unmatched by other snmptrap items'
logtimefmt: 'hh:mm:sszyyyy/MM/dd'
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: aa5e85ef78504fc080b97342baf6cb35
name: 'System contact details'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.2.1.1.4.0
key: 'system.contact[sysContact.0]'
- delay: 1h
+ delay: 15m
history: 2w
trends: '0'
value_type: CHAR
@@ -550,17 +566,18 @@ zabbix_export:
-
type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- - 1d
+ - 12h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: f1df592a2b114677a1beabec33ce01f9
name: 'System description'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.2.1.1.1.0
key: 'system.descr[sysDescr.0]'
- delay: 1h
+ delay: 15m
history: 2w
trends: '0'
value_type: CHAR
@@ -573,10 +590,11 @@ zabbix_export:
-
type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- - 1d
+ - 12h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: b109475e72e74e76846aa478e9937101
name: 'System location'
@@ -599,7 +617,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 93b6e128e95a4a96bde38ef15d74d510
name: Model
@@ -620,7 +639,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: d6f2c9770c28487d9fa6af2b63917958
name: 'System name'
@@ -644,7 +664,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
triggers:
-
uuid: 811ff6e90d904c8c98feadc89a18e733
@@ -678,7 +699,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: ef25b1e818534420920ff6260fa2932e
name: 'Serial number'
@@ -702,7 +724,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: fc207a1df4324fcf99ba1da262527fe3
name: Uptime
@@ -724,7 +747,8 @@ zabbix_export:
- '0.01'
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 5c50881846c649dbb47adcfb3dfc7d68
@@ -743,6 +767,12 @@ zabbix_export:
type: INTERNAL
key: 'zabbix[host,snmp,available]'
history: 7d
+ description: |
+ Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list.
+ Possible value:
+ 0 - not available
+ 1 - available
+ 2 - unknown
valuemap:
name: zabbix.host.available
preprocessing:
@@ -752,7 +782,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: e12b11324a634eeba56db1aec1834d5f
@@ -791,7 +822,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 0c8fc55bbe984d919c3b87a096d900d5
name: 'External battery packs discovery'
@@ -828,7 +860,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 41cd82bb312344b7bdb9c7c5aac2eb21
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery pack cartridge health'
@@ -855,7 +888,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 94e469f639cb4ae4ab3ac23918cfa651
@@ -903,7 +937,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 60bf7de80cd741caa1c622e797da1d69
@@ -948,7 +983,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: bdd4bb9fac784bc0b0dc72db3ac9e040
@@ -976,7 +1012,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: ffb60da941114174932b219e14892be9
name: 'External sensor port 1 discovery'
@@ -1007,7 +1044,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 1a41c120082948bdb6865413bdc09917
name: '{#EXTERNAL_SENSOR1_NAME}: Sensor alarm status'
@@ -1031,7 +1069,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 93d474d1badc45d5a48fe0e610744ff6
@@ -1071,7 +1110,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
overrides:
-
name: Temp
@@ -1119,7 +1159,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 492835d959d644d7b95fc480cba5d3dc
name: '{#EXTERNAL_SENSOR2_NAME}: Sensor alarm status'
@@ -1143,7 +1184,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 55acc85739e04ebea3414059907ef2e4
@@ -1183,7 +1225,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
overrides:
-
name: Temp
@@ -1234,7 +1277,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 7356945fc0e94026a2ca04d297fdf953
name: '{#PHASEINDEX}: Phase input voltage'
@@ -1255,7 +1299,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 1824f0be30284d13bad9f895f7adaa0e
@@ -1297,7 +1342,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 3eb001cece8340d59cd0e7f59812f149
name: '{#PHASEINDEX}: Phase output load, %'
@@ -1319,7 +1365,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: f09e23dcb5b24170b356556a36bb39cc
name: '{#PHASEINDEX}: Phase output voltage'
@@ -1340,7 +1387,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 675dc7c59e974f7eadd5d1562dec00ce
diff --git a/templates/power/apc/apc_ups_smart_2200_rm_snmp/README.md b/templates/power/apc/apc_ups_smart_2200_rm_snmp/README.md
index 8765b6cfe9d..406dc621edb 100644
--- a/templates/power/apc/apc_ups_smart_2200_rm_snmp/README.md
+++ b/templates/power/apc/apc_ups_smart_2200_rm_snmp/README.md
@@ -55,8 +55,8 @@ There are no template links in this template.
|Output phases discovery |<p>The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1</p> |SNMP |output.phases.discovery |
|External battery packs discovery | |SNMP |battery.packs.discovery<p>**Filter**:</p>AND <p>- A: {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`</p> |
|External bad battery packs discovery |<p>Discovery of the number of external defective battery packs.</p> |SNMP |battery.packs.bad.discovery |
-|External sensor port 1 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor1.discovery |
-|External sensor port 2 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor2.discovery |
+|External sensor port 1 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor1.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR1_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
+|External sensor port 2 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor2.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR2_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
## Items collected
@@ -64,12 +64,12 @@ There are no template links in this template.
|-----|----|-----------|----|---------------------|
|General |Model |<p>MIB: PowerNet-MIB</p><p>The UPS model name (e.g. 'APC Smart-UPS 600').</p> |SNMP |system.model[upsBasicIdentModel]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|General |Serial number |<p>MIB: PowerNet-MIB</p><p>An 8-character string identifying the serial number of</p><p> the UPS internal microprocessor. This number is set at</p><p> the factory. NOTE: This number does NOT correspond to</p><p> the serial number on the rear of the UPS.</p> |SNMP |system.sn[upsAdvIdentSerialNumber]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
-|General |SNMP traps (fallback) |<p>Item is used to collect all SNMP traps unmatched by other snmptrap items</p> |SNMP_TRAP |snmptrap.fallback |
+|General |SNMP traps (fallback) |<p>The item is used to collect all SNMP traps unmatched by other snmptrap items</p> |SNMP_TRAP |snmptrap.fallback |
|General |System location |<p>MIB: SNMPv2-MIB</p><p>The physical location of this node (e.g., `telephone closet,</p><p>3rd floor'). If the location is unknown, the value is the zero-length string.</p> |SNMP |system.location[sysLocation.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
-|General |System contact details |<p>MIB: SNMPv2-MIB</p><p>The textual identification of the contact person for this managed</p><p>node, together with information on how to contact this person. If no contact</p><p>information is known, the value is the zero-length string.</p> |SNMP |system.contact[sysContact.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `1d`</p> |
+|General |System contact details |<p>MIB: SNMPv2-MIB</p><p>The textual identification of the contact person for this managed</p><p>node, together with information on how to contact this person. If no contact</p><p>information is known, the value is the zero-length string.</p> |SNMP |system.contact[sysContact.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `12h`</p> |
|General |System object ID |<p>MIB: SNMPv2-MIB</p><p>The vendor's authoritative identification of the network management</p><p>subsystem contained in the entity. This value is allocated within the SMI enterprises</p><p>subtree (1.3.6.1.4.1) and provides an easy and unambiguous means for determining`what</p><p>kind of box' is being managed. For example, if vendor`Flintstones, Inc.' was</p><p>assigned the subtree1.3.6.1.4.1.4242, it could assign the identifier 1.3.6.1.4.1.4242.1.1</p><p>to its `Fred Router'.</p> |SNMP |system.objectid[sysObjectID.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|General |System name |<p>MIB: SNMPv2-MIB</p><p>An administratively-assigned name for this managed node.By</p><p>convention, this is the node's fully-qualified domain name. If the name is unknown,</p><p>the value is the zero-length string.</p> |SNMP |system.name[sysName.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
-|General |System description |<p>MIB: SNMPv2-MIB</p><p>A textual description of the entity. This value should</p><p>include the full name and version identification of the system's hardware type, software operating-system, and</p><p>networking software.</p> |SNMP |system.descr[sysDescr.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `1d`</p> |
+|General |System description |<p>MIB: SNMPv2-MIB</p><p>A textual description of the entity. This value should</p><p>include the full name and version identification of the system's hardware type, software operating-system, and</p><p>networking software.</p> |SNMP |system.descr[sysDescr.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `12h`</p> |
|General |{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Serial number |<p>MIB: PowerNet-MIB</p><p>The battery pack serial number.</p> |SNMP |system.sn[upsHighPrecBatteryPackSerialNumber.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Battery status |<p>MIB: PowerNet-MIB</p><p>The status of the UPS batteries. A batteryLow(3) value</p><p> indicates the UPS will be unable to sustain the current</p><p> load, and its services will be lost if power is not restored.</p><p> The amount of run time in reserve at the time of low battery</p><p> can be configured by the upsAdvConfigLowBatteryRunTime.</p><p> A batteryInFaultCondition(4)value indicates that a battery</p><p> installed has an internal error condition.</p> |SNMP |battery.status[upsBasicBatteryStatus]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Battery capacity |<p>MIB: PowerNet-MIB</p><p>The remaining battery capacity expressed as</p><p> percentage of full capacity.</p> |SNMP |battery.capacity[upsHighPrecBatteryCapacity]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
@@ -87,7 +87,7 @@ There are no template links in this template.
|Status |Output current |<p>MIB: PowerNet-MIB</p><p>The current in amperes drawn by the load on the UPS.</p> |SNMP |output.current[upsHighPrecOutputCurrent]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Output status |<p>MIB: PowerNet-MIB</p><p>The current state of the UPS. If the UPS is unable to</p><p> determine the state of the UPS this variable is set</p><p> to unknown(1).</p><p>During self-test most UPSes report onBattery(3) but</p><p> some that support it will report onBatteryTest(15).</p><p> To determine self-test status across all UPSes, refer</p><p> to the upsBasicStateOutputState OID.</p> |SNMP |output.status[upsBasicOutputStatus]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Uptime |<p>MIB: SNMPv2-MIB</p><p>The time (in hundredths of a second) since the network management</p><p>portion of the system was last re-initialized.</p> |SNMP |system.uptime[sysUpTime.0]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.01`</p> |
-|Status |SNMP agent availability |<p>-</p> |INTERNAL |zabbix[host,snmp,available]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
+|Status |SNMP agent availability |<p>Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list.</p><p>Possible value:</p><p>0 - not available</p><p>1 - available</p><p>2 - unknown</p> |INTERNAL |zabbix[host,snmp,available]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |{#PHASEINDEX}: Phase input voltage |<p>MIB: PowerNet-MIB</p><p>The input voltage in VAC, or -1 if it's unsupported</p><p> by this UPS.</p> |SNMP |phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |{#PHASEINDEX}: Phase input current |<p>MIB: PowerNet-MIB</p><p>The input current in 0.1 amperes, or -0.1 if it's</p><p> unsupported by this UPS.</p> |SNMP |phase.input.current[upsPhaseInputCurrent.1.1.{#PHASEINDEX}]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |{#PHASEINDEX}: Phase output voltage |<p>MIB: PowerNet-MIB</p><p>The output voltage in VAC, or -1 if it's unsupported</p><p> by this UPS.</p> |SNMP |phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
@@ -109,39 +109,39 @@ There are no template links in this template.
|Name|Description|Expression|Severity|Dependencies and additional info|
|----|-----------|----|----|----|
-|System name has changed (new name: {ITEM.VALUE}) |<p>System name has changed. Ack to close.</p> |`{TEMPLATE_NAME:system.name[sysName.0].diff()}=1 and {TEMPLATE_NAME:system.name[sysName.0].strlen()}>0` |INFO |<p>Manual close: YES</p> |
-|Battery has an internal error condition |<p>A battery installed has an internal error condition.</p> |`{TEMPLATE_NAME:battery.status[upsBasicBatteryStatus].last()}=4` |AVERAGE | |
-|Battery is Low |<p>The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.</p> |`{TEMPLATE_NAME:battery.status[upsBasicBatteryStatus].last()}=3` |AVERAGE | |
-|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) | |`{TEMPLATE_NAME:battery.capacity[upsHighPrecBatteryCapacity].last()} < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
-|Battery needs replacement |<p>A battery installed has an internal error condition.</p> |`{TEMPLATE_NAME:battery.replace_indicator[upsAdvBatteryReplaceIndicator].last()}=2` |HIGH | |
-|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:battery.temperature[upsHighPrecBatteryTemperature].min({$TIME.PERIOD})} > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
-|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:input.voltage[upsHighPrecInputLineVoltage].min({$TIME.PERIOD})} > 0 and ({TEMPLATE_NAME:input.voltage[upsHighPrecInputLineVoltage].min({$TIME.PERIOD})} > {$UPS.INPUT_VOLT.MAX.WARN} or {TEMPLATE_NAME:input.voltage[upsHighPrecInputLineVoltage].max({$TIME.PERIOD})} < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
-|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:input.frequency[upsHighPrecInputFrequency].min({$TIME.PERIOD})} > 0 and ({TEMPLATE_NAME:input.frequency[upsHighPrecInputFrequency].min({$TIME.PERIOD})} > {$UPS.INPUT_FREQ.MAX.WARN} or {TEMPLATE_NAME:input.frequency[upsHighPrecInputFrequency].max({$TIME.PERIOD})} < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
-|Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD}) |<p>A battery installed has an internal error condition.</p> |`{TEMPLATE_NAME:output.load[upsHighPrecOutputLoad].min({$TIME.PERIOD})} > {$UPS.OUTPUT.MAX.WARN}` |HIGH | |
-|UPS is Timed Sleeping | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=5` |AVERAGE | |
-|UPS is Switched Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=9` |AVERAGE | |
-|UPS is Software Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=6` |AVERAGE | |
-|UPS is Sleeping Until Power Return | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=11` |AVERAGE | |
-|UPS is Rebooting | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=8` |AVERAGE | |
-|UPS is On Smart Trim | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=12` |AVERAGE | |
-|UPS is on Smart Boost | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=4` |AVERAGE | |
-|UPS is on battery | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=3` |AVERAGE | |
-|UPS is Off | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=7` |AVERAGE | |
-|UPS is Emergency Static Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=16` |AVERAGE | |
-|UPS is Hardware Failure Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=10` |AVERAGE | |
-|{HOST.NAME} has been restarted (uptime < 10m) |<p>Uptime is less than 10 minutes</p> |`{TEMPLATE_NAME:system.uptime[sysUpTime.0].last()}<10m` |WARNING |<p>Manual close: YES</p><p>**Depends on**:</p><p>- No SNMP data collection</p> |
-|No SNMP data collection |<p>SNMP is not available for polling. Please check device connectivity and SNMP settings.</p> |`{TEMPLATE_NAME:zabbix[host,snmp,available].max({$SNMP.TIMEOUT})}=0` |WARNING | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}].min({$TIME.PERIOD})} > {$UPS.INPUT_VOLT.MAX.WARN} or {TEMPLATE_NAME:phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}].max({$TIME.PERIOD})} < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}].min({$TIME.PERIOD})} > {$UPS.INPUT_VOLT.MAX.WARN} or {TEMPLATE_NAME:phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}].max({$TIME.PERIOD})} < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |<p>The battery cartridge status:</p><p>bit 0 Disconnected</p><p>bit 1 Overvoltage</p><p>bit 2 NeedsReplacement</p><p>bit 3 OvertemperatureCritical</p><p>bit 4 Charger</p><p>bit 5 TemperatureSensor</p><p>bit 6 BusSoftStart</p><p>bit 7 OvertemperatureWarning</p><p>bit 8 GeneralError</p><p>bit 9 Communication</p><p>bit 10 DisconnectedFrame</p><p>bit 11 FirmwareMismatch</p> |`{TEMPLATE_NAME:battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}].regexp("^(0{16})$")}=0` |WARNING | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}].min({$TIME.PERIOD})} > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |<p>The battery cartridge health.</p><p> bit 0 Battery lifetime okay</p><p> bit 1 Battery lifetime near end, order replacement cartridge</p><p> bit 2 Battery lifetime exceeded, replace battery</p><p> bit 3 Battery lifetime near end acknowledged, order replacement cartridge</p><p> bit 4 Battery lifetime exceeded acknowledged, replace battery</p><p> bit 5 Battery measured lifetime near end, order replacement cartridge</p><p> bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge</p> |`{TEMPLATE_NAME:battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}].regexp("^(0)[0|1]{15}$")}=1` |WARNING | |
-|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}].last()}=4` |INFO | |
-|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}].last()}=2` |AVERAGE | |
-|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}].last()}=3` |HIGH | |
-|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}].last()}=4` |INFO | |
-|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}].last()}=2` |AVERAGE | |
-|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}].last()}=3` |HIGH | |
+|System name has changed (new name: {ITEM.VALUE}) |<p>System name has changed. Ack to close.</p> |`last(/APC Smart-UPS 2200 RM SNMP/system.name[sysName.0],#1)<>last(/APC Smart-UPS 2200 RM SNMP/system.name[sysName.0],#2) and length(last(/APC Smart-UPS 2200 RM SNMP/system.name[sysName.0]))>0` |INFO |<p>Manual close: YES</p> |
+|Battery has an internal error condition |<p>A battery installed has an internal error condition.</p> |`last(/APC Smart-UPS 2200 RM SNMP/battery.status[upsBasicBatteryStatus])=4` |AVERAGE | |
+|Battery is Low |<p>The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.</p> |`last(/APC Smart-UPS 2200 RM SNMP/battery.status[upsBasicBatteryStatus])=3` |AVERAGE | |
+|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) | |`last(/APC Smart-UPS 2200 RM SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
+|Battery needs replacement |<p>A battery installed has an internal error condition.</p> |`last(/APC Smart-UPS 2200 RM SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2` |HIGH | |
+|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC Smart-UPS 2200 RM SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS 2200 RM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS 2200 RM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS 2200 RM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
+|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) | |`min(/APC Smart-UPS 2200 RM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS 2200 RM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC Smart-UPS 2200 RM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
+|Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD}) |<p>A battery installed has an internal error condition.</p> |`min(/APC Smart-UPS 2200 RM SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}` |HIGH | |
+|UPS is Timed Sleeping | |`last(/APC Smart-UPS 2200 RM SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | |
+|UPS is Switched Bypass | |`last(/APC Smart-UPS 2200 RM SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | |
+|UPS is Software Bypass | |`last(/APC Smart-UPS 2200 RM SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | |
+|UPS is Sleeping Until Power Return | |`last(/APC Smart-UPS 2200 RM SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | |
+|UPS is Rebooting | |`last(/APC Smart-UPS 2200 RM SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | |
+|UPS is On Smart Trim | |`last(/APC Smart-UPS 2200 RM SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | |
+|UPS is on Smart Boost | |`last(/APC Smart-UPS 2200 RM SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | |
+|UPS is on battery | |`last(/APC Smart-UPS 2200 RM SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | |
+|UPS is Off | |`last(/APC Smart-UPS 2200 RM SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | |
+|UPS is Emergency Static Bypass | |`last(/APC Smart-UPS 2200 RM SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | |
+|UPS is Hardware Failure Bypass | |`last(/APC Smart-UPS 2200 RM SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | |
+|{HOST.NAME} has been restarted (uptime < 10m) |<p>Uptime is less than 10 minutes</p> |`last(/APC Smart-UPS 2200 RM SNMP/system.uptime[sysUpTime.0])<10m` |WARNING |<p>Manual close: YES</p><p>**Depends on**:</p><p>- No SNMP data collection</p> |
+|No SNMP data collection |<p>SNMP is not available for polling. Please check device connectivity and SNMP settings.</p> |`max(/APC Smart-UPS 2200 RM SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0` |WARNING | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS 2200 RM SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS 2200 RM SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS 2200 RM SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS 2200 RM SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |<p>The battery cartridge status:</p><p>bit 0 Disconnected</p><p>bit 1 Overvoltage</p><p>bit 2 NeedsReplacement</p><p>bit 3 OvertemperatureCritical</p><p>bit 4 Charger</p><p>bit 5 TemperatureSensor</p><p>bit 6 BusSoftStart</p><p>bit 7 OvertemperatureWarning</p><p>bit 8 GeneralError</p><p>bit 9 Communication</p><p>bit 10 DisconnectedFrame</p><p>bit 11 FirmwareMismatch</p> |`find(/APC Smart-UPS 2200 RM SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0` |WARNING | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC Smart-UPS 2200 RM SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |<p>The battery cartridge health.</p><p> bit 0 Battery lifetime okay</p><p> bit 1 Battery lifetime near end, order replacement cartridge</p><p> bit 2 Battery lifetime exceeded, replace battery</p><p> bit 3 Battery lifetime near end acknowledged, order replacement cartridge</p><p> bit 4 Battery lifetime exceeded acknowledged, replace battery</p><p> bit 5 Battery measured lifetime near end, order replacement cartridge</p><p> bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge</p> |`find(/APC Smart-UPS 2200 RM SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1` |WARNING | |
+|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`last(/APC Smart-UPS 2200 RM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4` |INFO | |
+|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`last(/APC Smart-UPS 2200 RM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2` |AVERAGE | |
+|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`last(/APC Smart-UPS 2200 RM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=3` |HIGH | |
+|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`last(/APC Smart-UPS 2200 RM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=4` |INFO | |
+|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`last(/APC Smart-UPS 2200 RM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=2` |AVERAGE | |
+|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`last(/APC Smart-UPS 2200 RM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=3` |HIGH | |
## Feedback
diff --git a/templates/power/apc/apc_ups_smart_2200_rm_snmp/template_power_apc_ups_smart_2200_rm_snmp.yaml b/templates/power/apc/apc_ups_smart_2200_rm_snmp/template_power_apc_ups_smart_2200_rm_snmp.yaml
index e5cb18dc812..6542e938299 100644
--- a/templates/power/apc/apc_ups_smart_2200_rm_snmp/template_power_apc_ups_smart_2200_rm_snmp.yaml
+++ b/templates/power/apc/apc_ups_smart_2200_rm_snmp/template_power_apc_ups_smart_2200_rm_snmp.yaml
@@ -1,6 +1,6 @@
zabbix_export:
- version: '5.4'
- date: '2021-05-11T08:05:02Z'
+ version: '6.0'
+ date: '2021-10-28T08:23:52Z'
groups:
-
uuid: 3dcd5bbe90534f9e8eb5c2d53756af63
@@ -19,7 +19,7 @@ zabbix_export:
You can discuss this template or leave feedback on our forum https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups
- Template tooling version used: 0.38
+ Template tooling version used: 0.39
groups:
-
name: Templates/Power
@@ -48,7 +48,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 58a0749ef9c94cf9802a62d274b6dad9
@@ -76,7 +77,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 147e0b7b466e402ba59d73d66801ef1a
name: 'Battery last replace date'
@@ -101,7 +103,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 4c1107eb93114d9096518dc134e08bdc
name: 'Battery replace indicator'
@@ -121,7 +124,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 8370727883de45dfa6b6d79f60cc86b3
@@ -153,7 +157,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 078719d0396247bca76d85e1e4c650de
name: 'Battery status'
@@ -179,7 +184,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 2fb002b1a4584aa0bf0389360171893c
@@ -217,7 +223,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 1e8c0b3d2d65487199e7fc3e1dde6e50
@@ -248,7 +255,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: b83275fc1176451dacaa28606edf045a
name: 'Input fail cause'
@@ -291,7 +299,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: cfd390d57dbc4046a3a6af384420b697
name: 'Input frequency'
@@ -315,7 +324,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: b89b059a430842aebbd3e6af71514303
@@ -346,7 +356,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 2dbc2b96d332488cae4cbf87c985c6b0
@@ -377,7 +388,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: df799c65dbe5437aa941de3e6d386b26
name: 'Output load'
@@ -402,7 +414,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: edb059eeee004d80a9b42154f16ab18a
@@ -436,7 +449,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 20ffc78c2f314ff58b5e75907605c82f
@@ -516,7 +530,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 94d838cc8cf2438296477c0139a3c152
name: 'SNMP traps (fallback)'
@@ -525,18 +540,19 @@ zabbix_export:
history: 2w
trends: '0'
value_type: LOG
- description: 'Item is used to collect all SNMP traps unmatched by other snmptrap items'
+ description: 'The item is used to collect all SNMP traps unmatched by other snmptrap items'
logtimefmt: 'hh:mm:sszyyyy/MM/dd'
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 943b146891ac461c92d286704a0864b2
name: 'System contact details'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.2.1.1.4.0
key: 'system.contact[sysContact.0]'
- delay: 1h
+ delay: 15m
history: 2w
trends: '0'
value_type: CHAR
@@ -550,17 +566,18 @@ zabbix_export:
-
type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- - 1d
+ - 12h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: e5d72eba4dfb41f8ae73904c936dd64b
name: 'System description'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.2.1.1.1.0
key: 'system.descr[sysDescr.0]'
- delay: 1h
+ delay: 15m
history: 2w
trends: '0'
value_type: CHAR
@@ -573,10 +590,11 @@ zabbix_export:
-
type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- - 1d
+ - 12h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: ac995904f95240d9b1f44c27adea5731
name: 'System location'
@@ -599,7 +617,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 1ba45d867e3d4bb99eeb8c0c320ef127
name: Model
@@ -620,7 +639,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: d9452c921e4946719726b292d8c0cbd6
name: 'System name'
@@ -644,7 +664,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
triggers:
-
uuid: 30153a623f0649e380de8f9ec5086b48
@@ -678,7 +699,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 4e87619ed81346d497c3c3f548c342b5
name: 'Serial number'
@@ -702,7 +724,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: f077c3558d24471ca807ea24b3f0c5ea
name: Uptime
@@ -724,7 +747,8 @@ zabbix_export:
- '0.01'
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: f23282a63bec4b1d951f80439947672d
@@ -743,6 +767,12 @@ zabbix_export:
type: INTERNAL
key: 'zabbix[host,snmp,available]'
history: 7d
+ description: |
+ Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list.
+ Possible value:
+ 0 - not available
+ 1 - available
+ 2 - unknown
valuemap:
name: zabbix.host.available
preprocessing:
@@ -752,7 +782,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: e9dc225935594e8aa25fb80fcfa68e4c
@@ -791,7 +822,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 38aa32616e964db088f4faff12867f1a
name: 'External battery packs discovery'
@@ -828,7 +860,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 2e3adbdd7c9a4f3f9f151d19e69885bf
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery pack cartridge health'
@@ -855,7 +888,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 02e19fb51d6949cdb99a6aafa71ff654
@@ -903,7 +937,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: a4f42d0a944f41349e0d206f1181bd3b
@@ -948,7 +983,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: cb9603c5b7674e12a1a1ac98d4b73a65
@@ -976,7 +1012,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: e428310ecc5f4a53ab7932bcf1247a30
name: 'External sensor port 1 discovery'
@@ -1007,7 +1044,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: c4bd5c3b0af145448aa2b084738f5149
name: '{#EXTERNAL_SENSOR1_NAME}: Sensor alarm status'
@@ -1031,7 +1069,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 603b13b89c7b4ad0bd51d63b93501174
@@ -1071,7 +1110,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
overrides:
-
name: Temp
@@ -1119,7 +1159,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: fc4623c5e962448dbffc98301ddcef4b
name: '{#EXTERNAL_SENSOR2_NAME}: Sensor alarm status'
@@ -1143,7 +1184,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 7639c07a79054f9b99687f84db5c95a0
@@ -1183,7 +1225,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
overrides:
-
name: Temp
@@ -1234,7 +1277,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: dac612b382ce4b93b588e2ba43c01c68
name: '{#PHASEINDEX}: Phase input voltage'
@@ -1255,7 +1299,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 0e9c22ab97cb4db8b96fb907e4b21e04
@@ -1297,7 +1342,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 3af338de874c439daeba535156033317
name: '{#PHASEINDEX}: Phase output load, %'
@@ -1319,7 +1365,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: a7aecf3b0c2e448b9c09babc79c52380
name: '{#PHASEINDEX}: Phase output voltage'
@@ -1340,7 +1387,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 91ac886a5dda41cdb6a6912672d70625
diff --git a/templates/power/apc/apc_ups_smart_3000_xlm_snmp/README.md b/templates/power/apc/apc_ups_smart_3000_xlm_snmp/README.md
index 1e7721cc06d..4d03cf2a90c 100644
--- a/templates/power/apc/apc_ups_smart_3000_xlm_snmp/README.md
+++ b/templates/power/apc/apc_ups_smart_3000_xlm_snmp/README.md
@@ -55,8 +55,8 @@ There are no template links in this template.
|Output phases discovery |<p>The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1</p> |SNMP |output.phases.discovery |
|External battery packs discovery | |SNMP |battery.packs.discovery<p>**Filter**:</p>AND <p>- A: {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`</p> |
|External bad battery packs discovery |<p>Discovery of the number of external defective battery packs.</p> |SNMP |battery.packs.bad.discovery |
-|External sensor port 1 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor1.discovery |
-|External sensor port 2 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor2.discovery |
+|External sensor port 1 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor1.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR1_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
+|External sensor port 2 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor2.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR2_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
## Items collected
@@ -64,12 +64,12 @@ There are no template links in this template.
|-----|----|-----------|----|---------------------|
|General |Model |<p>MIB: PowerNet-MIB</p><p>The UPS model name (e.g. 'APC Smart-UPS 600').</p> |SNMP |system.model[upsBasicIdentModel]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|General |Serial number |<p>MIB: PowerNet-MIB</p><p>An 8-character string identifying the serial number of</p><p> the UPS internal microprocessor. This number is set at</p><p> the factory. NOTE: This number does NOT correspond to</p><p> the serial number on the rear of the UPS.</p> |SNMP |system.sn[upsAdvIdentSerialNumber]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
-|General |SNMP traps (fallback) |<p>Item is used to collect all SNMP traps unmatched by other snmptrap items</p> |SNMP_TRAP |snmptrap.fallback |
+|General |SNMP traps (fallback) |<p>The item is used to collect all SNMP traps unmatched by other snmptrap items</p> |SNMP_TRAP |snmptrap.fallback |
|General |System location |<p>MIB: SNMPv2-MIB</p><p>The physical location of this node (e.g., `telephone closet,</p><p>3rd floor'). If the location is unknown, the value is the zero-length string.</p> |SNMP |system.location[sysLocation.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
-|General |System contact details |<p>MIB: SNMPv2-MIB</p><p>The textual identification of the contact person for this managed</p><p>node, together with information on how to contact this person. If no contact</p><p>information is known, the value is the zero-length string.</p> |SNMP |system.contact[sysContact.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `1d`</p> |
+|General |System contact details |<p>MIB: SNMPv2-MIB</p><p>The textual identification of the contact person for this managed</p><p>node, together with information on how to contact this person. If no contact</p><p>information is known, the value is the zero-length string.</p> |SNMP |system.contact[sysContact.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `12h`</p> |
|General |System object ID |<p>MIB: SNMPv2-MIB</p><p>The vendor's authoritative identification of the network management</p><p>subsystem contained in the entity. This value is allocated within the SMI enterprises</p><p>subtree (1.3.6.1.4.1) and provides an easy and unambiguous means for determining`what</p><p>kind of box' is being managed. For example, if vendor`Flintstones, Inc.' was</p><p>assigned the subtree1.3.6.1.4.1.4242, it could assign the identifier 1.3.6.1.4.1.4242.1.1</p><p>to its `Fred Router'.</p> |SNMP |system.objectid[sysObjectID.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|General |System name |<p>MIB: SNMPv2-MIB</p><p>An administratively-assigned name for this managed node.By</p><p>convention, this is the node's fully-qualified domain name. If the name is unknown,</p><p>the value is the zero-length string.</p> |SNMP |system.name[sysName.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
-|General |System description |<p>MIB: SNMPv2-MIB</p><p>A textual description of the entity. This value should</p><p>include the full name and version identification of the system's hardware type, software operating-system, and</p><p>networking software.</p> |SNMP |system.descr[sysDescr.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `1d`</p> |
+|General |System description |<p>MIB: SNMPv2-MIB</p><p>A textual description of the entity. This value should</p><p>include the full name and version identification of the system's hardware type, software operating-system, and</p><p>networking software.</p> |SNMP |system.descr[sysDescr.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `12h`</p> |
|General |{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Serial number |<p>MIB: PowerNet-MIB</p><p>The battery pack serial number.</p> |SNMP |system.sn[upsHighPrecBatteryPackSerialNumber.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Battery status |<p>MIB: PowerNet-MIB</p><p>The status of the UPS batteries. A batteryLow(3) value</p><p> indicates the UPS will be unable to sustain the current</p><p> load, and its services will be lost if power is not restored.</p><p> The amount of run time in reserve at the time of low battery</p><p> can be configured by the upsAdvConfigLowBatteryRunTime.</p><p> A batteryInFaultCondition(4)value indicates that a battery</p><p> installed has an internal error condition.</p> |SNMP |battery.status[upsBasicBatteryStatus]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Battery capacity |<p>MIB: PowerNet-MIB</p><p>The remaining battery capacity expressed as</p><p> percentage of full capacity.</p> |SNMP |battery.capacity[upsHighPrecBatteryCapacity]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
@@ -87,7 +87,7 @@ There are no template links in this template.
|Status |Output current |<p>MIB: PowerNet-MIB</p><p>The current in amperes drawn by the load on the UPS.</p> |SNMP |output.current[upsHighPrecOutputCurrent]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Output status |<p>MIB: PowerNet-MIB</p><p>The current state of the UPS. If the UPS is unable to</p><p> determine the state of the UPS this variable is set</p><p> to unknown(1).</p><p>During self-test most UPSes report onBattery(3) but</p><p> some that support it will report onBatteryTest(15).</p><p> To determine self-test status across all UPSes, refer</p><p> to the upsBasicStateOutputState OID.</p> |SNMP |output.status[upsBasicOutputStatus]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Uptime |<p>MIB: SNMPv2-MIB</p><p>The time (in hundredths of a second) since the network management</p><p>portion of the system was last re-initialized.</p> |SNMP |system.uptime[sysUpTime.0]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.01`</p> |
-|Status |SNMP agent availability |<p>-</p> |INTERNAL |zabbix[host,snmp,available]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
+|Status |SNMP agent availability |<p>Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list.</p><p>Possible value:</p><p>0 - not available</p><p>1 - available</p><p>2 - unknown</p> |INTERNAL |zabbix[host,snmp,available]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |{#PHASEINDEX}: Phase input voltage |<p>MIB: PowerNet-MIB</p><p>The input voltage in VAC, or -1 if it's unsupported</p><p> by this UPS.</p> |SNMP |phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |{#PHASEINDEX}: Phase input current |<p>MIB: PowerNet-MIB</p><p>The input current in 0.1 amperes, or -0.1 if it's</p><p> unsupported by this UPS.</p> |SNMP |phase.input.current[upsPhaseInputCurrent.1.1.{#PHASEINDEX}]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |{#PHASEINDEX}: Phase output voltage |<p>MIB: PowerNet-MIB</p><p>The output voltage in VAC, or -1 if it's unsupported</p><p> by this UPS.</p> |SNMP |phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
@@ -109,39 +109,39 @@ There are no template links in this template.
|Name|Description|Expression|Severity|Dependencies and additional info|
|----|-----------|----|----|----|
-|System name has changed (new name: {ITEM.VALUE}) |<p>System name has changed. Ack to close.</p> |`{TEMPLATE_NAME:system.name[sysName.0].diff()}=1 and {TEMPLATE_NAME:system.name[sysName.0].strlen()}>0` |INFO |<p>Manual close: YES</p> |
-|Battery has an internal error condition |<p>A battery installed has an internal error condition.</p> |`{TEMPLATE_NAME:battery.status[upsBasicBatteryStatus].last()}=4` |AVERAGE | |
-|Battery is Low |<p>The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.</p> |`{TEMPLATE_NAME:battery.status[upsBasicBatteryStatus].last()}=3` |AVERAGE | |
-|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) | |`{TEMPLATE_NAME:battery.capacity[upsHighPrecBatteryCapacity].last()} < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
-|Battery needs replacement |<p>A battery installed has an internal error condition.</p> |`{TEMPLATE_NAME:battery.replace_indicator[upsAdvBatteryReplaceIndicator].last()}=2` |HIGH | |
-|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:battery.temperature[upsHighPrecBatteryTemperature].min({$TIME.PERIOD})} > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
-|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:input.voltage[upsHighPrecInputLineVoltage].min({$TIME.PERIOD})} > 0 and ({TEMPLATE_NAME:input.voltage[upsHighPrecInputLineVoltage].min({$TIME.PERIOD})} > {$UPS.INPUT_VOLT.MAX.WARN} or {TEMPLATE_NAME:input.voltage[upsHighPrecInputLineVoltage].max({$TIME.PERIOD})} < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
-|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:input.frequency[upsHighPrecInputFrequency].min({$TIME.PERIOD})} > 0 and ({TEMPLATE_NAME:input.frequency[upsHighPrecInputFrequency].min({$TIME.PERIOD})} > {$UPS.INPUT_FREQ.MAX.WARN} or {TEMPLATE_NAME:input.frequency[upsHighPrecInputFrequency].max({$TIME.PERIOD})} < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
-|Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD}) |<p>A battery installed has an internal error condition.</p> |`{TEMPLATE_NAME:output.load[upsHighPrecOutputLoad].min({$TIME.PERIOD})} > {$UPS.OUTPUT.MAX.WARN}` |HIGH | |
-|UPS is Timed Sleeping | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=5` |AVERAGE | |
-|UPS is Switched Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=9` |AVERAGE | |
-|UPS is Software Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=6` |AVERAGE | |
-|UPS is Sleeping Until Power Return | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=11` |AVERAGE | |
-|UPS is Rebooting | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=8` |AVERAGE | |
-|UPS is On Smart Trim | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=12` |AVERAGE | |
-|UPS is on Smart Boost | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=4` |AVERAGE | |
-|UPS is on battery | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=3` |AVERAGE | |
-|UPS is Off | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=7` |AVERAGE | |
-|UPS is Emergency Static Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=16` |AVERAGE | |
-|UPS is Hardware Failure Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=10` |AVERAGE | |
-|{HOST.NAME} has been restarted (uptime < 10m) |<p>Uptime is less than 10 minutes</p> |`{TEMPLATE_NAME:system.uptime[sysUpTime.0].last()}<10m` |WARNING |<p>Manual close: YES</p><p>**Depends on**:</p><p>- No SNMP data collection</p> |
-|No SNMP data collection |<p>SNMP is not available for polling. Please check device connectivity and SNMP settings.</p> |`{TEMPLATE_NAME:zabbix[host,snmp,available].max({$SNMP.TIMEOUT})}=0` |WARNING | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}].min({$TIME.PERIOD})} > {$UPS.INPUT_VOLT.MAX.WARN} or {TEMPLATE_NAME:phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}].max({$TIME.PERIOD})} < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}].min({$TIME.PERIOD})} > {$UPS.INPUT_VOLT.MAX.WARN} or {TEMPLATE_NAME:phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}].max({$TIME.PERIOD})} < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |<p>The battery cartridge status:</p><p>bit 0 Disconnected</p><p>bit 1 Overvoltage</p><p>bit 2 NeedsReplacement</p><p>bit 3 OvertemperatureCritical</p><p>bit 4 Charger</p><p>bit 5 TemperatureSensor</p><p>bit 6 BusSoftStart</p><p>bit 7 OvertemperatureWarning</p><p>bit 8 GeneralError</p><p>bit 9 Communication</p><p>bit 10 DisconnectedFrame</p><p>bit 11 FirmwareMismatch</p> |`{TEMPLATE_NAME:battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}].regexp("^(0{16})$")}=0` |WARNING | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}].min({$TIME.PERIOD})} > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |<p>The battery cartridge health.</p><p> bit 0 Battery lifetime okay</p><p> bit 1 Battery lifetime near end, order replacement cartridge</p><p> bit 2 Battery lifetime exceeded, replace battery</p><p> bit 3 Battery lifetime near end acknowledged, order replacement cartridge</p><p> bit 4 Battery lifetime exceeded acknowledged, replace battery</p><p> bit 5 Battery measured lifetime near end, order replacement cartridge</p><p> bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge</p> |`{TEMPLATE_NAME:battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}].regexp("^(0)[0|1]{15}$")}=1` |WARNING | |
-|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}].last()}=4` |INFO | |
-|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}].last()}=2` |AVERAGE | |
-|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}].last()}=3` |HIGH | |
-|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}].last()}=4` |INFO | |
-|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}].last()}=2` |AVERAGE | |
-|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}].last()}=3` |HIGH | |
+|System name has changed (new name: {ITEM.VALUE}) |<p>System name has changed. Ack to close.</p> |`last(/APC Smart-UPS 3000 XLM SNMP/system.name[sysName.0],#1)<>last(/APC Smart-UPS 3000 XLM SNMP/system.name[sysName.0],#2) and length(last(/APC Smart-UPS 3000 XLM SNMP/system.name[sysName.0]))>0` |INFO |<p>Manual close: YES</p> |
+|Battery has an internal error condition |<p>A battery installed has an internal error condition.</p> |`last(/APC Smart-UPS 3000 XLM SNMP/battery.status[upsBasicBatteryStatus])=4` |AVERAGE | |
+|Battery is Low |<p>The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.</p> |`last(/APC Smart-UPS 3000 XLM SNMP/battery.status[upsBasicBatteryStatus])=3` |AVERAGE | |
+|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) | |`last(/APC Smart-UPS 3000 XLM SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
+|Battery needs replacement |<p>A battery installed has an internal error condition.</p> |`last(/APC Smart-UPS 3000 XLM SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2` |HIGH | |
+|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC Smart-UPS 3000 XLM SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS 3000 XLM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS 3000 XLM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS 3000 XLM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
+|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) | |`min(/APC Smart-UPS 3000 XLM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS 3000 XLM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC Smart-UPS 3000 XLM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
+|Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD}) |<p>A battery installed has an internal error condition.</p> |`min(/APC Smart-UPS 3000 XLM SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}` |HIGH | |
+|UPS is Timed Sleeping | |`last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | |
+|UPS is Switched Bypass | |`last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | |
+|UPS is Software Bypass | |`last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | |
+|UPS is Sleeping Until Power Return | |`last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | |
+|UPS is Rebooting | |`last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | |
+|UPS is On Smart Trim | |`last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | |
+|UPS is on Smart Boost | |`last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | |
+|UPS is on battery | |`last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | |
+|UPS is Off | |`last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | |
+|UPS is Emergency Static Bypass | |`last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | |
+|UPS is Hardware Failure Bypass | |`last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | |
+|{HOST.NAME} has been restarted (uptime < 10m) |<p>Uptime is less than 10 minutes</p> |`last(/APC Smart-UPS 3000 XLM SNMP/system.uptime[sysUpTime.0])<10m` |WARNING |<p>Manual close: YES</p><p>**Depends on**:</p><p>- No SNMP data collection</p> |
+|No SNMP data collection |<p>SNMP is not available for polling. Please check device connectivity and SNMP settings.</p> |`max(/APC Smart-UPS 3000 XLM SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0` |WARNING | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS 3000 XLM SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS 3000 XLM SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS 3000 XLM SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS 3000 XLM SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |<p>The battery cartridge status:</p><p>bit 0 Disconnected</p><p>bit 1 Overvoltage</p><p>bit 2 NeedsReplacement</p><p>bit 3 OvertemperatureCritical</p><p>bit 4 Charger</p><p>bit 5 TemperatureSensor</p><p>bit 6 BusSoftStart</p><p>bit 7 OvertemperatureWarning</p><p>bit 8 GeneralError</p><p>bit 9 Communication</p><p>bit 10 DisconnectedFrame</p><p>bit 11 FirmwareMismatch</p> |`find(/APC Smart-UPS 3000 XLM SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0` |WARNING | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC Smart-UPS 3000 XLM SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |<p>The battery cartridge health.</p><p> bit 0 Battery lifetime okay</p><p> bit 1 Battery lifetime near end, order replacement cartridge</p><p> bit 2 Battery lifetime exceeded, replace battery</p><p> bit 3 Battery lifetime near end acknowledged, order replacement cartridge</p><p> bit 4 Battery lifetime exceeded acknowledged, replace battery</p><p> bit 5 Battery measured lifetime near end, order replacement cartridge</p><p> bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge</p> |`find(/APC Smart-UPS 3000 XLM SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1` |WARNING | |
+|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`last(/APC Smart-UPS 3000 XLM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4` |INFO | |
+|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`last(/APC Smart-UPS 3000 XLM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2` |AVERAGE | |
+|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`last(/APC Smart-UPS 3000 XLM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=3` |HIGH | |
+|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`last(/APC Smart-UPS 3000 XLM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=4` |INFO | |
+|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`last(/APC Smart-UPS 3000 XLM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=2` |AVERAGE | |
+|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`last(/APC Smart-UPS 3000 XLM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=3` |HIGH | |
## Feedback
diff --git a/templates/power/apc/apc_ups_smart_3000_xlm_snmp/template_power_apc_ups_smart_3000_xlm_snmp.yaml b/templates/power/apc/apc_ups_smart_3000_xlm_snmp/template_power_apc_ups_smart_3000_xlm_snmp.yaml
index 5992ce127bb..77bbdcdf865 100644
--- a/templates/power/apc/apc_ups_smart_3000_xlm_snmp/template_power_apc_ups_smart_3000_xlm_snmp.yaml
+++ b/templates/power/apc/apc_ups_smart_3000_xlm_snmp/template_power_apc_ups_smart_3000_xlm_snmp.yaml
@@ -1,6 +1,6 @@
zabbix_export:
- version: '5.4'
- date: '2021-05-11T08:04:57Z'
+ version: '6.0'
+ date: '2021-10-28T08:22:51Z'
groups:
-
uuid: 3dcd5bbe90534f9e8eb5c2d53756af63
@@ -19,7 +19,7 @@ zabbix_export:
You can discuss this template or leave feedback on our forum https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups
- Template tooling version used: 0.38
+ Template tooling version used: 0.39
groups:
-
name: Templates/Power
@@ -48,7 +48,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 13fe1336e40c4bafb8dbd409497abf8f
@@ -76,7 +77,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 1928e58e65a34b188916086bad5b8725
name: 'Battery last replace date'
@@ -101,7 +103,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: b50a17ab043c404990dd088ac9f74078
name: 'Battery replace indicator'
@@ -121,7 +124,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 4590ac935e044c19978fe01d117e2995
@@ -153,7 +157,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 9fa77fdcbd7343ca904c6282efcb7c72
name: 'Battery status'
@@ -179,7 +184,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: e98ba83e63d246408aeeda76da62d5a4
@@ -217,7 +223,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 1c67af712882479bbf7143bd3e16ed77
@@ -248,7 +255,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 7b7d6fdeea2e49c9bb74eb301ecca93a
name: 'Input fail cause'
@@ -291,7 +299,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: ab28b72c192e48b5819079bd386ba8ea
name: 'Input frequency'
@@ -315,7 +324,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 78e47553d4bb488991067f53cc8f8a01
@@ -346,7 +356,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 28ad85fa6035433f9a7ec45a8393b603
@@ -377,7 +388,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: a2613c8d71864594a0c94064d99e059e
name: 'Output load'
@@ -402,7 +414,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: f667172a5cf44ed6b98f2bb38a3f3806
@@ -436,7 +449,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 80e30d37b1724c6ba1d58cedbcf6307f
@@ -516,7 +530,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 92c2ef138bf148199cdb6d9684b6fa23
name: 'SNMP traps (fallback)'
@@ -525,18 +540,19 @@ zabbix_export:
history: 2w
trends: '0'
value_type: LOG
- description: 'Item is used to collect all SNMP traps unmatched by other snmptrap items'
+ description: 'The item is used to collect all SNMP traps unmatched by other snmptrap items'
logtimefmt: 'hh:mm:sszyyyy/MM/dd'
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: fbcbe2cffc8c4bb6b11276cdd03376c3
name: 'System contact details'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.2.1.1.4.0
key: 'system.contact[sysContact.0]'
- delay: 1h
+ delay: 15m
history: 2w
trends: '0'
value_type: CHAR
@@ -550,17 +566,18 @@ zabbix_export:
-
type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- - 1d
+ - 12h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: a312df9175ca45528375398f56fa3b3b
name: 'System description'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.2.1.1.1.0
key: 'system.descr[sysDescr.0]'
- delay: 1h
+ delay: 15m
history: 2w
trends: '0'
value_type: CHAR
@@ -573,10 +590,11 @@ zabbix_export:
-
type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- - 1d
+ - 12h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: a5c6c4c44132439abd0e5fd88e3c90cf
name: 'System location'
@@ -599,7 +617,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 272883d0a1cd4bb585a6ede50336c873
name: Model
@@ -620,7 +639,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 1f591627fea54a9ebdd8f10cbf39b9ed
name: 'System name'
@@ -644,7 +664,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
triggers:
-
uuid: c9b1f69a882148a180ec1e2600068671
@@ -678,7 +699,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 0c36d0bb59a44db2b80ae4a4ff2d7c1b
name: 'Serial number'
@@ -702,7 +724,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 39dd6b9b815a4a838a43d2ebf3fcc8f9
name: Uptime
@@ -724,7 +747,8 @@ zabbix_export:
- '0.01'
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 15764a5819174d3fadc75436f42650fb
@@ -743,6 +767,12 @@ zabbix_export:
type: INTERNAL
key: 'zabbix[host,snmp,available]'
history: 7d
+ description: |
+ Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list.
+ Possible value:
+ 0 - not available
+ 1 - available
+ 2 - unknown
valuemap:
name: zabbix.host.available
preprocessing:
@@ -752,7 +782,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 71994587c45546bfb0950606d7f69936
@@ -791,7 +822,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: a0d8d681bfb54c1d9792beaf3f708d69
name: 'External battery packs discovery'
@@ -828,7 +860,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: b86ac9ee81fe40c8995618c387775270
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery pack cartridge health'
@@ -855,7 +888,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 400987be93b34a78865685fedb72a5ee
@@ -903,7 +937,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 03a100c0bb8d457690e2467c502fcadb
@@ -948,7 +983,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 9760f6a951a64e3fa6c67a9dd751f79a
@@ -976,7 +1012,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 88f5bc98004740fe886f5b1144de2c35
name: 'External sensor port 1 discovery'
@@ -1007,7 +1044,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 04425d6cc153491d9cb710b875f8c9cb
name: '{#EXTERNAL_SENSOR1_NAME}: Sensor alarm status'
@@ -1031,7 +1069,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 9ba51ee0398444e1bd12cb805c1f7452
@@ -1071,7 +1110,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
overrides:
-
name: Temp
@@ -1119,7 +1159,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 58a2e39cd7fc4fe1bd825ce6086b4931
name: '{#EXTERNAL_SENSOR2_NAME}: Sensor alarm status'
@@ -1143,7 +1184,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 944fd36a2ad14fd29dd063ad03197cd7
@@ -1183,7 +1225,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
overrides:
-
name: Temp
@@ -1234,7 +1277,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 593b355efb0a4e40bd3527c24994da0a
name: '{#PHASEINDEX}: Phase input voltage'
@@ -1255,7 +1299,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 709ad3894aca49f0be051d338d4ffaed
@@ -1297,7 +1342,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 32c88f722f074fd699d880a603aaa91b
name: '{#PHASEINDEX}: Phase output load, %'
@@ -1319,7 +1365,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 0502345887e54bbc849a9a4e46a571da
name: '{#PHASEINDEX}: Phase output voltage'
@@ -1340,7 +1387,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: dbdf66b61dce4b6dbf49371e9b1f8146
diff --git a/templates/power/apc/apc_ups_smart_rt_1000_rm_xl_snmp/README.md b/templates/power/apc/apc_ups_smart_rt_1000_rm_xl_snmp/README.md
index 003412a353c..6e6e8ade840 100644
--- a/templates/power/apc/apc_ups_smart_rt_1000_rm_xl_snmp/README.md
+++ b/templates/power/apc/apc_ups_smart_rt_1000_rm_xl_snmp/README.md
@@ -55,8 +55,8 @@ There are no template links in this template.
|Output phases discovery |<p>The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1</p> |SNMP |output.phases.discovery |
|External battery packs discovery | |SNMP |battery.packs.discovery<p>**Filter**:</p>AND <p>- A: {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`</p> |
|External bad battery packs discovery |<p>Discovery of the number of external defective battery packs.</p> |SNMP |battery.packs.bad.discovery |
-|External sensor port 1 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor1.discovery |
-|External sensor port 2 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor2.discovery |
+|External sensor port 1 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor1.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR1_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
+|External sensor port 2 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor2.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR2_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
## Items collected
@@ -64,12 +64,12 @@ There are no template links in this template.
|-----|----|-----------|----|---------------------|
|General |Model |<p>MIB: PowerNet-MIB</p><p>The UPS model name (e.g. 'APC Smart-UPS 600').</p> |SNMP |system.model[upsBasicIdentModel]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|General |Serial number |<p>MIB: PowerNet-MIB</p><p>An 8-character string identifying the serial number of</p><p> the UPS internal microprocessor. This number is set at</p><p> the factory. NOTE: This number does NOT correspond to</p><p> the serial number on the rear of the UPS.</p> |SNMP |system.sn[upsAdvIdentSerialNumber]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
-|General |SNMP traps (fallback) |<p>Item is used to collect all SNMP traps unmatched by other snmptrap items</p> |SNMP_TRAP |snmptrap.fallback |
+|General |SNMP traps (fallback) |<p>The item is used to collect all SNMP traps unmatched by other snmptrap items</p> |SNMP_TRAP |snmptrap.fallback |
|General |System location |<p>MIB: SNMPv2-MIB</p><p>The physical location of this node (e.g., `telephone closet,</p><p>3rd floor'). If the location is unknown, the value is the zero-length string.</p> |SNMP |system.location[sysLocation.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
-|General |System contact details |<p>MIB: SNMPv2-MIB</p><p>The textual identification of the contact person for this managed</p><p>node, together with information on how to contact this person. If no contact</p><p>information is known, the value is the zero-length string.</p> |SNMP |system.contact[sysContact.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `1d`</p> |
+|General |System contact details |<p>MIB: SNMPv2-MIB</p><p>The textual identification of the contact person for this managed</p><p>node, together with information on how to contact this person. If no contact</p><p>information is known, the value is the zero-length string.</p> |SNMP |system.contact[sysContact.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `12h`</p> |
|General |System object ID |<p>MIB: SNMPv2-MIB</p><p>The vendor's authoritative identification of the network management</p><p>subsystem contained in the entity. This value is allocated within the SMI enterprises</p><p>subtree (1.3.6.1.4.1) and provides an easy and unambiguous means for determining`what</p><p>kind of box' is being managed. For example, if vendor`Flintstones, Inc.' was</p><p>assigned the subtree1.3.6.1.4.1.4242, it could assign the identifier 1.3.6.1.4.1.4242.1.1</p><p>to its `Fred Router'.</p> |SNMP |system.objectid[sysObjectID.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|General |System name |<p>MIB: SNMPv2-MIB</p><p>An administratively-assigned name for this managed node.By</p><p>convention, this is the node's fully-qualified domain name. If the name is unknown,</p><p>the value is the zero-length string.</p> |SNMP |system.name[sysName.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
-|General |System description |<p>MIB: SNMPv2-MIB</p><p>A textual description of the entity. This value should</p><p>include the full name and version identification of the system's hardware type, software operating-system, and</p><p>networking software.</p> |SNMP |system.descr[sysDescr.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `1d`</p> |
+|General |System description |<p>MIB: SNMPv2-MIB</p><p>A textual description of the entity. This value should</p><p>include the full name and version identification of the system's hardware type, software operating-system, and</p><p>networking software.</p> |SNMP |system.descr[sysDescr.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `12h`</p> |
|General |{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Serial number |<p>MIB: PowerNet-MIB</p><p>The battery pack serial number.</p> |SNMP |system.sn[upsHighPrecBatteryPackSerialNumber.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Battery status |<p>MIB: PowerNet-MIB</p><p>The status of the UPS batteries. A batteryLow(3) value</p><p> indicates the UPS will be unable to sustain the current</p><p> load, and its services will be lost if power is not restored.</p><p> The amount of run time in reserve at the time of low battery</p><p> can be configured by the upsAdvConfigLowBatteryRunTime.</p><p> A batteryInFaultCondition(4)value indicates that a battery</p><p> installed has an internal error condition.</p> |SNMP |battery.status[upsBasicBatteryStatus]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Battery capacity |<p>MIB: PowerNet-MIB</p><p>The remaining battery capacity expressed as</p><p> percentage of full capacity.</p> |SNMP |battery.capacity[upsHighPrecBatteryCapacity]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
@@ -87,7 +87,7 @@ There are no template links in this template.
|Status |Output current |<p>MIB: PowerNet-MIB</p><p>The current in amperes drawn by the load on the UPS.</p> |SNMP |output.current[upsHighPrecOutputCurrent]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Output status |<p>MIB: PowerNet-MIB</p><p>The current state of the UPS. If the UPS is unable to</p><p> determine the state of the UPS this variable is set</p><p> to unknown(1).</p><p>During self-test most UPSes report onBattery(3) but</p><p> some that support it will report onBatteryTest(15).</p><p> To determine self-test status across all UPSes, refer</p><p> to the upsBasicStateOutputState OID.</p> |SNMP |output.status[upsBasicOutputStatus]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Uptime |<p>MIB: SNMPv2-MIB</p><p>The time (in hundredths of a second) since the network management</p><p>portion of the system was last re-initialized.</p> |SNMP |system.uptime[sysUpTime.0]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.01`</p> |
-|Status |SNMP agent availability |<p>-</p> |INTERNAL |zabbix[host,snmp,available]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
+|Status |SNMP agent availability |<p>Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list.</p><p>Possible value:</p><p>0 - not available</p><p>1 - available</p><p>2 - unknown</p> |INTERNAL |zabbix[host,snmp,available]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |{#PHASEINDEX}: Phase input voltage |<p>MIB: PowerNet-MIB</p><p>The input voltage in VAC, or -1 if it's unsupported</p><p> by this UPS.</p> |SNMP |phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |{#PHASEINDEX}: Phase input current |<p>MIB: PowerNet-MIB</p><p>The input current in 0.1 amperes, or -0.1 if it's</p><p> unsupported by this UPS.</p> |SNMP |phase.input.current[upsPhaseInputCurrent.1.1.{#PHASEINDEX}]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |{#PHASEINDEX}: Phase output voltage |<p>MIB: PowerNet-MIB</p><p>The output voltage in VAC, or -1 if it's unsupported</p><p> by this UPS.</p> |SNMP |phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
@@ -109,39 +109,39 @@ There are no template links in this template.
|Name|Description|Expression|Severity|Dependencies and additional info|
|----|-----------|----|----|----|
-|System name has changed (new name: {ITEM.VALUE}) |<p>System name has changed. Ack to close.</p> |`{TEMPLATE_NAME:system.name[sysName.0].diff()}=1 and {TEMPLATE_NAME:system.name[sysName.0].strlen()}>0` |INFO |<p>Manual close: YES</p> |
-|Battery has an internal error condition |<p>A battery installed has an internal error condition.</p> |`{TEMPLATE_NAME:battery.status[upsBasicBatteryStatus].last()}=4` |AVERAGE | |
-|Battery is Low |<p>The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.</p> |`{TEMPLATE_NAME:battery.status[upsBasicBatteryStatus].last()}=3` |AVERAGE | |
-|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) | |`{TEMPLATE_NAME:battery.capacity[upsHighPrecBatteryCapacity].last()} < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
-|Battery needs replacement |<p>A battery installed has an internal error condition.</p> |`{TEMPLATE_NAME:battery.replace_indicator[upsAdvBatteryReplaceIndicator].last()}=2` |HIGH | |
-|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:battery.temperature[upsHighPrecBatteryTemperature].min({$TIME.PERIOD})} > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
-|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:input.voltage[upsHighPrecInputLineVoltage].min({$TIME.PERIOD})} > 0 and ({TEMPLATE_NAME:input.voltage[upsHighPrecInputLineVoltage].min({$TIME.PERIOD})} > {$UPS.INPUT_VOLT.MAX.WARN} or {TEMPLATE_NAME:input.voltage[upsHighPrecInputLineVoltage].max({$TIME.PERIOD})} < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
-|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:input.frequency[upsHighPrecInputFrequency].min({$TIME.PERIOD})} > 0 and ({TEMPLATE_NAME:input.frequency[upsHighPrecInputFrequency].min({$TIME.PERIOD})} > {$UPS.INPUT_FREQ.MAX.WARN} or {TEMPLATE_NAME:input.frequency[upsHighPrecInputFrequency].max({$TIME.PERIOD})} < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
-|Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD}) |<p>A battery installed has an internal error condition.</p> |`{TEMPLATE_NAME:output.load[upsHighPrecOutputLoad].min({$TIME.PERIOD})} > {$UPS.OUTPUT.MAX.WARN}` |HIGH | |
-|UPS is Timed Sleeping | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=5` |AVERAGE | |
-|UPS is Switched Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=9` |AVERAGE | |
-|UPS is Software Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=6` |AVERAGE | |
-|UPS is Sleeping Until Power Return | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=11` |AVERAGE | |
-|UPS is Rebooting | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=8` |AVERAGE | |
-|UPS is On Smart Trim | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=12` |AVERAGE | |
-|UPS is on Smart Boost | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=4` |AVERAGE | |
-|UPS is on battery | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=3` |AVERAGE | |
-|UPS is Off | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=7` |AVERAGE | |
-|UPS is Emergency Static Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=16` |AVERAGE | |
-|UPS is Hardware Failure Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=10` |AVERAGE | |
-|{HOST.NAME} has been restarted (uptime < 10m) |<p>Uptime is less than 10 minutes</p> |`{TEMPLATE_NAME:system.uptime[sysUpTime.0].last()}<10m` |WARNING |<p>Manual close: YES</p><p>**Depends on**:</p><p>- No SNMP data collection</p> |
-|No SNMP data collection |<p>SNMP is not available for polling. Please check device connectivity and SNMP settings.</p> |`{TEMPLATE_NAME:zabbix[host,snmp,available].max({$SNMP.TIMEOUT})}=0` |WARNING | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}].min({$TIME.PERIOD})} > {$UPS.INPUT_VOLT.MAX.WARN} or {TEMPLATE_NAME:phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}].max({$TIME.PERIOD})} < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}].min({$TIME.PERIOD})} > {$UPS.INPUT_VOLT.MAX.WARN} or {TEMPLATE_NAME:phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}].max({$TIME.PERIOD})} < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |<p>The battery cartridge status:</p><p>bit 0 Disconnected</p><p>bit 1 Overvoltage</p><p>bit 2 NeedsReplacement</p><p>bit 3 OvertemperatureCritical</p><p>bit 4 Charger</p><p>bit 5 TemperatureSensor</p><p>bit 6 BusSoftStart</p><p>bit 7 OvertemperatureWarning</p><p>bit 8 GeneralError</p><p>bit 9 Communication</p><p>bit 10 DisconnectedFrame</p><p>bit 11 FirmwareMismatch</p> |`{TEMPLATE_NAME:battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}].regexp("^(0{16})$")}=0` |WARNING | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}].min({$TIME.PERIOD})} > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |<p>The battery cartridge health.</p><p> bit 0 Battery lifetime okay</p><p> bit 1 Battery lifetime near end, order replacement cartridge</p><p> bit 2 Battery lifetime exceeded, replace battery</p><p> bit 3 Battery lifetime near end acknowledged, order replacement cartridge</p><p> bit 4 Battery lifetime exceeded acknowledged, replace battery</p><p> bit 5 Battery measured lifetime near end, order replacement cartridge</p><p> bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge</p> |`{TEMPLATE_NAME:battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}].regexp("^(0)[0|1]{15}$")}=1` |WARNING | |
-|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}].last()}=4` |INFO | |
-|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}].last()}=2` |AVERAGE | |
-|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}].last()}=3` |HIGH | |
-|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}].last()}=4` |INFO | |
-|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}].last()}=2` |AVERAGE | |
-|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}].last()}=3` |HIGH | |
+|System name has changed (new name: {ITEM.VALUE}) |<p>System name has changed. Ack to close.</p> |`last(/APC Smart-UPS RT 1000 RM XL SNMP/system.name[sysName.0],#1)<>last(/APC Smart-UPS RT 1000 RM XL SNMP/system.name[sysName.0],#2) and length(last(/APC Smart-UPS RT 1000 RM XL SNMP/system.name[sysName.0]))>0` |INFO |<p>Manual close: YES</p> |
+|Battery has an internal error condition |<p>A battery installed has an internal error condition.</p> |`last(/APC Smart-UPS RT 1000 RM XL SNMP/battery.status[upsBasicBatteryStatus])=4` |AVERAGE | |
+|Battery is Low |<p>The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.</p> |`last(/APC Smart-UPS RT 1000 RM XL SNMP/battery.status[upsBasicBatteryStatus])=3` |AVERAGE | |
+|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) | |`last(/APC Smart-UPS RT 1000 RM XL SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
+|Battery needs replacement |<p>A battery installed has an internal error condition.</p> |`last(/APC Smart-UPS RT 1000 RM XL SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2` |HIGH | |
+|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC Smart-UPS RT 1000 RM XL SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS RT 1000 RM XL SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS RT 1000 RM XL SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS RT 1000 RM XL SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
+|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) | |`min(/APC Smart-UPS RT 1000 RM XL SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS RT 1000 RM XL SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC Smart-UPS RT 1000 RM XL SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
+|Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD}) |<p>A battery installed has an internal error condition.</p> |`min(/APC Smart-UPS RT 1000 RM XL SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}` |HIGH | |
+|UPS is Timed Sleeping | |`last(/APC Smart-UPS RT 1000 RM XL SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | |
+|UPS is Switched Bypass | |`last(/APC Smart-UPS RT 1000 RM XL SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | |
+|UPS is Software Bypass | |`last(/APC Smart-UPS RT 1000 RM XL SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | |
+|UPS is Sleeping Until Power Return | |`last(/APC Smart-UPS RT 1000 RM XL SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | |
+|UPS is Rebooting | |`last(/APC Smart-UPS RT 1000 RM XL SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | |
+|UPS is On Smart Trim | |`last(/APC Smart-UPS RT 1000 RM XL SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | |
+|UPS is on Smart Boost | |`last(/APC Smart-UPS RT 1000 RM XL SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | |
+|UPS is on battery | |`last(/APC Smart-UPS RT 1000 RM XL SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | |
+|UPS is Off | |`last(/APC Smart-UPS RT 1000 RM XL SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | |
+|UPS is Emergency Static Bypass | |`last(/APC Smart-UPS RT 1000 RM XL SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | |
+|UPS is Hardware Failure Bypass | |`last(/APC Smart-UPS RT 1000 RM XL SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | |
+|{HOST.NAME} has been restarted (uptime < 10m) |<p>Uptime is less than 10 minutes</p> |`last(/APC Smart-UPS RT 1000 RM XL SNMP/system.uptime[sysUpTime.0])<10m` |WARNING |<p>Manual close: YES</p><p>**Depends on**:</p><p>- No SNMP data collection</p> |
+|No SNMP data collection |<p>SNMP is not available for polling. Please check device connectivity and SNMP settings.</p> |`max(/APC Smart-UPS RT 1000 RM XL SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0` |WARNING | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS RT 1000 RM XL SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS RT 1000 RM XL SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS RT 1000 RM XL SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS RT 1000 RM XL SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |<p>The battery cartridge status:</p><p>bit 0 Disconnected</p><p>bit 1 Overvoltage</p><p>bit 2 NeedsReplacement</p><p>bit 3 OvertemperatureCritical</p><p>bit 4 Charger</p><p>bit 5 TemperatureSensor</p><p>bit 6 BusSoftStart</p><p>bit 7 OvertemperatureWarning</p><p>bit 8 GeneralError</p><p>bit 9 Communication</p><p>bit 10 DisconnectedFrame</p><p>bit 11 FirmwareMismatch</p> |`find(/APC Smart-UPS RT 1000 RM XL SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0` |WARNING | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC Smart-UPS RT 1000 RM XL SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |<p>The battery cartridge health.</p><p> bit 0 Battery lifetime okay</p><p> bit 1 Battery lifetime near end, order replacement cartridge</p><p> bit 2 Battery lifetime exceeded, replace battery</p><p> bit 3 Battery lifetime near end acknowledged, order replacement cartridge</p><p> bit 4 Battery lifetime exceeded acknowledged, replace battery</p><p> bit 5 Battery measured lifetime near end, order replacement cartridge</p><p> bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge</p> |`find(/APC Smart-UPS RT 1000 RM XL SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1` |WARNING | |
+|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`last(/APC Smart-UPS RT 1000 RM XL SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4` |INFO | |
+|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`last(/APC Smart-UPS RT 1000 RM XL SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2` |AVERAGE | |
+|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`last(/APC Smart-UPS RT 1000 RM XL SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=3` |HIGH | |
+|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`last(/APC Smart-UPS RT 1000 RM XL SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=4` |INFO | |
+|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`last(/APC Smart-UPS RT 1000 RM XL SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=2` |AVERAGE | |
+|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`last(/APC Smart-UPS RT 1000 RM XL SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=3` |HIGH | |
## Feedback
diff --git a/templates/power/apc/apc_ups_smart_rt_1000_rm_xl_snmp/template_power_apc_ups_smart_rt_1000_rm_xl_snmp.yaml b/templates/power/apc/apc_ups_smart_rt_1000_rm_xl_snmp/template_power_apc_ups_smart_rt_1000_rm_xl_snmp.yaml
index deb9476fd15..0c15548075f 100644
--- a/templates/power/apc/apc_ups_smart_rt_1000_rm_xl_snmp/template_power_apc_ups_smart_rt_1000_rm_xl_snmp.yaml
+++ b/templates/power/apc/apc_ups_smart_rt_1000_rm_xl_snmp/template_power_apc_ups_smart_rt_1000_rm_xl_snmp.yaml
@@ -1,6 +1,6 @@
zabbix_export:
- version: '5.4'
- date: '2021-05-11T08:05:02Z'
+ version: '6.0'
+ date: '2021-10-28T08:23:59Z'
groups:
-
uuid: 3dcd5bbe90534f9e8eb5c2d53756af63
@@ -19,7 +19,7 @@ zabbix_export:
You can discuss this template or leave feedback on our forum https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups
- Template tooling version used: 0.38
+ Template tooling version used: 0.39
groups:
-
name: Templates/Power
@@ -48,7 +48,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 8ab182b26a0443539a1a114767d8acd7
@@ -76,7 +77,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 7a887ae254b04b19bac605bb36141767
name: 'Battery last replace date'
@@ -101,7 +103,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 8f4351d23be04a3abee1e6edb746a9ec
name: 'Battery replace indicator'
@@ -121,7 +124,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: ab0db1327cf04a9c9a9ee757f0869603
@@ -153,7 +157,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: a631704123c2498aa8ce973e36c13698
name: 'Battery status'
@@ -179,7 +184,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: c8787a09c2ea4aeb977b868ae0a3218b
@@ -217,7 +223,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: e2debe06675d4d4584b60b768633887b
@@ -248,7 +255,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 0a12f157ae844129a35084b5ab0a8eab
name: 'Input fail cause'
@@ -291,7 +299,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 0ceb5a6d71f440fcbd2da06b0cc1bbb3
name: 'Input frequency'
@@ -315,7 +324,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: b29cd7e33c1e4e16b10fe436c1f7e6d6
@@ -346,7 +356,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: d38f2151f0eb486e8d44b72a2e361a5f
@@ -377,7 +388,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: cd7b2c1b12df4fd19f37485aa380b295
name: 'Output load'
@@ -402,7 +414,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 57197c601f8a433d8ccdcb040d047f6f
@@ -436,7 +449,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: e9289d8f4e124097990e2af98e916368
@@ -516,7 +530,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: d08fb7e3fae84d2cbae64ab9771ffcdc
name: 'SNMP traps (fallback)'
@@ -525,18 +540,19 @@ zabbix_export:
history: 2w
trends: '0'
value_type: LOG
- description: 'Item is used to collect all SNMP traps unmatched by other snmptrap items'
+ description: 'The item is used to collect all SNMP traps unmatched by other snmptrap items'
logtimefmt: 'hh:mm:sszyyyy/MM/dd'
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: da60acc731a64257a90512b5c70d1e92
name: 'System contact details'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.2.1.1.4.0
key: 'system.contact[sysContact.0]'
- delay: 1h
+ delay: 15m
history: 2w
trends: '0'
value_type: CHAR
@@ -550,17 +566,18 @@ zabbix_export:
-
type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- - 1d
+ - 12h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 01302a36cafd421c90d746f785c83f3f
name: 'System description'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.2.1.1.1.0
key: 'system.descr[sysDescr.0]'
- delay: 1h
+ delay: 15m
history: 2w
trends: '0'
value_type: CHAR
@@ -573,10 +590,11 @@ zabbix_export:
-
type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- - 1d
+ - 12h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: d0351d1bc1dc4f1b853fe64d456b3570
name: 'System location'
@@ -599,7 +617,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 866889bb71e949c18520bf8fefd3e7ea
name: Model
@@ -620,7 +639,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 482bec6573f249abbb721f2ec90def3b
name: 'System name'
@@ -644,7 +664,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
triggers:
-
uuid: b13b087b9828426aac82a281071ceb8b
@@ -678,7 +699,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 269ce166bb904fa8b11fc2fdf1f67d76
name: 'Serial number'
@@ -702,7 +724,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 336ef2166914449fafa13ab08fe7c7a1
name: Uptime
@@ -724,7 +747,8 @@ zabbix_export:
- '0.01'
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 87ebd137f2744ae6879d6fd9d51314ef
@@ -743,6 +767,12 @@ zabbix_export:
type: INTERNAL
key: 'zabbix[host,snmp,available]'
history: 7d
+ description: |
+ Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list.
+ Possible value:
+ 0 - not available
+ 1 - available
+ 2 - unknown
valuemap:
name: zabbix.host.available
preprocessing:
@@ -752,7 +782,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 53263bf0536d479785b45883b9b7ab21
@@ -791,7 +822,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: b4a8277fdf6f4e76a641690aaf6e7faa
name: 'External battery packs discovery'
@@ -828,7 +860,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 2e7f6a940840406cb17bb1af20936326
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery pack cartridge health'
@@ -855,7 +888,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: c1eefbeeb0d146c3bea5cae929d0c30b
@@ -903,7 +937,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 28b8fb69a85549288cf0e26b9ca0a2cf
@@ -948,7 +983,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: fa007fcfbe7c499d8f97a808991f2800
@@ -976,7 +1012,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 59467725274d4dba8e839d167cabe693
name: 'External sensor port 1 discovery'
@@ -1007,7 +1044,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 137fdf42e0ab476e86e7b0b3bc87d5cc
name: '{#EXTERNAL_SENSOR1_NAME}: Sensor alarm status'
@@ -1031,7 +1069,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 175c1def62ac412eb5f9ef015a9b8ac3
@@ -1071,7 +1110,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
overrides:
-
name: Temp
@@ -1119,7 +1159,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: e10189271da445a494d274d99269ab75
name: '{#EXTERNAL_SENSOR2_NAME}: Sensor alarm status'
@@ -1143,7 +1184,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 5e937c991aa146fe98c1a4f868be6b70
@@ -1183,7 +1225,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
overrides:
-
name: Temp
@@ -1234,7 +1277,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 1baaad88e9064b92b453fb2c1c7d73d5
name: '{#PHASEINDEX}: Phase input voltage'
@@ -1255,7 +1299,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 971301abf4d6457da125fd7ebd903728
@@ -1297,7 +1342,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 6d1812674e5646f8acf2ea47acf05a6d
name: '{#PHASEINDEX}: Phase output load, %'
@@ -1319,7 +1365,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 3c0573d586b24e53aeebb6c44b907bbd
name: '{#PHASEINDEX}: Phase output voltage'
@@ -1340,7 +1387,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: d7167a129de146d19218edb85c82c69b
diff --git a/templates/power/apc/apc_ups_smart_rt_1000_xl_snmp/README.md b/templates/power/apc/apc_ups_smart_rt_1000_xl_snmp/README.md
index 5949480d7f9..47c7170833b 100644
--- a/templates/power/apc/apc_ups_smart_rt_1000_xl_snmp/README.md
+++ b/templates/power/apc/apc_ups_smart_rt_1000_xl_snmp/README.md
@@ -55,8 +55,8 @@ There are no template links in this template.
|Output phases discovery |<p>The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1</p> |SNMP |output.phases.discovery |
|External battery packs discovery | |SNMP |battery.packs.discovery<p>**Filter**:</p>AND <p>- A: {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`</p> |
|External bad battery packs discovery |<p>Discovery of the number of external defective battery packs.</p> |SNMP |battery.packs.bad.discovery |
-|External sensor port 1 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor1.discovery |
-|External sensor port 2 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor2.discovery |
+|External sensor port 1 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor1.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR1_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
+|External sensor port 2 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor2.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR2_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
## Items collected
@@ -64,12 +64,12 @@ There are no template links in this template.
|-----|----|-----------|----|---------------------|
|General |Model |<p>MIB: PowerNet-MIB</p><p>The UPS model name (e.g. 'APC Smart-UPS 600').</p> |SNMP |system.model[upsBasicIdentModel]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|General |Serial number |<p>MIB: PowerNet-MIB</p><p>An 8-character string identifying the serial number of</p><p> the UPS internal microprocessor. This number is set at</p><p> the factory. NOTE: This number does NOT correspond to</p><p> the serial number on the rear of the UPS.</p> |SNMP |system.sn[upsAdvIdentSerialNumber]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
-|General |SNMP traps (fallback) |<p>Item is used to collect all SNMP traps unmatched by other snmptrap items</p> |SNMP_TRAP |snmptrap.fallback |
+|General |SNMP traps (fallback) |<p>The item is used to collect all SNMP traps unmatched by other snmptrap items</p> |SNMP_TRAP |snmptrap.fallback |
|General |System location |<p>MIB: SNMPv2-MIB</p><p>The physical location of this node (e.g., `telephone closet,</p><p>3rd floor'). If the location is unknown, the value is the zero-length string.</p> |SNMP |system.location[sysLocation.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
-|General |System contact details |<p>MIB: SNMPv2-MIB</p><p>The textual identification of the contact person for this managed</p><p>node, together with information on how to contact this person. If no contact</p><p>information is known, the value is the zero-length string.</p> |SNMP |system.contact[sysContact.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `1d`</p> |
+|General |System contact details |<p>MIB: SNMPv2-MIB</p><p>The textual identification of the contact person for this managed</p><p>node, together with information on how to contact this person. If no contact</p><p>information is known, the value is the zero-length string.</p> |SNMP |system.contact[sysContact.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `12h`</p> |
|General |System object ID |<p>MIB: SNMPv2-MIB</p><p>The vendor's authoritative identification of the network management</p><p>subsystem contained in the entity. This value is allocated within the SMI enterprises</p><p>subtree (1.3.6.1.4.1) and provides an easy and unambiguous means for determining`what</p><p>kind of box' is being managed. For example, if vendor`Flintstones, Inc.' was</p><p>assigned the subtree1.3.6.1.4.1.4242, it could assign the identifier 1.3.6.1.4.1.4242.1.1</p><p>to its `Fred Router'.</p> |SNMP |system.objectid[sysObjectID.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|General |System name |<p>MIB: SNMPv2-MIB</p><p>An administratively-assigned name for this managed node.By</p><p>convention, this is the node's fully-qualified domain name. If the name is unknown,</p><p>the value is the zero-length string.</p> |SNMP |system.name[sysName.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
-|General |System description |<p>MIB: SNMPv2-MIB</p><p>A textual description of the entity. This value should</p><p>include the full name and version identification of the system's hardware type, software operating-system, and</p><p>networking software.</p> |SNMP |system.descr[sysDescr.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `1d`</p> |
+|General |System description |<p>MIB: SNMPv2-MIB</p><p>A textual description of the entity. This value should</p><p>include the full name and version identification of the system's hardware type, software operating-system, and</p><p>networking software.</p> |SNMP |system.descr[sysDescr.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `12h`</p> |
|General |{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Serial number |<p>MIB: PowerNet-MIB</p><p>The battery pack serial number.</p> |SNMP |system.sn[upsHighPrecBatteryPackSerialNumber.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Battery status |<p>MIB: PowerNet-MIB</p><p>The status of the UPS batteries. A batteryLow(3) value</p><p> indicates the UPS will be unable to sustain the current</p><p> load, and its services will be lost if power is not restored.</p><p> The amount of run time in reserve at the time of low battery</p><p> can be configured by the upsAdvConfigLowBatteryRunTime.</p><p> A batteryInFaultCondition(4)value indicates that a battery</p><p> installed has an internal error condition.</p> |SNMP |battery.status[upsBasicBatteryStatus]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Battery capacity |<p>MIB: PowerNet-MIB</p><p>The remaining battery capacity expressed as</p><p> percentage of full capacity.</p> |SNMP |battery.capacity[upsHighPrecBatteryCapacity]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
@@ -87,7 +87,7 @@ There are no template links in this template.
|Status |Output current |<p>MIB: PowerNet-MIB</p><p>The current in amperes drawn by the load on the UPS.</p> |SNMP |output.current[upsHighPrecOutputCurrent]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Output status |<p>MIB: PowerNet-MIB</p><p>The current state of the UPS. If the UPS is unable to</p><p> determine the state of the UPS this variable is set</p><p> to unknown(1).</p><p>During self-test most UPSes report onBattery(3) but</p><p> some that support it will report onBatteryTest(15).</p><p> To determine self-test status across all UPSes, refer</p><p> to the upsBasicStateOutputState OID.</p> |SNMP |output.status[upsBasicOutputStatus]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Uptime |<p>MIB: SNMPv2-MIB</p><p>The time (in hundredths of a second) since the network management</p><p>portion of the system was last re-initialized.</p> |SNMP |system.uptime[sysUpTime.0]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.01`</p> |
-|Status |SNMP agent availability |<p>-</p> |INTERNAL |zabbix[host,snmp,available]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
+|Status |SNMP agent availability |<p>Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list.</p><p>Possible value:</p><p>0 - not available</p><p>1 - available</p><p>2 - unknown</p> |INTERNAL |zabbix[host,snmp,available]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |{#PHASEINDEX}: Phase input voltage |<p>MIB: PowerNet-MIB</p><p>The input voltage in VAC, or -1 if it's unsupported</p><p> by this UPS.</p> |SNMP |phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |{#PHASEINDEX}: Phase input current |<p>MIB: PowerNet-MIB</p><p>The input current in 0.1 amperes, or -0.1 if it's</p><p> unsupported by this UPS.</p> |SNMP |phase.input.current[upsPhaseInputCurrent.1.1.{#PHASEINDEX}]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |{#PHASEINDEX}: Phase output voltage |<p>MIB: PowerNet-MIB</p><p>The output voltage in VAC, or -1 if it's unsupported</p><p> by this UPS.</p> |SNMP |phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
@@ -109,39 +109,39 @@ There are no template links in this template.
|Name|Description|Expression|Severity|Dependencies and additional info|
|----|-----------|----|----|----|
-|System name has changed (new name: {ITEM.VALUE}) |<p>System name has changed. Ack to close.</p> |`{TEMPLATE_NAME:system.name[sysName.0].diff()}=1 and {TEMPLATE_NAME:system.name[sysName.0].strlen()}>0` |INFO |<p>Manual close: YES</p> |
-|Battery has an internal error condition |<p>A battery installed has an internal error condition.</p> |`{TEMPLATE_NAME:battery.status[upsBasicBatteryStatus].last()}=4` |AVERAGE | |
-|Battery is Low |<p>The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.</p> |`{TEMPLATE_NAME:battery.status[upsBasicBatteryStatus].last()}=3` |AVERAGE | |
-|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) | |`{TEMPLATE_NAME:battery.capacity[upsHighPrecBatteryCapacity].last()} < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
-|Battery needs replacement |<p>A battery installed has an internal error condition.</p> |`{TEMPLATE_NAME:battery.replace_indicator[upsAdvBatteryReplaceIndicator].last()}=2` |HIGH | |
-|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:battery.temperature[upsHighPrecBatteryTemperature].min({$TIME.PERIOD})} > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
-|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:input.voltage[upsHighPrecInputLineVoltage].min({$TIME.PERIOD})} > 0 and ({TEMPLATE_NAME:input.voltage[upsHighPrecInputLineVoltage].min({$TIME.PERIOD})} > {$UPS.INPUT_VOLT.MAX.WARN} or {TEMPLATE_NAME:input.voltage[upsHighPrecInputLineVoltage].max({$TIME.PERIOD})} < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
-|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:input.frequency[upsHighPrecInputFrequency].min({$TIME.PERIOD})} > 0 and ({TEMPLATE_NAME:input.frequency[upsHighPrecInputFrequency].min({$TIME.PERIOD})} > {$UPS.INPUT_FREQ.MAX.WARN} or {TEMPLATE_NAME:input.frequency[upsHighPrecInputFrequency].max({$TIME.PERIOD})} < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
-|Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD}) |<p>A battery installed has an internal error condition.</p> |`{TEMPLATE_NAME:output.load[upsHighPrecOutputLoad].min({$TIME.PERIOD})} > {$UPS.OUTPUT.MAX.WARN}` |HIGH | |
-|UPS is Timed Sleeping | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=5` |AVERAGE | |
-|UPS is Switched Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=9` |AVERAGE | |
-|UPS is Software Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=6` |AVERAGE | |
-|UPS is Sleeping Until Power Return | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=11` |AVERAGE | |
-|UPS is Rebooting | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=8` |AVERAGE | |
-|UPS is On Smart Trim | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=12` |AVERAGE | |
-|UPS is on Smart Boost | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=4` |AVERAGE | |
-|UPS is on battery | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=3` |AVERAGE | |
-|UPS is Off | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=7` |AVERAGE | |
-|UPS is Emergency Static Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=16` |AVERAGE | |
-|UPS is Hardware Failure Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=10` |AVERAGE | |
-|{HOST.NAME} has been restarted (uptime < 10m) |<p>Uptime is less than 10 minutes</p> |`{TEMPLATE_NAME:system.uptime[sysUpTime.0].last()}<10m` |WARNING |<p>Manual close: YES</p><p>**Depends on**:</p><p>- No SNMP data collection</p> |
-|No SNMP data collection |<p>SNMP is not available for polling. Please check device connectivity and SNMP settings.</p> |`{TEMPLATE_NAME:zabbix[host,snmp,available].max({$SNMP.TIMEOUT})}=0` |WARNING | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}].min({$TIME.PERIOD})} > {$UPS.INPUT_VOLT.MAX.WARN} or {TEMPLATE_NAME:phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}].max({$TIME.PERIOD})} < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}].min({$TIME.PERIOD})} > {$UPS.INPUT_VOLT.MAX.WARN} or {TEMPLATE_NAME:phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}].max({$TIME.PERIOD})} < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |<p>The battery cartridge status:</p><p>bit 0 Disconnected</p><p>bit 1 Overvoltage</p><p>bit 2 NeedsReplacement</p><p>bit 3 OvertemperatureCritical</p><p>bit 4 Charger</p><p>bit 5 TemperatureSensor</p><p>bit 6 BusSoftStart</p><p>bit 7 OvertemperatureWarning</p><p>bit 8 GeneralError</p><p>bit 9 Communication</p><p>bit 10 DisconnectedFrame</p><p>bit 11 FirmwareMismatch</p> |`{TEMPLATE_NAME:battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}].regexp("^(0{16})$")}=0` |WARNING | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}].min({$TIME.PERIOD})} > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |<p>The battery cartridge health.</p><p> bit 0 Battery lifetime okay</p><p> bit 1 Battery lifetime near end, order replacement cartridge</p><p> bit 2 Battery lifetime exceeded, replace battery</p><p> bit 3 Battery lifetime near end acknowledged, order replacement cartridge</p><p> bit 4 Battery lifetime exceeded acknowledged, replace battery</p><p> bit 5 Battery measured lifetime near end, order replacement cartridge</p><p> bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge</p> |`{TEMPLATE_NAME:battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}].regexp("^(0)[0|1]{15}$")}=1` |WARNING | |
-|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}].last()}=4` |INFO | |
-|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}].last()}=2` |AVERAGE | |
-|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}].last()}=3` |HIGH | |
-|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}].last()}=4` |INFO | |
-|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}].last()}=2` |AVERAGE | |
-|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}].last()}=3` |HIGH | |
+|System name has changed (new name: {ITEM.VALUE}) |<p>System name has changed. Ack to close.</p> |`last(/APC Smart-UPS RT 1000 XL SNMP/system.name[sysName.0],#1)<>last(/APC Smart-UPS RT 1000 XL SNMP/system.name[sysName.0],#2) and length(last(/APC Smart-UPS RT 1000 XL SNMP/system.name[sysName.0]))>0` |INFO |<p>Manual close: YES</p> |
+|Battery has an internal error condition |<p>A battery installed has an internal error condition.</p> |`last(/APC Smart-UPS RT 1000 XL SNMP/battery.status[upsBasicBatteryStatus])=4` |AVERAGE | |
+|Battery is Low |<p>The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.</p> |`last(/APC Smart-UPS RT 1000 XL SNMP/battery.status[upsBasicBatteryStatus])=3` |AVERAGE | |
+|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) | |`last(/APC Smart-UPS RT 1000 XL SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
+|Battery needs replacement |<p>A battery installed has an internal error condition.</p> |`last(/APC Smart-UPS RT 1000 XL SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2` |HIGH | |
+|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC Smart-UPS RT 1000 XL SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS RT 1000 XL SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS RT 1000 XL SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS RT 1000 XL SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
+|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) | |`min(/APC Smart-UPS RT 1000 XL SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS RT 1000 XL SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC Smart-UPS RT 1000 XL SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
+|Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD}) |<p>A battery installed has an internal error condition.</p> |`min(/APC Smart-UPS RT 1000 XL SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}` |HIGH | |
+|UPS is Timed Sleeping | |`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | |
+|UPS is Switched Bypass | |`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | |
+|UPS is Software Bypass | |`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | |
+|UPS is Sleeping Until Power Return | |`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | |
+|UPS is Rebooting | |`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | |
+|UPS is On Smart Trim | |`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | |
+|UPS is on Smart Boost | |`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | |
+|UPS is on battery | |`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | |
+|UPS is Off | |`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | |
+|UPS is Emergency Static Bypass | |`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | |
+|UPS is Hardware Failure Bypass | |`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | |
+|{HOST.NAME} has been restarted (uptime < 10m) |<p>Uptime is less than 10 minutes</p> |`last(/APC Smart-UPS RT 1000 XL SNMP/system.uptime[sysUpTime.0])<10m` |WARNING |<p>Manual close: YES</p><p>**Depends on**:</p><p>- No SNMP data collection</p> |
+|No SNMP data collection |<p>SNMP is not available for polling. Please check device connectivity and SNMP settings.</p> |`max(/APC Smart-UPS RT 1000 XL SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0` |WARNING | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS RT 1000 XL SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS RT 1000 XL SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS RT 1000 XL SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS RT 1000 XL SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |<p>The battery cartridge status:</p><p>bit 0 Disconnected</p><p>bit 1 Overvoltage</p><p>bit 2 NeedsReplacement</p><p>bit 3 OvertemperatureCritical</p><p>bit 4 Charger</p><p>bit 5 TemperatureSensor</p><p>bit 6 BusSoftStart</p><p>bit 7 OvertemperatureWarning</p><p>bit 8 GeneralError</p><p>bit 9 Communication</p><p>bit 10 DisconnectedFrame</p><p>bit 11 FirmwareMismatch</p> |`find(/APC Smart-UPS RT 1000 XL SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0` |WARNING | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC Smart-UPS RT 1000 XL SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |<p>The battery cartridge health.</p><p> bit 0 Battery lifetime okay</p><p> bit 1 Battery lifetime near end, order replacement cartridge</p><p> bit 2 Battery lifetime exceeded, replace battery</p><p> bit 3 Battery lifetime near end acknowledged, order replacement cartridge</p><p> bit 4 Battery lifetime exceeded acknowledged, replace battery</p><p> bit 5 Battery measured lifetime near end, order replacement cartridge</p><p> bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge</p> |`find(/APC Smart-UPS RT 1000 XL SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1` |WARNING | |
+|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`last(/APC Smart-UPS RT 1000 XL SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4` |INFO | |
+|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`last(/APC Smart-UPS RT 1000 XL SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2` |AVERAGE | |
+|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`last(/APC Smart-UPS RT 1000 XL SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=3` |HIGH | |
+|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`last(/APC Smart-UPS RT 1000 XL SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=4` |INFO | |
+|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`last(/APC Smart-UPS RT 1000 XL SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=2` |AVERAGE | |
+|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`last(/APC Smart-UPS RT 1000 XL SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=3` |HIGH | |
## Feedback
diff --git a/templates/power/apc/apc_ups_smart_rt_1000_xl_snmp/template_power_apc_ups_smart_rt_1000_xl_snmp.yaml b/templates/power/apc/apc_ups_smart_rt_1000_xl_snmp/template_power_apc_ups_smart_rt_1000_xl_snmp.yaml
index 25b9e083b7f..305851d9198 100644
--- a/templates/power/apc/apc_ups_smart_rt_1000_xl_snmp/template_power_apc_ups_smart_rt_1000_xl_snmp.yaml
+++ b/templates/power/apc/apc_ups_smart_rt_1000_xl_snmp/template_power_apc_ups_smart_rt_1000_xl_snmp.yaml
@@ -1,6 +1,6 @@
zabbix_export:
- version: '5.4'
- date: '2021-05-11T08:04:59Z'
+ version: '6.0'
+ date: '2021-10-28T08:23:25Z'
groups:
-
uuid: 3dcd5bbe90534f9e8eb5c2d53756af63
@@ -19,7 +19,7 @@ zabbix_export:
You can discuss this template or leave feedback on our forum https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups
- Template tooling version used: 0.38
+ Template tooling version used: 0.39
groups:
-
name: Templates/Power
@@ -48,7 +48,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: b5d618c6090447429191fe4d07e85afa
@@ -76,7 +77,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 87b91005f5ff4ba5b0086e25eaa799bd
name: 'Battery last replace date'
@@ -101,7 +103,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 44a33eba233e4bd7ac51ca2dcabf2939
name: 'Battery replace indicator'
@@ -121,7 +124,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: dc92c19a5b7e43a4b155d6d51912aaf8
@@ -153,7 +157,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 047a5a3a957949d288588eb11f36f25e
name: 'Battery status'
@@ -179,7 +184,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 70c32834ea40487c8f13a55b7ed7c88f
@@ -217,7 +223,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 33695c02cf6141f78e21ca899af10c03
@@ -248,7 +255,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 4cb80c94f3d14674bc7a3933c7571eac
name: 'Input fail cause'
@@ -291,7 +299,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 700a78a4ab3c441496ecafc5ddde6a9d
name: 'Input frequency'
@@ -315,7 +324,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 167de2d832984944878767571b0b5fe4
@@ -346,7 +356,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: b8741bc0081a4a9db2824c9f93ecb399
@@ -377,7 +388,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 1d9d7ef724ff41eda4fd536df6af93cb
name: 'Output load'
@@ -402,7 +414,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: a4faec3975134cd59e83f1ca7fa3ef7d
@@ -436,7 +449,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: deedd977f1ed4b9fbb5cc161dde0c116
@@ -516,7 +530,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: d633cd3273e74209a1b0c6b761028e0a
name: 'SNMP traps (fallback)'
@@ -525,18 +540,19 @@ zabbix_export:
history: 2w
trends: '0'
value_type: LOG
- description: 'Item is used to collect all SNMP traps unmatched by other snmptrap items'
+ description: 'The item is used to collect all SNMP traps unmatched by other snmptrap items'
logtimefmt: 'hh:mm:sszyyyy/MM/dd'
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 50cc8e7cea0c40948c006623dfa94dae
name: 'System contact details'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.2.1.1.4.0
key: 'system.contact[sysContact.0]'
- delay: 1h
+ delay: 15m
history: 2w
trends: '0'
value_type: CHAR
@@ -550,17 +566,18 @@ zabbix_export:
-
type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- - 1d
+ - 12h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: e0d638ab398f40e8a9555925cd8ba907
name: 'System description'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.2.1.1.1.0
key: 'system.descr[sysDescr.0]'
- delay: 1h
+ delay: 15m
history: 2w
trends: '0'
value_type: CHAR
@@ -573,10 +590,11 @@ zabbix_export:
-
type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- - 1d
+ - 12h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 031b9d385cae4641b9ecfb76c4174262
name: 'System location'
@@ -599,7 +617,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 320221ba30744ca78b8dce03dccd549b
name: Model
@@ -620,7 +639,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: e4d9441075954c068b6fd92bbff49cef
name: 'System name'
@@ -644,7 +664,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
triggers:
-
uuid: 31bb0ff1ea334cd59d9f8b8f489611ef
@@ -678,7 +699,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 9ebb979a5e4a45fd9acf956df034f9be
name: 'Serial number'
@@ -702,7 +724,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: bbcb555846df4169bc7aead77403e8eb
name: Uptime
@@ -724,7 +747,8 @@ zabbix_export:
- '0.01'
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 860d3beb50c0400283a71c2c4b4ea5e2
@@ -743,6 +767,12 @@ zabbix_export:
type: INTERNAL
key: 'zabbix[host,snmp,available]'
history: 7d
+ description: |
+ Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list.
+ Possible value:
+ 0 - not available
+ 1 - available
+ 2 - unknown
valuemap:
name: zabbix.host.available
preprocessing:
@@ -752,7 +782,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 21fc3a198f3b423fa14676278f53a4be
@@ -791,7 +822,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: ec66331f2ae64801a3ef51d6dec5a00f
name: 'External battery packs discovery'
@@ -828,7 +860,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 3c829e3adec64fb39334dbacc03a3229
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery pack cartridge health'
@@ -855,7 +888,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: c353d8e0b0584c6c8ba81514f5c66995
@@ -903,7 +937,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 26535b11c27b4fbe92285b56cbbf5a73
@@ -948,7 +983,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 7f8613d752524d588e60aa1cab2c60bd
@@ -976,7 +1012,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 19379361227740c3bf8bc9852886538d
name: 'External sensor port 1 discovery'
@@ -1007,7 +1044,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 1a475822bc324bbf8c4aa15c34734270
name: '{#EXTERNAL_SENSOR1_NAME}: Sensor alarm status'
@@ -1031,7 +1069,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 40e22c5379f34edf87d1ea52ffae60b8
@@ -1071,7 +1110,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
overrides:
-
name: Temp
@@ -1119,7 +1159,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 4774fd152aab49de9064490cf7ec1d0a
name: '{#EXTERNAL_SENSOR2_NAME}: Sensor alarm status'
@@ -1143,7 +1184,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 650a1d16e56c45188c6246e960d62857
@@ -1183,7 +1225,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
overrides:
-
name: Temp
@@ -1234,7 +1277,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: cf03abf328754a4082017f480051292f
name: '{#PHASEINDEX}: Phase input voltage'
@@ -1255,7 +1299,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 8c9226411afb4b32ba3e9d6232ff4710
@@ -1297,7 +1342,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: ba4a2ae8abea4e2692b9a43231783648
name: '{#PHASEINDEX}: Phase output load, %'
@@ -1319,7 +1365,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 4e22c7f6d7e14b20b3720e082042fd4f
name: '{#PHASEINDEX}: Phase output voltage'
@@ -1340,7 +1387,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 58e0697a9a9147a4b1dfda251f2b593e
diff --git a/templates/power/apc/apc_ups_smart_srt_5000_snmp/README.md b/templates/power/apc/apc_ups_smart_srt_5000_snmp/README.md
index f671f4bdf8b..b994c2a36f6 100644
--- a/templates/power/apc/apc_ups_smart_srt_5000_snmp/README.md
+++ b/templates/power/apc/apc_ups_smart_srt_5000_snmp/README.md
@@ -55,8 +55,8 @@ There are no template links in this template.
|Output phases discovery |<p>The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1</p> |SNMP |output.phases.discovery |
|External battery packs discovery | |SNMP |battery.packs.discovery<p>**Filter**:</p>AND <p>- A: {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`</p> |
|External bad battery packs discovery |<p>Discovery of the number of external defective battery packs.</p> |SNMP |battery.packs.bad.discovery |
-|External sensor port 1 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor1.discovery |
-|External sensor port 2 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor2.discovery |
+|External sensor port 1 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor1.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR1_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
+|External sensor port 2 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor2.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR2_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
## Items collected
@@ -64,12 +64,12 @@ There are no template links in this template.
|-----|----|-----------|----|---------------------|
|General |Model |<p>MIB: PowerNet-MIB</p><p>The UPS model name (e.g. 'APC Smart-UPS 600').</p> |SNMP |system.model[upsBasicIdentModel]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|General |Serial number |<p>MIB: PowerNet-MIB</p><p>An 8-character string identifying the serial number of</p><p> the UPS internal microprocessor. This number is set at</p><p> the factory. NOTE: This number does NOT correspond to</p><p> the serial number on the rear of the UPS.</p> |SNMP |system.sn[upsAdvIdentSerialNumber]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
-|General |SNMP traps (fallback) |<p>Item is used to collect all SNMP traps unmatched by other snmptrap items</p> |SNMP_TRAP |snmptrap.fallback |
+|General |SNMP traps (fallback) |<p>The item is used to collect all SNMP traps unmatched by other snmptrap items</p> |SNMP_TRAP |snmptrap.fallback |
|General |System location |<p>MIB: SNMPv2-MIB</p><p>The physical location of this node (e.g., `telephone closet,</p><p>3rd floor'). If the location is unknown, the value is the zero-length string.</p> |SNMP |system.location[sysLocation.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
-|General |System contact details |<p>MIB: SNMPv2-MIB</p><p>The textual identification of the contact person for this managed</p><p>node, together with information on how to contact this person. If no contact</p><p>information is known, the value is the zero-length string.</p> |SNMP |system.contact[sysContact.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `1d`</p> |
+|General |System contact details |<p>MIB: SNMPv2-MIB</p><p>The textual identification of the contact person for this managed</p><p>node, together with information on how to contact this person. If no contact</p><p>information is known, the value is the zero-length string.</p> |SNMP |system.contact[sysContact.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `12h`</p> |
|General |System object ID |<p>MIB: SNMPv2-MIB</p><p>The vendor's authoritative identification of the network management</p><p>subsystem contained in the entity. This value is allocated within the SMI enterprises</p><p>subtree (1.3.6.1.4.1) and provides an easy and unambiguous means for determining`what</p><p>kind of box' is being managed. For example, if vendor`Flintstones, Inc.' was</p><p>assigned the subtree1.3.6.1.4.1.4242, it could assign the identifier 1.3.6.1.4.1.4242.1.1</p><p>to its `Fred Router'.</p> |SNMP |system.objectid[sysObjectID.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|General |System name |<p>MIB: SNMPv2-MIB</p><p>An administratively-assigned name for this managed node.By</p><p>convention, this is the node's fully-qualified domain name. If the name is unknown,</p><p>the value is the zero-length string.</p> |SNMP |system.name[sysName.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
-|General |System description |<p>MIB: SNMPv2-MIB</p><p>A textual description of the entity. This value should</p><p>include the full name and version identification of the system's hardware type, software operating-system, and</p><p>networking software.</p> |SNMP |system.descr[sysDescr.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `1d`</p> |
+|General |System description |<p>MIB: SNMPv2-MIB</p><p>A textual description of the entity. This value should</p><p>include the full name and version identification of the system's hardware type, software operating-system, and</p><p>networking software.</p> |SNMP |system.descr[sysDescr.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `12h`</p> |
|General |{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Serial number |<p>MIB: PowerNet-MIB</p><p>The battery pack serial number.</p> |SNMP |system.sn[upsHighPrecBatteryPackSerialNumber.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Battery status |<p>MIB: PowerNet-MIB</p><p>The status of the UPS batteries. A batteryLow(3) value</p><p> indicates the UPS will be unable to sustain the current</p><p> load, and its services will be lost if power is not restored.</p><p> The amount of run time in reserve at the time of low battery</p><p> can be configured by the upsAdvConfigLowBatteryRunTime.</p><p> A batteryInFaultCondition(4)value indicates that a battery</p><p> installed has an internal error condition.</p> |SNMP |battery.status[upsBasicBatteryStatus]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Battery capacity |<p>MIB: PowerNet-MIB</p><p>The remaining battery capacity expressed as</p><p> percentage of full capacity.</p> |SNMP |battery.capacity[upsHighPrecBatteryCapacity]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
@@ -87,7 +87,7 @@ There are no template links in this template.
|Status |Output current |<p>MIB: PowerNet-MIB</p><p>The current in amperes drawn by the load on the UPS.</p> |SNMP |output.current[upsHighPrecOutputCurrent]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Output status |<p>MIB: PowerNet-MIB</p><p>The current state of the UPS. If the UPS is unable to</p><p> determine the state of the UPS this variable is set</p><p> to unknown(1).</p><p>During self-test most UPSes report onBattery(3) but</p><p> some that support it will report onBatteryTest(15).</p><p> To determine self-test status across all UPSes, refer</p><p> to the upsBasicStateOutputState OID.</p> |SNMP |output.status[upsBasicOutputStatus]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Uptime |<p>MIB: SNMPv2-MIB</p><p>The time (in hundredths of a second) since the network management</p><p>portion of the system was last re-initialized.</p> |SNMP |system.uptime[sysUpTime.0]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.01`</p> |
-|Status |SNMP agent availability |<p>-</p> |INTERNAL |zabbix[host,snmp,available]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
+|Status |SNMP agent availability |<p>Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list.</p><p>Possible value:</p><p>0 - not available</p><p>1 - available</p><p>2 - unknown</p> |INTERNAL |zabbix[host,snmp,available]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |{#PHASEINDEX}: Phase input voltage |<p>MIB: PowerNet-MIB</p><p>The input voltage in VAC, or -1 if it's unsupported</p><p> by this UPS.</p> |SNMP |phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |{#PHASEINDEX}: Phase input current |<p>MIB: PowerNet-MIB</p><p>The input current in 0.1 amperes, or -0.1 if it's</p><p> unsupported by this UPS.</p> |SNMP |phase.input.current[upsPhaseInputCurrent.1.1.{#PHASEINDEX}]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |{#PHASEINDEX}: Phase output voltage |<p>MIB: PowerNet-MIB</p><p>The output voltage in VAC, or -1 if it's unsupported</p><p> by this UPS.</p> |SNMP |phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
@@ -109,39 +109,39 @@ There are no template links in this template.
|Name|Description|Expression|Severity|Dependencies and additional info|
|----|-----------|----|----|----|
-|System name has changed (new name: {ITEM.VALUE}) |<p>System name has changed. Ack to close.</p> |`{TEMPLATE_NAME:system.name[sysName.0].diff()}=1 and {TEMPLATE_NAME:system.name[sysName.0].strlen()}>0` |INFO |<p>Manual close: YES</p> |
-|Battery has an internal error condition |<p>A battery installed has an internal error condition.</p> |`{TEMPLATE_NAME:battery.status[upsBasicBatteryStatus].last()}=4` |AVERAGE | |
-|Battery is Low |<p>The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.</p> |`{TEMPLATE_NAME:battery.status[upsBasicBatteryStatus].last()}=3` |AVERAGE | |
-|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) | |`{TEMPLATE_NAME:battery.capacity[upsHighPrecBatteryCapacity].last()} < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
-|Battery needs replacement |<p>A battery installed has an internal error condition.</p> |`{TEMPLATE_NAME:battery.replace_indicator[upsAdvBatteryReplaceIndicator].last()}=2` |HIGH | |
-|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:battery.temperature[upsHighPrecBatteryTemperature].min({$TIME.PERIOD})} > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
-|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:input.voltage[upsHighPrecInputLineVoltage].min({$TIME.PERIOD})} > 0 and ({TEMPLATE_NAME:input.voltage[upsHighPrecInputLineVoltage].min({$TIME.PERIOD})} > {$UPS.INPUT_VOLT.MAX.WARN} or {TEMPLATE_NAME:input.voltage[upsHighPrecInputLineVoltage].max({$TIME.PERIOD})} < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
-|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:input.frequency[upsHighPrecInputFrequency].min({$TIME.PERIOD})} > 0 and ({TEMPLATE_NAME:input.frequency[upsHighPrecInputFrequency].min({$TIME.PERIOD})} > {$UPS.INPUT_FREQ.MAX.WARN} or {TEMPLATE_NAME:input.frequency[upsHighPrecInputFrequency].max({$TIME.PERIOD})} < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
-|Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD}) |<p>A battery installed has an internal error condition.</p> |`{TEMPLATE_NAME:output.load[upsHighPrecOutputLoad].min({$TIME.PERIOD})} > {$UPS.OUTPUT.MAX.WARN}` |HIGH | |
-|UPS is Timed Sleeping | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=5` |AVERAGE | |
-|UPS is Switched Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=9` |AVERAGE | |
-|UPS is Software Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=6` |AVERAGE | |
-|UPS is Sleeping Until Power Return | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=11` |AVERAGE | |
-|UPS is Rebooting | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=8` |AVERAGE | |
-|UPS is On Smart Trim | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=12` |AVERAGE | |
-|UPS is on Smart Boost | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=4` |AVERAGE | |
-|UPS is on battery | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=3` |AVERAGE | |
-|UPS is Off | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=7` |AVERAGE | |
-|UPS is Emergency Static Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=16` |AVERAGE | |
-|UPS is Hardware Failure Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=10` |AVERAGE | |
-|{HOST.NAME} has been restarted (uptime < 10m) |<p>Uptime is less than 10 minutes</p> |`{TEMPLATE_NAME:system.uptime[sysUpTime.0].last()}<10m` |WARNING |<p>Manual close: YES</p><p>**Depends on**:</p><p>- No SNMP data collection</p> |
-|No SNMP data collection |<p>SNMP is not available for polling. Please check device connectivity and SNMP settings.</p> |`{TEMPLATE_NAME:zabbix[host,snmp,available].max({$SNMP.TIMEOUT})}=0` |WARNING | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}].min({$TIME.PERIOD})} > {$UPS.INPUT_VOLT.MAX.WARN} or {TEMPLATE_NAME:phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}].max({$TIME.PERIOD})} < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}].min({$TIME.PERIOD})} > {$UPS.INPUT_VOLT.MAX.WARN} or {TEMPLATE_NAME:phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}].max({$TIME.PERIOD})} < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |<p>The battery cartridge status:</p><p>bit 0 Disconnected</p><p>bit 1 Overvoltage</p><p>bit 2 NeedsReplacement</p><p>bit 3 OvertemperatureCritical</p><p>bit 4 Charger</p><p>bit 5 TemperatureSensor</p><p>bit 6 BusSoftStart</p><p>bit 7 OvertemperatureWarning</p><p>bit 8 GeneralError</p><p>bit 9 Communication</p><p>bit 10 DisconnectedFrame</p><p>bit 11 FirmwareMismatch</p> |`{TEMPLATE_NAME:battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}].regexp("^(0{16})$")}=0` |WARNING | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}].min({$TIME.PERIOD})} > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |<p>The battery cartridge health.</p><p> bit 0 Battery lifetime okay</p><p> bit 1 Battery lifetime near end, order replacement cartridge</p><p> bit 2 Battery lifetime exceeded, replace battery</p><p> bit 3 Battery lifetime near end acknowledged, order replacement cartridge</p><p> bit 4 Battery lifetime exceeded acknowledged, replace battery</p><p> bit 5 Battery measured lifetime near end, order replacement cartridge</p><p> bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge</p> |`{TEMPLATE_NAME:battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}].regexp("^(0)[0|1]{15}$")}=1` |WARNING | |
-|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}].last()}=4` |INFO | |
-|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}].last()}=2` |AVERAGE | |
-|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}].last()}=3` |HIGH | |
-|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}].last()}=4` |INFO | |
-|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}].last()}=2` |AVERAGE | |
-|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}].last()}=3` |HIGH | |
+|System name has changed (new name: {ITEM.VALUE}) |<p>System name has changed. Ack to close.</p> |`last(/APC Smart-UPS SRT 5000 SNMP/system.name[sysName.0],#1)<>last(/APC Smart-UPS SRT 5000 SNMP/system.name[sysName.0],#2) and length(last(/APC Smart-UPS SRT 5000 SNMP/system.name[sysName.0]))>0` |INFO |<p>Manual close: YES</p> |
+|Battery has an internal error condition |<p>A battery installed has an internal error condition.</p> |`last(/APC Smart-UPS SRT 5000 SNMP/battery.status[upsBasicBatteryStatus])=4` |AVERAGE | |
+|Battery is Low |<p>The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.</p> |`last(/APC Smart-UPS SRT 5000 SNMP/battery.status[upsBasicBatteryStatus])=3` |AVERAGE | |
+|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) | |`last(/APC Smart-UPS SRT 5000 SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
+|Battery needs replacement |<p>A battery installed has an internal error condition.</p> |`last(/APC Smart-UPS SRT 5000 SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2` |HIGH | |
+|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC Smart-UPS SRT 5000 SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS SRT 5000 SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and ((min(/APC Smart-UPS SRT 5000 SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS SRT 5000 SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}))` |HIGH | |
+|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) | |`min(/APC Smart-UPS SRT 5000 SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and ((min(/APC Smart-UPS SRT 5000 SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC Smart-UPS SRT 5000 SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN}))` |HIGH | |
+|Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD}) |<p>A battery installed has an internal error condition.</p> |`min(/APC Smart-UPS SRT 5000 SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}` |HIGH | |
+|UPS is Timed Sleeping | |`last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | |
+|UPS is Switched Bypass | |`last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | |
+|UPS is Software Bypass | |`last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | |
+|UPS is Sleeping Until Power Return | |`last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | |
+|UPS is Rebooting | |`last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | |
+|UPS is On Smart Trim | |`last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | |
+|UPS is on Smart Boost | |`last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | |
+|UPS is on battery | |`last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | |
+|UPS is Off | |`last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | |
+|UPS is Emergency Static Bypass | |`last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | |
+|UPS is Hardware Failure Bypass | |`last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | |
+|{HOST.NAME} has been restarted (uptime < 10m) |<p>Uptime is less than 10 minutes</p> |`last(/APC Smart-UPS SRT 5000 SNMP/system.uptime[sysUpTime.0])<10m` |WARNING |<p>Manual close: YES</p><p>**Depends on**:</p><p>- No SNMP data collection</p> |
+|No SNMP data collection |<p>SNMP is not available for polling. Please check device connectivity and SNMP settings.</p> |`max(/APC Smart-UPS SRT 5000 SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0` |WARNING | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS SRT 5000 SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS SRT 5000 SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS SRT 5000 SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS SRT 5000 SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |<p>The battery cartridge status:</p><p>bit 0 Disconnected</p><p>bit 1 Overvoltage</p><p>bit 2 NeedsReplacement</p><p>bit 3 OvertemperatureCritical</p><p>bit 4 Charger</p><p>bit 5 TemperatureSensor</p><p>bit 6 BusSoftStart</p><p>bit 7 OvertemperatureWarning</p><p>bit 8 GeneralError</p><p>bit 9 Communication</p><p>bit 10 DisconnectedFrame</p><p>bit 11 FirmwareMismatch</p> |`find(/APC Smart-UPS SRT 5000 SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0` |WARNING | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC Smart-UPS SRT 5000 SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |<p>The battery cartridge health.</p><p> bit 0 Battery lifetime okay</p><p> bit 1 Battery lifetime near end, order replacement cartridge</p><p> bit 2 Battery lifetime exceeded, replace battery</p><p> bit 3 Battery lifetime near end acknowledged, order replacement cartridge</p><p> bit 4 Battery lifetime exceeded acknowledged, replace battery</p><p> bit 5 Battery measured lifetime near end, order replacement cartridge</p><p> bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge</p> |`find(/APC Smart-UPS SRT 5000 SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1` |WARNING | |
+|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`last(/APC Smart-UPS SRT 5000 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4` |INFO | |
+|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`last(/APC Smart-UPS SRT 5000 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2` |AVERAGE | |
+|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`last(/APC Smart-UPS SRT 5000 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=3` |HIGH | |
+|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`last(/APC Smart-UPS SRT 5000 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=4` |INFO | |
+|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`last(/APC Smart-UPS SRT 5000 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=2` |AVERAGE | |
+|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`last(/APC Smart-UPS SRT 5000 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=3` |HIGH | |
## Feedback
diff --git a/templates/power/apc/apc_ups_smart_srt_5000_snmp/template_power_apc_ups_smart_srt_5000_snmp.yaml b/templates/power/apc/apc_ups_smart_srt_5000_snmp/template_power_apc_ups_smart_srt_5000_snmp.yaml
index e114b4d4dca..8b973b21d43 100644
--- a/templates/power/apc/apc_ups_smart_srt_5000_snmp/template_power_apc_ups_smart_srt_5000_snmp.yaml
+++ b/templates/power/apc/apc_ups_smart_srt_5000_snmp/template_power_apc_ups_smart_srt_5000_snmp.yaml
@@ -1,6 +1,6 @@
zabbix_export:
- version: '5.4'
- date: '2021-05-11T08:05:00Z'
+ version: '6.0'
+ date: '2021-10-28T08:23:38Z'
groups:
-
uuid: 3dcd5bbe90534f9e8eb5c2d53756af63
@@ -19,7 +19,7 @@ zabbix_export:
You can discuss this template or leave feedback on our forum https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups
- Template tooling version used: 0.38
+ Template tooling version used: 0.39
groups:
-
name: Templates/Power
@@ -540,7 +540,7 @@ zabbix_export:
history: 2w
trends: '0'
value_type: LOG
- description: 'Item is used to collect all SNMP traps unmatched by other snmptrap items'
+ description: 'The item is used to collect all SNMP traps unmatched by other snmptrap items'
logtimefmt: 'hh:mm:sszyyyy/MM/dd'
tags:
-
@@ -552,7 +552,7 @@ zabbix_export:
type: SNMP_AGENT
snmp_oid: 1.3.6.1.2.1.1.4.0
key: 'system.contact[sysContact.0]'
- delay: 1h
+ delay: 15m
history: 2w
trends: '0'
value_type: CHAR
@@ -566,7 +566,7 @@ zabbix_export:
-
type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- - 1d
+ - 12h
tags:
-
tag: Application
@@ -577,7 +577,7 @@ zabbix_export:
type: SNMP_AGENT
snmp_oid: 1.3.6.1.2.1.1.1.0
key: 'system.descr[sysDescr.0]'
- delay: 1h
+ delay: 15m
history: 2w
trends: '0'
value_type: CHAR
@@ -590,7 +590,7 @@ zabbix_export:
-
type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- - 1d
+ - 12h
tags:
-
tag: Application
@@ -767,6 +767,12 @@ zabbix_export:
type: INTERNAL
key: 'zabbix[host,snmp,available]'
history: 7d
+ description: |
+ Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list.
+ Possible value:
+ 0 - not available
+ 1 - available
+ 2 - unknown
valuemap:
name: zabbix.host.available
preprocessing:
@@ -1427,178 +1433,6 @@ zabbix_export:
macro: '{$UPS.OUTPUT.MAX.WARN}'
value: '80'
description: 'Maximum output load in % for trigger expression.'
- dashboards:
- -
- uuid: ceb28c7c39e44859a4c1076978a40788
- name: 'UPS Summary'
- pages:
- -
- widgets:
- -
- type: PLAIN_TEXT
- width: '8'
- fields:
- -
- type: INTEGER
- name: show_lines
- value: '1'
- -
- type: INTEGER
- name: show_as_html
- value: '0'
- -
- type: ITEM
- name: itemids
- value:
- key: 'system.uptime[sysUpTime.0]'
- host: 'APC Smart-UPS SRT 5000 SNMP'
- -
- type: PLAIN_TEXT
- x: '8'
- width: '8'
- fields:
- -
- type: INTEGER
- name: show_lines
- value: '1'
- -
- type: INTEGER
- name: show_as_html
- value: '0'
- -
- type: ITEM
- name: itemids
- value:
- key: 'input.fail[upsAdvInputLineFailCause]'
- host: 'APC Smart-UPS SRT 5000 SNMP'
- -
- type: PLAIN_TEXT
- x: '16'
- width: '8'
- fields:
- -
- type: INTEGER
- name: show_lines
- value: '1'
- -
- type: INTEGER
- name: show_as_html
- value: '0'
- -
- type: ITEM
- name: itemids
- value:
- key: 'output.status[upsBasicOutputStatus]'
- host: 'APC Smart-UPS SRT 5000 SNMP'
- -
- type: PLAIN_TEXT
- 'y': '2'
- width: '8'
- fields:
- -
- type: INTEGER
- name: show_lines
- value: '1'
- -
- type: INTEGER
- name: show_as_html
- value: '0'
- -
- type: ITEM
- name: itemids
- value:
- key: 'battery.status[upsBasicBatteryStatus]'
- host: 'APC Smart-UPS SRT 5000 SNMP'
- -
- type: PLAIN_TEXT
- x: '8'
- 'y': '2'
- width: '8'
- fields:
- -
- type: INTEGER
- name: show_lines
- value: '1'
- -
- type: INTEGER
- name: show_as_html
- value: '0'
- -
- type: ITEM
- name: itemids
- value:
- key: 'battery.runtime_remaining[upsAdvBatteryRunTimeRemaining]'
- host: 'APC Smart-UPS SRT 5000 SNMP'
- -
- type: PLAIN_TEXT
- x: '16'
- 'y': '2'
- width: '8'
- fields:
- -
- type: INTEGER
- name: show_lines
- value: '1'
- -
- type: INTEGER
- name: show_as_html
- value: '0'
- -
- type: ITEM
- name: itemids
- value:
- key: 'battery.last_replace_date[upsBasicBatteryLastReplaceDate]'
- host: 'APC Smart-UPS SRT 5000 SNMP'
- -
- type: GRAPH_CLASSIC
- 'y': '4'
- width: '8'
- height: '7'
- fields:
- -
- type: INTEGER
- name: source_type
- value: '0'
- -
- type: GRAPH
- name: graphid
- value:
- name: 'Capacity of the UPS batteries'
- host: 'APC Smart-UPS SRT 5000 SNMP'
- -
- type: GRAPH_CLASSIC
- x: '8'
- 'y': '4'
- width: '8'
- height: '7'
- fields:
- -
- type: INTEGER
- name: source_type
- value: '0'
- -
- type: GRAPH
- name: graphid
- value:
- name: Voltage
- host: 'APC Smart-UPS SRT 5000 SNMP'
- -
- type: GRAPH_CLASSIC
- x: '16'
- 'y': '4'
- width: '8'
- height: '7'
- fields:
- -
- type: INTEGER
- name: source_type
- value: '0'
- -
- type: GRAPH
- name: graphid
- value:
- name: Output
- host: 'APC Smart-UPS SRT 5000 SNMP'
valuemaps:
-
uuid: 41e166e2a5f948488238198920ab4b17
diff --git a/templates/power/apc/apc_ups_smart_srt_8000_snmp/README.md b/templates/power/apc/apc_ups_smart_srt_8000_snmp/README.md
index f6e7e8560cc..275cef95eb4 100644
--- a/templates/power/apc/apc_ups_smart_srt_8000_snmp/README.md
+++ b/templates/power/apc/apc_ups_smart_srt_8000_snmp/README.md
@@ -55,8 +55,8 @@ There are no template links in this template.
|Output phases discovery |<p>The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1</p> |SNMP |output.phases.discovery |
|External battery packs discovery | |SNMP |battery.packs.discovery<p>**Filter**:</p>AND <p>- A: {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`</p> |
|External bad battery packs discovery |<p>Discovery of the number of external defective battery packs.</p> |SNMP |battery.packs.bad.discovery |
-|External sensor port 1 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor1.discovery |
-|External sensor port 2 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor2.discovery |
+|External sensor port 1 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor1.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR1_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
+|External sensor port 2 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor2.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR2_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
## Items collected
@@ -64,12 +64,12 @@ There are no template links in this template.
|-----|----|-----------|----|---------------------|
|General |Model |<p>MIB: PowerNet-MIB</p><p>The UPS model name (e.g. 'APC Smart-UPS 600').</p> |SNMP |system.model[upsBasicIdentModel]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|General |Serial number |<p>MIB: PowerNet-MIB</p><p>An 8-character string identifying the serial number of</p><p> the UPS internal microprocessor. This number is set at</p><p> the factory. NOTE: This number does NOT correspond to</p><p> the serial number on the rear of the UPS.</p> |SNMP |system.sn[upsAdvIdentSerialNumber]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
-|General |SNMP traps (fallback) |<p>Item is used to collect all SNMP traps unmatched by other snmptrap items</p> |SNMP_TRAP |snmptrap.fallback |
+|General |SNMP traps (fallback) |<p>The item is used to collect all SNMP traps unmatched by other snmptrap items</p> |SNMP_TRAP |snmptrap.fallback |
|General |System location |<p>MIB: SNMPv2-MIB</p><p>The physical location of this node (e.g., `telephone closet,</p><p>3rd floor'). If the location is unknown, the value is the zero-length string.</p> |SNMP |system.location[sysLocation.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
-|General |System contact details |<p>MIB: SNMPv2-MIB</p><p>The textual identification of the contact person for this managed</p><p>node, together with information on how to contact this person. If no contact</p><p>information is known, the value is the zero-length string.</p> |SNMP |system.contact[sysContact.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `1d`</p> |
+|General |System contact details |<p>MIB: SNMPv2-MIB</p><p>The textual identification of the contact person for this managed</p><p>node, together with information on how to contact this person. If no contact</p><p>information is known, the value is the zero-length string.</p> |SNMP |system.contact[sysContact.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `12h`</p> |
|General |System object ID |<p>MIB: SNMPv2-MIB</p><p>The vendor's authoritative identification of the network management</p><p>subsystem contained in the entity. This value is allocated within the SMI enterprises</p><p>subtree (1.3.6.1.4.1) and provides an easy and unambiguous means for determining`what</p><p>kind of box' is being managed. For example, if vendor`Flintstones, Inc.' was</p><p>assigned the subtree1.3.6.1.4.1.4242, it could assign the identifier 1.3.6.1.4.1.4242.1.1</p><p>to its `Fred Router'.</p> |SNMP |system.objectid[sysObjectID.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|General |System name |<p>MIB: SNMPv2-MIB</p><p>An administratively-assigned name for this managed node.By</p><p>convention, this is the node's fully-qualified domain name. If the name is unknown,</p><p>the value is the zero-length string.</p> |SNMP |system.name[sysName.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
-|General |System description |<p>MIB: SNMPv2-MIB</p><p>A textual description of the entity. This value should</p><p>include the full name and version identification of the system's hardware type, software operating-system, and</p><p>networking software.</p> |SNMP |system.descr[sysDescr.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `1d`</p> |
+|General |System description |<p>MIB: SNMPv2-MIB</p><p>A textual description of the entity. This value should</p><p>include the full name and version identification of the system's hardware type, software operating-system, and</p><p>networking software.</p> |SNMP |system.descr[sysDescr.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `12h`</p> |
|General |{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Serial number |<p>MIB: PowerNet-MIB</p><p>The battery pack serial number.</p> |SNMP |system.sn[upsHighPrecBatteryPackSerialNumber.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Battery status |<p>MIB: PowerNet-MIB</p><p>The status of the UPS batteries. A batteryLow(3) value</p><p> indicates the UPS will be unable to sustain the current</p><p> load, and its services will be lost if power is not restored.</p><p> The amount of run time in reserve at the time of low battery</p><p> can be configured by the upsAdvConfigLowBatteryRunTime.</p><p> A batteryInFaultCondition(4)value indicates that a battery</p><p> installed has an internal error condition.</p> |SNMP |battery.status[upsBasicBatteryStatus]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Battery capacity |<p>MIB: PowerNet-MIB</p><p>The remaining battery capacity expressed as</p><p> percentage of full capacity.</p> |SNMP |battery.capacity[upsHighPrecBatteryCapacity]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
@@ -87,7 +87,7 @@ There are no template links in this template.
|Status |Output current |<p>MIB: PowerNet-MIB</p><p>The current in amperes drawn by the load on the UPS.</p> |SNMP |output.current[upsHighPrecOutputCurrent]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Output status |<p>MIB: PowerNet-MIB</p><p>The current state of the UPS. If the UPS is unable to</p><p> determine the state of the UPS this variable is set</p><p> to unknown(1).</p><p>During self-test most UPSes report onBattery(3) but</p><p> some that support it will report onBatteryTest(15).</p><p> To determine self-test status across all UPSes, refer</p><p> to the upsBasicStateOutputState OID.</p> |SNMP |output.status[upsBasicOutputStatus]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Uptime |<p>MIB: SNMPv2-MIB</p><p>The time (in hundredths of a second) since the network management</p><p>portion of the system was last re-initialized.</p> |SNMP |system.uptime[sysUpTime.0]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.01`</p> |
-|Status |SNMP agent availability |<p>-</p> |INTERNAL |zabbix[host,snmp,available]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
+|Status |SNMP agent availability |<p>Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list.</p><p>Possible value:</p><p>0 - not available</p><p>1 - available</p><p>2 - unknown</p> |INTERNAL |zabbix[host,snmp,available]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |{#PHASEINDEX}: Phase input voltage |<p>MIB: PowerNet-MIB</p><p>The input voltage in VAC, or -1 if it's unsupported</p><p> by this UPS.</p> |SNMP |phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |{#PHASEINDEX}: Phase input current |<p>MIB: PowerNet-MIB</p><p>The input current in 0.1 amperes, or -0.1 if it's</p><p> unsupported by this UPS.</p> |SNMP |phase.input.current[upsPhaseInputCurrent.1.1.{#PHASEINDEX}]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |{#PHASEINDEX}: Phase output voltage |<p>MIB: PowerNet-MIB</p><p>The output voltage in VAC, or -1 if it's unsupported</p><p> by this UPS.</p> |SNMP |phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
@@ -109,39 +109,39 @@ There are no template links in this template.
|Name|Description|Expression|Severity|Dependencies and additional info|
|----|-----------|----|----|----|
-|System name has changed (new name: {ITEM.VALUE}) |<p>System name has changed. Ack to close.</p> |`{TEMPLATE_NAME:system.name[sysName.0].diff()}=1 and {TEMPLATE_NAME:system.name[sysName.0].strlen()}>0` |INFO |<p>Manual close: YES</p> |
-|Battery has an internal error condition |<p>A battery installed has an internal error condition.</p> |`{TEMPLATE_NAME:battery.status[upsBasicBatteryStatus].last()}=4` |AVERAGE | |
-|Battery is Low |<p>The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.</p> |`{TEMPLATE_NAME:battery.status[upsBasicBatteryStatus].last()}=3` |AVERAGE | |
-|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) | |`{TEMPLATE_NAME:battery.capacity[upsHighPrecBatteryCapacity].last()} < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
-|Battery needs replacement |<p>A battery installed has an internal error condition.</p> |`{TEMPLATE_NAME:battery.replace_indicator[upsAdvBatteryReplaceIndicator].last()}=2` |HIGH | |
-|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:battery.temperature[upsHighPrecBatteryTemperature].min({$TIME.PERIOD})} > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
-|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:input.voltage[upsHighPrecInputLineVoltage].min({$TIME.PERIOD})} > 0 and ({TEMPLATE_NAME:input.voltage[upsHighPrecInputLineVoltage].min({$TIME.PERIOD})} > {$UPS.INPUT_VOLT.MAX.WARN} or {TEMPLATE_NAME:input.voltage[upsHighPrecInputLineVoltage].max({$TIME.PERIOD})} < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
-|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:input.frequency[upsHighPrecInputFrequency].min({$TIME.PERIOD})} > 0 and ({TEMPLATE_NAME:input.frequency[upsHighPrecInputFrequency].min({$TIME.PERIOD})} > {$UPS.INPUT_FREQ.MAX.WARN} or {TEMPLATE_NAME:input.frequency[upsHighPrecInputFrequency].max({$TIME.PERIOD})} < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
-|Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD}) |<p>A battery installed has an internal error condition.</p> |`{TEMPLATE_NAME:output.load[upsHighPrecOutputLoad].min({$TIME.PERIOD})} > {$UPS.OUTPUT.MAX.WARN}` |HIGH | |
-|UPS is Timed Sleeping | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=5` |AVERAGE | |
-|UPS is Switched Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=9` |AVERAGE | |
-|UPS is Software Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=6` |AVERAGE | |
-|UPS is Sleeping Until Power Return | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=11` |AVERAGE | |
-|UPS is Rebooting | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=8` |AVERAGE | |
-|UPS is On Smart Trim | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=12` |AVERAGE | |
-|UPS is on Smart Boost | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=4` |AVERAGE | |
-|UPS is on battery | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=3` |AVERAGE | |
-|UPS is Off | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=7` |AVERAGE | |
-|UPS is Emergency Static Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=16` |AVERAGE | |
-|UPS is Hardware Failure Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=10` |AVERAGE | |
-|{HOST.NAME} has been restarted (uptime < 10m) |<p>Uptime is less than 10 minutes</p> |`{TEMPLATE_NAME:system.uptime[sysUpTime.0].last()}<10m` |WARNING |<p>Manual close: YES</p><p>**Depends on**:</p><p>- No SNMP data collection</p> |
-|No SNMP data collection |<p>SNMP is not available for polling. Please check device connectivity and SNMP settings.</p> |`{TEMPLATE_NAME:zabbix[host,snmp,available].max({$SNMP.TIMEOUT})}=0` |WARNING | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}].min({$TIME.PERIOD})} > {$UPS.INPUT_VOLT.MAX.WARN} or {TEMPLATE_NAME:phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}].max({$TIME.PERIOD})} < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}].min({$TIME.PERIOD})} > {$UPS.INPUT_VOLT.MAX.WARN} or {TEMPLATE_NAME:phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}].max({$TIME.PERIOD})} < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |<p>The battery cartridge status:</p><p>bit 0 Disconnected</p><p>bit 1 Overvoltage</p><p>bit 2 NeedsReplacement</p><p>bit 3 OvertemperatureCritical</p><p>bit 4 Charger</p><p>bit 5 TemperatureSensor</p><p>bit 6 BusSoftStart</p><p>bit 7 OvertemperatureWarning</p><p>bit 8 GeneralError</p><p>bit 9 Communication</p><p>bit 10 DisconnectedFrame</p><p>bit 11 FirmwareMismatch</p> |`{TEMPLATE_NAME:battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}].regexp("^(0{16})$")}=0` |WARNING | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}].min({$TIME.PERIOD})} > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |<p>The battery cartridge health.</p><p> bit 0 Battery lifetime okay</p><p> bit 1 Battery lifetime near end, order replacement cartridge</p><p> bit 2 Battery lifetime exceeded, replace battery</p><p> bit 3 Battery lifetime near end acknowledged, order replacement cartridge</p><p> bit 4 Battery lifetime exceeded acknowledged, replace battery</p><p> bit 5 Battery measured lifetime near end, order replacement cartridge</p><p> bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge</p> |`{TEMPLATE_NAME:battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}].regexp("^(0)[0|1]{15}$")}=1` |WARNING | |
-|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}].last()}=4` |INFO | |
-|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}].last()}=2` |AVERAGE | |
-|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}].last()}=3` |HIGH | |
-|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}].last()}=4` |INFO | |
-|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}].last()}=2` |AVERAGE | |
-|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}].last()}=3` |HIGH | |
+|System name has changed (new name: {ITEM.VALUE}) |<p>System name has changed. Ack to close.</p> |`last(/APC Smart-UPS SRT 8000 SNMP/system.name[sysName.0],#1)<>last(/APC Smart-UPS SRT 8000 SNMP/system.name[sysName.0],#2) and length(last(/APC Smart-UPS SRT 8000 SNMP/system.name[sysName.0]))>0` |INFO |<p>Manual close: YES</p> |
+|Battery has an internal error condition |<p>A battery installed has an internal error condition.</p> |`last(/APC Smart-UPS SRT 8000 SNMP/battery.status[upsBasicBatteryStatus])=4` |AVERAGE | |
+|Battery is Low |<p>The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.</p> |`last(/APC Smart-UPS SRT 8000 SNMP/battery.status[upsBasicBatteryStatus])=3` |AVERAGE | |
+|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) | |`last(/APC Smart-UPS SRT 8000 SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
+|Battery needs replacement |<p>A battery installed has an internal error condition.</p> |`last(/APC Smart-UPS SRT 8000 SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2` |HIGH | |
+|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC Smart-UPS SRT 8000 SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS SRT 8000 SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS SRT 8000 SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS SRT 8000 SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
+|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) | |`min(/APC Smart-UPS SRT 8000 SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS SRT 8000 SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC Smart-UPS SRT 8000 SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
+|Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD}) |<p>A battery installed has an internal error condition.</p> |`min(/APC Smart-UPS SRT 8000 SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}` |HIGH | |
+|UPS is Timed Sleeping | |`last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | |
+|UPS is Switched Bypass | |`last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | |
+|UPS is Software Bypass | |`last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | |
+|UPS is Sleeping Until Power Return | |`last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | |
+|UPS is Rebooting | |`last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | |
+|UPS is On Smart Trim | |`last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | |
+|UPS is on Smart Boost | |`last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | |
+|UPS is on battery | |`last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | |
+|UPS is Off | |`last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | |
+|UPS is Emergency Static Bypass | |`last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | |
+|UPS is Hardware Failure Bypass | |`last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | |
+|{HOST.NAME} has been restarted (uptime < 10m) |<p>Uptime is less than 10 minutes</p> |`last(/APC Smart-UPS SRT 8000 SNMP/system.uptime[sysUpTime.0])<10m` |WARNING |<p>Manual close: YES</p><p>**Depends on**:</p><p>- No SNMP data collection</p> |
+|No SNMP data collection |<p>SNMP is not available for polling. Please check device connectivity and SNMP settings.</p> |`max(/APC Smart-UPS SRT 8000 SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0` |WARNING | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS SRT 8000 SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS SRT 8000 SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC Smart-UPS SRT 8000 SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS SRT 8000 SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |<p>The battery cartridge status:</p><p>bit 0 Disconnected</p><p>bit 1 Overvoltage</p><p>bit 2 NeedsReplacement</p><p>bit 3 OvertemperatureCritical</p><p>bit 4 Charger</p><p>bit 5 TemperatureSensor</p><p>bit 6 BusSoftStart</p><p>bit 7 OvertemperatureWarning</p><p>bit 8 GeneralError</p><p>bit 9 Communication</p><p>bit 10 DisconnectedFrame</p><p>bit 11 FirmwareMismatch</p> |`find(/APC Smart-UPS SRT 8000 SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0` |WARNING | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC Smart-UPS SRT 8000 SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |<p>The battery cartridge health.</p><p> bit 0 Battery lifetime okay</p><p> bit 1 Battery lifetime near end, order replacement cartridge</p><p> bit 2 Battery lifetime exceeded, replace battery</p><p> bit 3 Battery lifetime near end acknowledged, order replacement cartridge</p><p> bit 4 Battery lifetime exceeded acknowledged, replace battery</p><p> bit 5 Battery measured lifetime near end, order replacement cartridge</p><p> bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge</p> |`find(/APC Smart-UPS SRT 8000 SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1` |WARNING | |
+|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`last(/APC Smart-UPS SRT 8000 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4` |INFO | |
+|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`last(/APC Smart-UPS SRT 8000 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2` |AVERAGE | |
+|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`last(/APC Smart-UPS SRT 8000 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=3` |HIGH | |
+|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`last(/APC Smart-UPS SRT 8000 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=4` |INFO | |
+|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`last(/APC Smart-UPS SRT 8000 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=2` |AVERAGE | |
+|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`last(/APC Smart-UPS SRT 8000 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=3` |HIGH | |
## Feedback
diff --git a/templates/power/apc/apc_ups_smart_srt_8000_snmp/template_power_apc_ups_smart_srt_8000_snmp.yaml b/templates/power/apc/apc_ups_smart_srt_8000_snmp/template_power_apc_ups_smart_srt_8000_snmp.yaml
index e0d49e4e1db..5a4aa69fed1 100644
--- a/templates/power/apc/apc_ups_smart_srt_8000_snmp/template_power_apc_ups_smart_srt_8000_snmp.yaml
+++ b/templates/power/apc/apc_ups_smart_srt_8000_snmp/template_power_apc_ups_smart_srt_8000_snmp.yaml
@@ -1,6 +1,6 @@
zabbix_export:
- version: '5.4'
- date: '2021-05-11T08:05:01Z'
+ version: '6.0'
+ date: '2021-10-28T08:23:45Z'
groups:
-
uuid: 3dcd5bbe90534f9e8eb5c2d53756af63
@@ -19,7 +19,7 @@ zabbix_export:
You can discuss this template or leave feedback on our forum https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups
- Template tooling version used: 0.38
+ Template tooling version used: 0.39
groups:
-
name: Templates/Power
@@ -48,7 +48,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 92e6a65ffc6d4a6bae62303ee2796580
@@ -76,7 +77,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 552e030c272d43a0998bc2648f15ae44
name: 'Battery last replace date'
@@ -101,7 +103,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 4cdd4bbff845477194a6d96a31431d23
name: 'Battery replace indicator'
@@ -121,7 +124,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 0e8030c0028144728361153c2b47016b
@@ -153,7 +157,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: ceed5ddfc9964aabaebb0b97875b1bd9
name: 'Battery status'
@@ -179,7 +184,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: cf186014cfd94ccbad3cc4cbd22b6aa1
@@ -217,7 +223,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 1e883961b65e445997c57870734a58ca
@@ -248,7 +255,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 07754bb421d0435995abbc49d4597908
name: 'Input fail cause'
@@ -291,7 +299,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 7574344f67544554804c4c68e39d3d72
name: 'Input frequency'
@@ -315,7 +324,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: b9a134c942da46ffba1acdf85a7832e4
@@ -346,7 +356,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 694ab76079b1447b99ef510d80faab6a
@@ -377,7 +388,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 0413f6ef89894dc6ba51e42f6a963f94
name: 'Output load'
@@ -402,7 +414,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 68f92026e7b345c88bf4aa679f9b642c
@@ -436,7 +449,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 9952679fada845228bbbf05bcdada305
@@ -516,7 +530,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: ae4579b14c424c0492acbfcb5aa5dd67
name: 'SNMP traps (fallback)'
@@ -525,18 +540,19 @@ zabbix_export:
history: 2w
trends: '0'
value_type: LOG
- description: 'Item is used to collect all SNMP traps unmatched by other snmptrap items'
+ description: 'The item is used to collect all SNMP traps unmatched by other snmptrap items'
logtimefmt: 'hh:mm:sszyyyy/MM/dd'
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: e4995e72f6b442bd9b8c90f09eb54f16
name: 'System contact details'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.2.1.1.4.0
key: 'system.contact[sysContact.0]'
- delay: 1h
+ delay: 15m
history: 2w
trends: '0'
value_type: CHAR
@@ -550,17 +566,18 @@ zabbix_export:
-
type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- - 1d
+ - 12h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 13d3c18413a249d492272a7373ebd772
name: 'System description'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.2.1.1.1.0
key: 'system.descr[sysDescr.0]'
- delay: 1h
+ delay: 15m
history: 2w
trends: '0'
value_type: CHAR
@@ -573,10 +590,11 @@ zabbix_export:
-
type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- - 1d
+ - 12h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 25aa469a757347089191eb8e364d4df9
name: 'System location'
@@ -599,7 +617,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 57f3c4c2aff04eef83b7a7a53fa9f95c
name: Model
@@ -620,7 +639,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 13c26820947442f581c2234c38c052cc
name: 'System name'
@@ -644,7 +664,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
triggers:
-
uuid: 852083234a55441aa2fa57b202227bef
@@ -678,7 +699,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 63852531159c44f1beca7facd8f93fa2
name: 'Serial number'
@@ -702,7 +724,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 320bdbfd8076411bb1dd63fccddec126
name: Uptime
@@ -724,7 +747,8 @@ zabbix_export:
- '0.01'
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 6f0fbe74ad4945e987e7ffdfa741d92f
@@ -743,6 +767,12 @@ zabbix_export:
type: INTERNAL
key: 'zabbix[host,snmp,available]'
history: 7d
+ description: |
+ Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list.
+ Possible value:
+ 0 - not available
+ 1 - available
+ 2 - unknown
valuemap:
name: zabbix.host.available
preprocessing:
@@ -752,7 +782,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 9a0cb26712c14045a18a0e86de4cdd54
@@ -791,7 +822,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: abfe041a98dc4023b21ec6d9e829a94a
name: 'External battery packs discovery'
@@ -828,7 +860,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 820d8eda050b41a3a9ba2889e290a28a
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery pack cartridge health'
@@ -855,7 +888,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 2d9c4ef006994ebea581b895424203f3
@@ -903,7 +937,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 5358b97f94aa47f59351be88673407a0
@@ -948,7 +983,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: b88678e600694bc19ebaf57472d8658f
@@ -976,7 +1012,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 52e5451d8c7a41478ef9dde6a3c16378
name: 'External sensor port 1 discovery'
@@ -1007,7 +1044,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 53102fe478cf47bd9fbe5240aab7cf65
name: '{#EXTERNAL_SENSOR1_NAME}: Sensor alarm status'
@@ -1031,7 +1069,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 33f4ac80a8d44752b97bc4f885a8c95f
@@ -1071,7 +1110,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
overrides:
-
name: Temp
@@ -1119,7 +1159,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: b7af85f894194cf39c369fcba0401cc5
name: '{#EXTERNAL_SENSOR2_NAME}: Sensor alarm status'
@@ -1143,7 +1184,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 9247973676c44377a4fa550990384eeb
@@ -1183,7 +1225,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
overrides:
-
name: Temp
@@ -1234,7 +1277,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 113adf39a65548abab2da39aec20c169
name: '{#PHASEINDEX}: Phase input voltage'
@@ -1255,7 +1299,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 755f972a32904dbf81a6da77f4ba57f0
@@ -1297,7 +1342,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 99357a267db04c8ca9385aaa15116b79
name: '{#PHASEINDEX}: Phase output load, %'
@@ -1319,7 +1365,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 13315206a94948a09fbb4a9843d2e149
name: '{#PHASEINDEX}: Phase output voltage'
@@ -1340,7 +1387,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 5846a7a3d56f43de8394823ed64a11ae
diff --git a/templates/power/apc/apc_ups_snmp/README.md b/templates/power/apc/apc_ups_snmp/README.md
index d92385e5e0c..680846cb853 100644
--- a/templates/power/apc/apc_ups_snmp/README.md
+++ b/templates/power/apc/apc_ups_snmp/README.md
@@ -51,8 +51,8 @@ There are no template links in this template.
|Output phases discovery |<p>The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1</p> |SNMP |output.phases.discovery |
|External battery packs discovery | |SNMP |battery.packs.discovery<p>**Filter**:</p>AND <p>- A: {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`</p> |
|External bad battery packs discovery |<p>Discovery of the number of external defective battery packs.</p> |SNMP |battery.packs.bad.discovery |
-|External sensor port 1 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor1.discovery |
-|External sensor port 2 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor2.discovery |
+|External sensor port 1 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor1.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR1_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
+|External sensor port 2 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor2.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR2_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
## Items collected
@@ -60,12 +60,12 @@ There are no template links in this template.
|-----|----|-----------|----|---------------------|
|General |Model |<p>MIB: PowerNet-MIB</p><p>The UPS model name (e.g. 'APC Smart-UPS 600').</p> |SNMP |system.model[upsBasicIdentModel]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|General |Serial number |<p>MIB: PowerNet-MIB</p><p>An 8-character string identifying the serial number of</p><p> the UPS internal microprocessor. This number is set at</p><p> the factory. NOTE: This number does NOT correspond to</p><p> the serial number on the rear of the UPS.</p> |SNMP |system.sn[upsAdvIdentSerialNumber]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
-|General |SNMP traps (fallback) |<p>Item is used to collect all SNMP traps unmatched by other snmptrap items</p> |SNMP_TRAP |snmptrap.fallback |
+|General |SNMP traps (fallback) |<p>The item is used to collect all SNMP traps unmatched by other snmptrap items</p> |SNMP_TRAP |snmptrap.fallback |
|General |System location |<p>MIB: SNMPv2-MIB</p><p>The physical location of this node (e.g., `telephone closet,</p><p>3rd floor'). If the location is unknown, the value is the zero-length string.</p> |SNMP |system.location[sysLocation.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
-|General |System contact details |<p>MIB: SNMPv2-MIB</p><p>The textual identification of the contact person for this managed</p><p>node, together with information on how to contact this person. If no contact</p><p>information is known, the value is the zero-length string.</p> |SNMP |system.contact[sysContact.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `1d`</p> |
+|General |System contact details |<p>MIB: SNMPv2-MIB</p><p>The textual identification of the contact person for this managed</p><p>node, together with information on how to contact this person. If no contact</p><p>information is known, the value is the zero-length string.</p> |SNMP |system.contact[sysContact.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `12h`</p> |
|General |System object ID |<p>MIB: SNMPv2-MIB</p><p>The vendor's authoritative identification of the network management</p><p>subsystem contained in the entity. This value is allocated within the SMI enterprises</p><p>subtree (1.3.6.1.4.1) and provides an easy and unambiguous means for determining`what</p><p>kind of box' is being managed. For example, if vendor`Flintstones, Inc.' was</p><p>assigned the subtree1.3.6.1.4.1.4242, it could assign the identifier 1.3.6.1.4.1.4242.1.1</p><p>to its `Fred Router'.</p> |SNMP |system.objectid[sysObjectID.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|General |System name |<p>MIB: SNMPv2-MIB</p><p>An administratively-assigned name for this managed node.By</p><p>convention, this is the node's fully-qualified domain name. If the name is unknown,</p><p>the value is the zero-length string.</p> |SNMP |system.name[sysName.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
-|General |System description |<p>MIB: SNMPv2-MIB</p><p>A textual description of the entity. This value should</p><p>include the full name and version identification of the system's hardware type, software operating-system, and</p><p>networking software.</p> |SNMP |system.descr[sysDescr.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `1d`</p> |
+|General |System description |<p>MIB: SNMPv2-MIB</p><p>A textual description of the entity. This value should</p><p>include the full name and version identification of the system's hardware type, software operating-system, and</p><p>networking software.</p> |SNMP |system.descr[sysDescr.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `12h`</p> |
|General |{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Serial number |<p>MIB: PowerNet-MIB</p><p>The battery pack serial number.</p> |SNMP |system.sn[upsHighPrecBatteryPackSerialNumber.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Battery status |<p>MIB: PowerNet-MIB</p><p>The status of the UPS batteries. A batteryLow(3) value</p><p> indicates the UPS will be unable to sustain the current</p><p> load, and its services will be lost if power is not restored.</p><p> The amount of run time in reserve at the time of low battery</p><p> can be configured by the upsAdvConfigLowBatteryRunTime.</p><p> A batteryInFaultCondition(4)value indicates that a battery</p><p> installed has an internal error condition.</p> |SNMP |battery.status[upsBasicBatteryStatus]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Battery capacity |<p>MIB: PowerNet-MIB</p><p>The remaining battery capacity expressed as</p><p> percentage of full capacity.</p> |SNMP |battery.capacity[upsHighPrecBatteryCapacity]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
@@ -83,7 +83,7 @@ There are no template links in this template.
|Status |Output current |<p>MIB: PowerNet-MIB</p><p>The current in amperes drawn by the load on the UPS.</p> |SNMP |output.current[upsHighPrecOutputCurrent]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Output status |<p>MIB: PowerNet-MIB</p><p>The current state of the UPS. If the UPS is unable to</p><p> determine the state of the UPS this variable is set</p><p> to unknown(1).</p><p>During self-test most UPSes report onBattery(3) but</p><p> some that support it will report onBatteryTest(15).</p><p> To determine self-test status across all UPSes, refer</p><p> to the upsBasicStateOutputState OID.</p> |SNMP |output.status[upsBasicOutputStatus]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Uptime |<p>MIB: SNMPv2-MIB</p><p>The time (in hundredths of a second) since the network management</p><p>portion of the system was last re-initialized.</p> |SNMP |system.uptime[sysUpTime.0]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.01`</p> |
-|Status |SNMP agent availability |<p>-</p> |INTERNAL |zabbix[host,snmp,available]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
+|Status |SNMP agent availability |<p>Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list.</p><p>Possible value:</p><p>0 - not available</p><p>1 - available</p><p>2 - unknown</p> |INTERNAL |zabbix[host,snmp,available]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |{#PHASEINDEX}: Phase input voltage |<p>MIB: PowerNet-MIB</p><p>The input voltage in VAC, or -1 if it's unsupported</p><p> by this UPS.</p> |SNMP |phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |{#PHASEINDEX}: Phase input current |<p>MIB: PowerNet-MIB</p><p>The input current in 0.1 amperes, or -0.1 if it's</p><p> unsupported by this UPS.</p> |SNMP |phase.input.current[upsPhaseInputCurrent.1.1.{#PHASEINDEX}]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |{#PHASEINDEX}: Phase output voltage |<p>MIB: PowerNet-MIB</p><p>The output voltage in VAC, or -1 if it's unsupported</p><p> by this UPS.</p> |SNMP |phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
@@ -105,39 +105,39 @@ There are no template links in this template.
|Name|Description|Expression|Severity|Dependencies and additional info|
|----|-----------|----|----|----|
-|System name has changed (new name: {ITEM.VALUE}) |<p>System name has changed. Ack to close.</p> |`{TEMPLATE_NAME:system.name[sysName.0].diff()}=1 and {TEMPLATE_NAME:system.name[sysName.0].strlen()}>0` |INFO |<p>Manual close: YES</p> |
-|Battery has an internal error condition |<p>A battery installed has an internal error condition.</p> |`{TEMPLATE_NAME:battery.status[upsBasicBatteryStatus].last()}=4` |AVERAGE | |
-|Battery is Low |<p>The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.</p> |`{TEMPLATE_NAME:battery.status[upsBasicBatteryStatus].last()}=3` |AVERAGE | |
-|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) | |`{TEMPLATE_NAME:battery.capacity[upsHighPrecBatteryCapacity].last()} < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
-|Battery needs replacement |<p>A battery installed has an internal error condition.</p> |`{TEMPLATE_NAME:battery.replace_indicator[upsAdvBatteryReplaceIndicator].last()}=2` |HIGH | |
-|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:battery.temperature[upsHighPrecBatteryTemperature].min({$TIME.PERIOD})} > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
-|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:input.voltage[upsHighPrecInputLineVoltage].min({$TIME.PERIOD})} > 0 and ({TEMPLATE_NAME:input.voltage[upsHighPrecInputLineVoltage].min({$TIME.PERIOD})} > {$UPS.INPUT_VOLT.MAX.WARN} or {TEMPLATE_NAME:input.voltage[upsHighPrecInputLineVoltage].max({$TIME.PERIOD})} < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
-|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:input.frequency[upsHighPrecInputFrequency].min({$TIME.PERIOD})} > 0 and ({TEMPLATE_NAME:input.frequency[upsHighPrecInputFrequency].min({$TIME.PERIOD})} > {$UPS.INPUT_FREQ.MAX.WARN} or {TEMPLATE_NAME:input.frequency[upsHighPrecInputFrequency].max({$TIME.PERIOD})} < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
-|Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD}) |<p>A battery installed has an internal error condition.</p> |`{TEMPLATE_NAME:output.load[upsHighPrecOutputLoad].min({$TIME.PERIOD})} > {$UPS.OUTPUT.MAX.WARN}` |HIGH | |
-|UPS is Timed Sleeping | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=5` |AVERAGE | |
-|UPS is Switched Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=9` |AVERAGE | |
-|UPS is Software Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=6` |AVERAGE | |
-|UPS is Sleeping Until Power Return | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=11` |AVERAGE | |
-|UPS is Rebooting | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=8` |AVERAGE | |
-|UPS is On Smart Trim | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=12` |AVERAGE | |
-|UPS is on Smart Boost | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=4` |AVERAGE | |
-|UPS is on battery | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=3` |AVERAGE | |
-|UPS is Off | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=7` |AVERAGE | |
-|UPS is Emergency Static Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=16` |AVERAGE | |
-|UPS is Hardware Failure Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=10` |AVERAGE | |
-|{HOST.NAME} has been restarted (uptime < 10m) |<p>Uptime is less than 10 minutes</p> |`{TEMPLATE_NAME:system.uptime[sysUpTime.0].last()}<10m` |WARNING |<p>Manual close: YES</p><p>**Depends on**:</p><p>- No SNMP data collection</p> |
-|No SNMP data collection |<p>SNMP is not available for polling. Please check device connectivity and SNMP settings.</p> |`{TEMPLATE_NAME:zabbix[host,snmp,available].max({$SNMP.TIMEOUT})}=0` |WARNING | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}].min({$TIME.PERIOD})} > {$UPS.INPUT_VOLT.MAX.WARN} or {TEMPLATE_NAME:phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}].max({$TIME.PERIOD})} < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}].min({$TIME.PERIOD})} > {$UPS.INPUT_VOLT.MAX.WARN} or {TEMPLATE_NAME:phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}].max({$TIME.PERIOD})} < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |<p>The battery cartridge status:</p><p>bit 0 Disconnected</p><p>bit 1 Overvoltage</p><p>bit 2 NeedsReplacement</p><p>bit 3 OvertemperatureCritical</p><p>bit 4 Charger</p><p>bit 5 TemperatureSensor</p><p>bit 6 BusSoftStart</p><p>bit 7 OvertemperatureWarning</p><p>bit 8 GeneralError</p><p>bit 9 Communication</p><p>bit 10 DisconnectedFrame</p><p>bit 11 FirmwareMismatch</p> |`{TEMPLATE_NAME:battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}].regexp("^(0{16})$")}=0` |WARNING | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}].min({$TIME.PERIOD})} > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |<p>The battery cartridge health.</p><p> bit 0 Battery lifetime okay</p><p> bit 1 Battery lifetime near end, order replacement cartridge</p><p> bit 2 Battery lifetime exceeded, replace battery</p><p> bit 3 Battery lifetime near end acknowledged, order replacement cartridge</p><p> bit 4 Battery lifetime exceeded acknowledged, replace battery</p><p> bit 5 Battery measured lifetime near end, order replacement cartridge</p><p> bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge</p> |`{TEMPLATE_NAME:battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}].regexp("^(0)[0|1]{15}$")}=1` |WARNING | |
-|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}].last()}=4` |INFO | |
-|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}].last()}=2` |AVERAGE | |
-|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}].last()}=3` |HIGH | |
-|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}].last()}=4` |INFO | |
-|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}].last()}=2` |AVERAGE | |
-|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}].last()}=3` |HIGH | |
+|System name has changed (new name: {ITEM.VALUE}) |<p>System name has changed. Ack to close.</p> |`last(/APC UPS SNMP/system.name[sysName.0],#1)<>last(/APC UPS SNMP/system.name[sysName.0],#2) and length(last(/APC UPS SNMP/system.name[sysName.0]))>0` |INFO |<p>Manual close: YES</p> |
+|Battery has an internal error condition |<p>A battery installed has an internal error condition.</p> |`last(/APC UPS SNMP/battery.status[upsBasicBatteryStatus])=4` |AVERAGE | |
+|Battery is Low |<p>The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.</p> |`last(/APC UPS SNMP/battery.status[upsBasicBatteryStatus])=3` |AVERAGE | |
+|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) | |`last(/APC UPS SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
+|Battery needs replacement |<p>A battery installed has an internal error condition.</p> |`last(/APC UPS SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2` |HIGH | |
+|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC UPS SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC UPS SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC UPS SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
+|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) | |`min(/APC UPS SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC UPS SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC UPS SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
+|Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD}) |<p>A battery installed has an internal error condition.</p> |`min(/APC UPS SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}` |HIGH | |
+|UPS is Timed Sleeping | |`last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | |
+|UPS is Switched Bypass | |`last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | |
+|UPS is Software Bypass | |`last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | |
+|UPS is Sleeping Until Power Return | |`last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | |
+|UPS is Rebooting | |`last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | |
+|UPS is On Smart Trim | |`last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | |
+|UPS is on Smart Boost | |`last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | |
+|UPS is on battery | |`last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | |
+|UPS is Off | |`last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | |
+|UPS is Emergency Static Bypass | |`last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | |
+|UPS is Hardware Failure Bypass | |`last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | |
+|{HOST.NAME} has been restarted (uptime < 10m) |<p>Uptime is less than 10 minutes</p> |`last(/APC UPS SNMP/system.uptime[sysUpTime.0])<10m` |WARNING |<p>Manual close: YES</p><p>**Depends on**:</p><p>- No SNMP data collection</p> |
+|No SNMP data collection |<p>SNMP is not available for polling. Please check device connectivity and SNMP settings.</p> |`max(/APC UPS SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0` |WARNING | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC UPS SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC UPS SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |<p>The battery cartridge status:</p><p>bit 0 Disconnected</p><p>bit 1 Overvoltage</p><p>bit 2 NeedsReplacement</p><p>bit 3 OvertemperatureCritical</p><p>bit 4 Charger</p><p>bit 5 TemperatureSensor</p><p>bit 6 BusSoftStart</p><p>bit 7 OvertemperatureWarning</p><p>bit 8 GeneralError</p><p>bit 9 Communication</p><p>bit 10 DisconnectedFrame</p><p>bit 11 FirmwareMismatch</p> |`find(/APC UPS SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0` |WARNING | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC UPS SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |<p>The battery cartridge health.</p><p> bit 0 Battery lifetime okay</p><p> bit 1 Battery lifetime near end, order replacement cartridge</p><p> bit 2 Battery lifetime exceeded, replace battery</p><p> bit 3 Battery lifetime near end acknowledged, order replacement cartridge</p><p> bit 4 Battery lifetime exceeded acknowledged, replace battery</p><p> bit 5 Battery measured lifetime near end, order replacement cartridge</p><p> bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge</p> |`find(/APC UPS SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1` |WARNING | |
+|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`last(/APC UPS SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4` |INFO | |
+|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`last(/APC UPS SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2` |AVERAGE | |
+|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`last(/APC UPS SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=3` |HIGH | |
+|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`last(/APC UPS SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=4` |INFO | |
+|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`last(/APC UPS SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=2` |AVERAGE | |
+|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`last(/APC UPS SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=3` |HIGH | |
## Feedback
diff --git a/templates/power/apc/apc_ups_snmp/template_power_apc_ups_snmp.yaml b/templates/power/apc/apc_ups_snmp/template_power_apc_ups_snmp.yaml
index 1f0618afc4a..4db906f7b38 100644
--- a/templates/power/apc/apc_ups_snmp/template_power_apc_ups_snmp.yaml
+++ b/templates/power/apc/apc_ups_snmp/template_power_apc_ups_snmp.yaml
@@ -1,6 +1,6 @@
zabbix_export:
- version: '5.4'
- date: '2021-05-11T08:05:00Z'
+ version: '6.0'
+ date: '2021-10-28T08:23:31Z'
groups:
-
uuid: 3dcd5bbe90534f9e8eb5c2d53756af63
@@ -19,7 +19,7 @@ zabbix_export:
You can discuss this template or leave feedback on our forum https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups
- Template tooling version used: 0.38
+ Template tooling version used: 0.39
groups:
-
name: Templates/Power
@@ -48,7 +48,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: aa0bbfb321d440438fb421825f23e140
@@ -76,7 +77,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 3d69adaa88e64b8084d38c1482815bf2
name: 'Battery last replace date'
@@ -101,7 +103,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: eb74b3671b4d4335ad92bd3b027547b0
name: 'Battery replace indicator'
@@ -121,7 +124,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 7e40918732e74b5e8bd854422989e77d
@@ -153,7 +157,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: f4106603e47e40548592d60a7b8b3148
name: 'Battery status'
@@ -179,7 +184,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 7ae03f3f307b4f11ad2bc0548911cbd3
@@ -217,7 +223,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 36a14fe061d1433e9875373307a4e0f4
@@ -248,7 +255,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 6ce40beab0b44248868652b0ed543afc
name: 'Input fail cause'
@@ -291,7 +299,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 2c0b565f2b6a44a2a91cc61fd220f056
name: 'Input frequency'
@@ -315,7 +324,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 1ddd2699b87f452a8893f75f805c0a81
@@ -346,7 +356,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: f6527c4fed3d41168be23f9367f18405
@@ -377,7 +388,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: c17c7fd7e6504592869dc14c4a002254
name: 'Output load'
@@ -402,7 +414,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: ebef08a42d1e47ffa82ea586c1a5b3d6
@@ -436,7 +449,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: c0e0b1db9a1f41379c340c122426778d
@@ -516,7 +530,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 2c52ba1a964a40e1b4a75582ee6ad43b
name: 'SNMP traps (fallback)'
@@ -525,18 +540,19 @@ zabbix_export:
history: 2w
trends: '0'
value_type: LOG
- description: 'Item is used to collect all SNMP traps unmatched by other snmptrap items'
+ description: 'The item is used to collect all SNMP traps unmatched by other snmptrap items'
logtimefmt: 'hh:mm:sszyyyy/MM/dd'
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 299e4e11e0374888877e1dc386409726
name: 'System contact details'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.2.1.1.4.0
key: 'system.contact[sysContact.0]'
- delay: 1h
+ delay: 15m
history: 2w
trends: '0'
value_type: CHAR
@@ -550,17 +566,18 @@ zabbix_export:
-
type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- - 1d
+ - 12h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: ed42f6f2d8c24176b53f38e0a857a129
name: 'System description'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.2.1.1.1.0
key: 'system.descr[sysDescr.0]'
- delay: 1h
+ delay: 15m
history: 2w
trends: '0'
value_type: CHAR
@@ -573,10 +590,11 @@ zabbix_export:
-
type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- - 1d
+ - 12h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 445d7a843340424ab7c09ab001d5865c
name: 'System location'
@@ -599,7 +617,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 6030dbee3cc24dbeb15e4b802e89cbc8
name: Model
@@ -620,7 +639,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 45a80892f41b411e8457f99b069b59ee
name: 'System name'
@@ -644,7 +664,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
triggers:
-
uuid: facbfd1f8bb04401b563c162d7fe13a5
@@ -678,7 +699,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 1df309508ac9433397f88120b2895451
name: 'Serial number'
@@ -702,7 +724,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 701fa778bc03444aad94343d0dbe048e
name: Uptime
@@ -724,7 +747,8 @@ zabbix_export:
- '0.01'
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: b0959bdb606542bcb2952e820ac972c9
@@ -743,6 +767,12 @@ zabbix_export:
type: INTERNAL
key: 'zabbix[host,snmp,available]'
history: 7d
+ description: |
+ Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list.
+ Possible value:
+ 0 - not available
+ 1 - available
+ 2 - unknown
valuemap:
name: zabbix.host.available
preprocessing:
@@ -752,7 +782,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 4572d871f1d944bb855b93fdc6de5e88
@@ -791,7 +822,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: f7eb1c82c6694e72b7d28ba4d71d8741
name: 'External battery packs discovery'
@@ -828,7 +860,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: fd71d1ceaf524aeaac38de5f63d101fd
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery pack cartridge health'
@@ -855,7 +888,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: a248194aa30645c5918278b83944b20e
@@ -903,7 +937,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 834b1a48cbab46a3bfb0209fb4302674
@@ -948,7 +983,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 80f084121d56464f90e4a3ef9e198889
@@ -976,7 +1012,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 457169b3c43846739614a6ddc7155fda
name: 'External sensor port 1 discovery'
@@ -1007,7 +1044,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 0431cf0a54b449c9b77623b69629920f
name: '{#EXTERNAL_SENSOR1_NAME}: Sensor alarm status'
@@ -1031,7 +1069,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 3a40f3cb0a3b411697fe8d37f82404d4
@@ -1071,7 +1110,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
overrides:
-
name: Temp
@@ -1119,7 +1159,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: d04af1687eb846d18b57af04ab1b594b
name: '{#EXTERNAL_SENSOR2_NAME}: Sensor alarm status'
@@ -1143,7 +1184,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 8a62bc38e49e4779938c45839a190856
@@ -1183,7 +1225,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
overrides:
-
name: Temp
@@ -1234,7 +1277,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 40c05eaf739540979d11787a694cb8c9
name: '{#PHASEINDEX}: Phase input voltage'
@@ -1255,7 +1299,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 63c623a2a9af44f38388a17742c87486
@@ -1297,7 +1342,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 262d5cf179e64a2596edd86adc5570e3
name: '{#PHASEINDEX}: Phase output load, %'
@@ -1319,7 +1365,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: ab38f845f0e448f0b3638f6728cbf5bf
name: '{#PHASEINDEX}: Phase output voltage'
@@ -1340,7 +1387,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: feeb23a58ccb4ec1bed9d61f5d2ffc9e
diff --git a/templates/power/apc/apc_ups_symmetra_lx_snmp/README.md b/templates/power/apc/apc_ups_symmetra_lx_snmp/README.md
index 583d86e579b..d33de955844 100644
--- a/templates/power/apc/apc_ups_symmetra_lx_snmp/README.md
+++ b/templates/power/apc/apc_ups_symmetra_lx_snmp/README.md
@@ -55,8 +55,8 @@ There are no template links in this template.
|Output phases discovery |<p>The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1</p> |SNMP |output.phases.discovery |
|External battery packs discovery | |SNMP |battery.packs.discovery<p>**Filter**:</p>AND <p>- A: {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`</p> |
|External bad battery packs discovery |<p>Discovery of the number of external defective battery packs.</p> |SNMP |battery.packs.bad.discovery |
-|External sensor port 1 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor1.discovery |
-|External sensor port 2 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor2.discovery |
+|External sensor port 1 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor1.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR1_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
+|External sensor port 2 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor2.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR2_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
## Items collected
@@ -64,12 +64,12 @@ There are no template links in this template.
|-----|----|-----------|----|---------------------|
|General |Model |<p>MIB: PowerNet-MIB</p><p>The UPS model name (e.g. 'APC Smart-UPS 600').</p> |SNMP |system.model[upsBasicIdentModel]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|General |Serial number |<p>MIB: PowerNet-MIB</p><p>An 8-character string identifying the serial number of</p><p> the UPS internal microprocessor. This number is set at</p><p> the factory. NOTE: This number does NOT correspond to</p><p> the serial number on the rear of the UPS.</p> |SNMP |system.sn[upsAdvIdentSerialNumber]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
-|General |SNMP traps (fallback) |<p>Item is used to collect all SNMP traps unmatched by other snmptrap items</p> |SNMP_TRAP |snmptrap.fallback |
+|General |SNMP traps (fallback) |<p>The item is used to collect all SNMP traps unmatched by other snmptrap items</p> |SNMP_TRAP |snmptrap.fallback |
|General |System location |<p>MIB: SNMPv2-MIB</p><p>The physical location of this node (e.g., `telephone closet,</p><p>3rd floor'). If the location is unknown, the value is the zero-length string.</p> |SNMP |system.location[sysLocation.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
-|General |System contact details |<p>MIB: SNMPv2-MIB</p><p>The textual identification of the contact person for this managed</p><p>node, together with information on how to contact this person. If no contact</p><p>information is known, the value is the zero-length string.</p> |SNMP |system.contact[sysContact.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `1d`</p> |
+|General |System contact details |<p>MIB: SNMPv2-MIB</p><p>The textual identification of the contact person for this managed</p><p>node, together with information on how to contact this person. If no contact</p><p>information is known, the value is the zero-length string.</p> |SNMP |system.contact[sysContact.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `12h`</p> |
|General |System object ID |<p>MIB: SNMPv2-MIB</p><p>The vendor's authoritative identification of the network management</p><p>subsystem contained in the entity. This value is allocated within the SMI enterprises</p><p>subtree (1.3.6.1.4.1) and provides an easy and unambiguous means for determining`what</p><p>kind of box' is being managed. For example, if vendor`Flintstones, Inc.' was</p><p>assigned the subtree1.3.6.1.4.1.4242, it could assign the identifier 1.3.6.1.4.1.4242.1.1</p><p>to its `Fred Router'.</p> |SNMP |system.objectid[sysObjectID.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|General |System name |<p>MIB: SNMPv2-MIB</p><p>An administratively-assigned name for this managed node.By</p><p>convention, this is the node's fully-qualified domain name. If the name is unknown,</p><p>the value is the zero-length string.</p> |SNMP |system.name[sysName.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
-|General |System description |<p>MIB: SNMPv2-MIB</p><p>A textual description of the entity. This value should</p><p>include the full name and version identification of the system's hardware type, software operating-system, and</p><p>networking software.</p> |SNMP |system.descr[sysDescr.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `1d`</p> |
+|General |System description |<p>MIB: SNMPv2-MIB</p><p>A textual description of the entity. This value should</p><p>include the full name and version identification of the system's hardware type, software operating-system, and</p><p>networking software.</p> |SNMP |system.descr[sysDescr.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `12h`</p> |
|General |{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Serial number |<p>MIB: PowerNet-MIB</p><p>The battery pack serial number.</p> |SNMP |system.sn[upsHighPrecBatteryPackSerialNumber.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Battery status |<p>MIB: PowerNet-MIB</p><p>The status of the UPS batteries. A batteryLow(3) value</p><p> indicates the UPS will be unable to sustain the current</p><p> load, and its services will be lost if power is not restored.</p><p> The amount of run time in reserve at the time of low battery</p><p> can be configured by the upsAdvConfigLowBatteryRunTime.</p><p> A batteryInFaultCondition(4)value indicates that a battery</p><p> installed has an internal error condition.</p> |SNMP |battery.status[upsBasicBatteryStatus]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Battery capacity |<p>MIB: PowerNet-MIB</p><p>The remaining battery capacity expressed as</p><p> percentage of full capacity.</p> |SNMP |battery.capacity[upsHighPrecBatteryCapacity]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
@@ -87,7 +87,7 @@ There are no template links in this template.
|Status |Output current |<p>MIB: PowerNet-MIB</p><p>The current in amperes drawn by the load on the UPS.</p> |SNMP |output.current[upsHighPrecOutputCurrent]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Output status |<p>MIB: PowerNet-MIB</p><p>The current state of the UPS. If the UPS is unable to</p><p> determine the state of the UPS this variable is set</p><p> to unknown(1).</p><p>During self-test most UPSes report onBattery(3) but</p><p> some that support it will report onBatteryTest(15).</p><p> To determine self-test status across all UPSes, refer</p><p> to the upsBasicStateOutputState OID.</p> |SNMP |output.status[upsBasicOutputStatus]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Uptime |<p>MIB: SNMPv2-MIB</p><p>The time (in hundredths of a second) since the network management</p><p>portion of the system was last re-initialized.</p> |SNMP |system.uptime[sysUpTime.0]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.01`</p> |
-|Status |SNMP agent availability |<p>-</p> |INTERNAL |zabbix[host,snmp,available]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
+|Status |SNMP agent availability |<p>Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list.</p><p>Possible value:</p><p>0 - not available</p><p>1 - available</p><p>2 - unknown</p> |INTERNAL |zabbix[host,snmp,available]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |{#PHASEINDEX}: Phase input voltage |<p>MIB: PowerNet-MIB</p><p>The input voltage in VAC, or -1 if it's unsupported</p><p> by this UPS.</p> |SNMP |phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |{#PHASEINDEX}: Phase input current |<p>MIB: PowerNet-MIB</p><p>The input current in 0.1 amperes, or -0.1 if it's</p><p> unsupported by this UPS.</p> |SNMP |phase.input.current[upsPhaseInputCurrent.1.1.{#PHASEINDEX}]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |{#PHASEINDEX}: Phase output voltage |<p>MIB: PowerNet-MIB</p><p>The output voltage in VAC, or -1 if it's unsupported</p><p> by this UPS.</p> |SNMP |phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
@@ -109,39 +109,39 @@ There are no template links in this template.
|Name|Description|Expression|Severity|Dependencies and additional info|
|----|-----------|----|----|----|
-|System name has changed (new name: {ITEM.VALUE}) |<p>System name has changed. Ack to close.</p> |`{TEMPLATE_NAME:system.name[sysName.0].diff()}=1 and {TEMPLATE_NAME:system.name[sysName.0].strlen()}>0` |INFO |<p>Manual close: YES</p> |
-|Battery has an internal error condition |<p>A battery installed has an internal error condition.</p> |`{TEMPLATE_NAME:battery.status[upsBasicBatteryStatus].last()}=4` |AVERAGE | |
-|Battery is Low |<p>The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.</p> |`{TEMPLATE_NAME:battery.status[upsBasicBatteryStatus].last()}=3` |AVERAGE | |
-|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) | |`{TEMPLATE_NAME:battery.capacity[upsHighPrecBatteryCapacity].last()} < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
-|Battery needs replacement |<p>A battery installed has an internal error condition.</p> |`{TEMPLATE_NAME:battery.replace_indicator[upsAdvBatteryReplaceIndicator].last()}=2` |HIGH | |
-|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:battery.temperature[upsHighPrecBatteryTemperature].min({$TIME.PERIOD})} > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
-|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:input.voltage[upsHighPrecInputLineVoltage].min({$TIME.PERIOD})} > 0 and ({TEMPLATE_NAME:input.voltage[upsHighPrecInputLineVoltage].min({$TIME.PERIOD})} > {$UPS.INPUT_VOLT.MAX.WARN} or {TEMPLATE_NAME:input.voltage[upsHighPrecInputLineVoltage].max({$TIME.PERIOD})} < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
-|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:input.frequency[upsHighPrecInputFrequency].min({$TIME.PERIOD})} > 0 and ({TEMPLATE_NAME:input.frequency[upsHighPrecInputFrequency].min({$TIME.PERIOD})} > {$UPS.INPUT_FREQ.MAX.WARN} or {TEMPLATE_NAME:input.frequency[upsHighPrecInputFrequency].max({$TIME.PERIOD})} < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
-|Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD}) |<p>A battery installed has an internal error condition.</p> |`{TEMPLATE_NAME:output.load[upsHighPrecOutputLoad].min({$TIME.PERIOD})} > {$UPS.OUTPUT.MAX.WARN}` |HIGH | |
-|UPS is Timed Sleeping | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=5` |AVERAGE | |
-|UPS is Switched Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=9` |AVERAGE | |
-|UPS is Software Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=6` |AVERAGE | |
-|UPS is Sleeping Until Power Return | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=11` |AVERAGE | |
-|UPS is Rebooting | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=8` |AVERAGE | |
-|UPS is On Smart Trim | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=12` |AVERAGE | |
-|UPS is on Smart Boost | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=4` |AVERAGE | |
-|UPS is on battery | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=3` |AVERAGE | |
-|UPS is Off | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=7` |AVERAGE | |
-|UPS is Emergency Static Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=16` |AVERAGE | |
-|UPS is Hardware Failure Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=10` |AVERAGE | |
-|{HOST.NAME} has been restarted (uptime < 10m) |<p>Uptime is less than 10 minutes</p> |`{TEMPLATE_NAME:system.uptime[sysUpTime.0].last()}<10m` |WARNING |<p>Manual close: YES</p><p>**Depends on**:</p><p>- No SNMP data collection</p> |
-|No SNMP data collection |<p>SNMP is not available for polling. Please check device connectivity and SNMP settings.</p> |`{TEMPLATE_NAME:zabbix[host,snmp,available].max({$SNMP.TIMEOUT})}=0` |WARNING | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}].min({$TIME.PERIOD})} > {$UPS.INPUT_VOLT.MAX.WARN} or {TEMPLATE_NAME:phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}].max({$TIME.PERIOD})} < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}].min({$TIME.PERIOD})} > {$UPS.INPUT_VOLT.MAX.WARN} or {TEMPLATE_NAME:phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}].max({$TIME.PERIOD})} < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |<p>The battery cartridge status:</p><p>bit 0 Disconnected</p><p>bit 1 Overvoltage</p><p>bit 2 NeedsReplacement</p><p>bit 3 OvertemperatureCritical</p><p>bit 4 Charger</p><p>bit 5 TemperatureSensor</p><p>bit 6 BusSoftStart</p><p>bit 7 OvertemperatureWarning</p><p>bit 8 GeneralError</p><p>bit 9 Communication</p><p>bit 10 DisconnectedFrame</p><p>bit 11 FirmwareMismatch</p> |`{TEMPLATE_NAME:battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}].regexp("^(0{16})$")}=0` |WARNING | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}].min({$TIME.PERIOD})} > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |<p>The battery cartridge health.</p><p> bit 0 Battery lifetime okay</p><p> bit 1 Battery lifetime near end, order replacement cartridge</p><p> bit 2 Battery lifetime exceeded, replace battery</p><p> bit 3 Battery lifetime near end acknowledged, order replacement cartridge</p><p> bit 4 Battery lifetime exceeded acknowledged, replace battery</p><p> bit 5 Battery measured lifetime near end, order replacement cartridge</p><p> bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge</p> |`{TEMPLATE_NAME:battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}].regexp("^(0)[0|1]{15}$")}=1` |WARNING | |
-|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}].last()}=4` |INFO | |
-|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}].last()}=2` |AVERAGE | |
-|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}].last()}=3` |HIGH | |
-|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}].last()}=4` |INFO | |
-|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}].last()}=2` |AVERAGE | |
-|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}].last()}=3` |HIGH | |
+|System name has changed (new name: {ITEM.VALUE}) |<p>System name has changed. Ack to close.</p> |`last(/APC UPS Symmetra LX SNMP/system.name[sysName.0],#1)<>last(/APC UPS Symmetra LX SNMP/system.name[sysName.0],#2) and length(last(/APC UPS Symmetra LX SNMP/system.name[sysName.0]))>0` |INFO |<p>Manual close: YES</p> |
+|Battery has an internal error condition |<p>A battery installed has an internal error condition.</p> |`last(/APC UPS Symmetra LX SNMP/battery.status[upsBasicBatteryStatus])=4` |AVERAGE | |
+|Battery is Low |<p>The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.</p> |`last(/APC UPS Symmetra LX SNMP/battery.status[upsBasicBatteryStatus])=3` |AVERAGE | |
+|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) | |`last(/APC UPS Symmetra LX SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
+|Battery needs replacement |<p>A battery installed has an internal error condition.</p> |`last(/APC UPS Symmetra LX SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2` |HIGH | |
+|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra LX SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra LX SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC UPS Symmetra LX SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra LX SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
+|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra LX SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC UPS Symmetra LX SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC UPS Symmetra LX SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
+|Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD}) |<p>A battery installed has an internal error condition.</p> |`min(/APC UPS Symmetra LX SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}` |HIGH | |
+|UPS is Timed Sleeping | |`last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | |
+|UPS is Switched Bypass | |`last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | |
+|UPS is Software Bypass | |`last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | |
+|UPS is Sleeping Until Power Return | |`last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | |
+|UPS is Rebooting | |`last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | |
+|UPS is On Smart Trim | |`last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | |
+|UPS is on Smart Boost | |`last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | |
+|UPS is on battery | |`last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | |
+|UPS is Off | |`last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | |
+|UPS is Emergency Static Bypass | |`last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | |
+|UPS is Hardware Failure Bypass | |`last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | |
+|{HOST.NAME} has been restarted (uptime < 10m) |<p>Uptime is less than 10 minutes</p> |`last(/APC UPS Symmetra LX SNMP/system.uptime[sysUpTime.0])<10m` |WARNING |<p>Manual close: YES</p><p>**Depends on**:</p><p>- No SNMP data collection</p> |
+|No SNMP data collection |<p>SNMP is not available for polling. Please check device connectivity and SNMP settings.</p> |`max(/APC UPS Symmetra LX SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0` |WARNING | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra LX SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra LX SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra LX SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra LX SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |<p>The battery cartridge status:</p><p>bit 0 Disconnected</p><p>bit 1 Overvoltage</p><p>bit 2 NeedsReplacement</p><p>bit 3 OvertemperatureCritical</p><p>bit 4 Charger</p><p>bit 5 TemperatureSensor</p><p>bit 6 BusSoftStart</p><p>bit 7 OvertemperatureWarning</p><p>bit 8 GeneralError</p><p>bit 9 Communication</p><p>bit 10 DisconnectedFrame</p><p>bit 11 FirmwareMismatch</p> |`find(/APC UPS Symmetra LX SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0` |WARNING | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra LX SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |<p>The battery cartridge health.</p><p> bit 0 Battery lifetime okay</p><p> bit 1 Battery lifetime near end, order replacement cartridge</p><p> bit 2 Battery lifetime exceeded, replace battery</p><p> bit 3 Battery lifetime near end acknowledged, order replacement cartridge</p><p> bit 4 Battery lifetime exceeded acknowledged, replace battery</p><p> bit 5 Battery measured lifetime near end, order replacement cartridge</p><p> bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge</p> |`find(/APC UPS Symmetra LX SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1` |WARNING | |
+|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`last(/APC UPS Symmetra LX SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4` |INFO | |
+|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`last(/APC UPS Symmetra LX SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2` |AVERAGE | |
+|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`last(/APC UPS Symmetra LX SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=3` |HIGH | |
+|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`last(/APC UPS Symmetra LX SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=4` |INFO | |
+|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`last(/APC UPS Symmetra LX SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=2` |AVERAGE | |
+|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`last(/APC UPS Symmetra LX SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=3` |HIGH | |
## Feedback
diff --git a/templates/power/apc/apc_ups_symmetra_lx_snmp/template_power_apc_ups_symmetra_lx_snmp.yaml b/templates/power/apc/apc_ups_symmetra_lx_snmp/template_power_apc_ups_symmetra_lx_snmp.yaml
index 7ee849dacdd..f35ca281026 100644
--- a/templates/power/apc/apc_ups_symmetra_lx_snmp/template_power_apc_ups_symmetra_lx_snmp.yaml
+++ b/templates/power/apc/apc_ups_symmetra_lx_snmp/template_power_apc_ups_symmetra_lx_snmp.yaml
@@ -1,6 +1,6 @@
zabbix_export:
- version: '5.4'
- date: '2021-05-11T08:04:58Z'
+ version: '6.0'
+ date: '2021-10-28T08:22:58Z'
groups:
-
uuid: 3dcd5bbe90534f9e8eb5c2d53756af63
@@ -19,7 +19,7 @@ zabbix_export:
You can discuss this template or leave feedback on our forum https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups
- Template tooling version used: 0.38
+ Template tooling version used: 0.39
groups:
-
name: Templates/Power
@@ -48,7 +48,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: fdece80f2fc44ac1974fafe190ce186f
@@ -76,7 +77,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: f4bd3a4a637640e29f50ebd36fb510e5
name: 'Battery last replace date'
@@ -101,7 +103,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 731d350450f742d880d81ff2be69e67e
name: 'Battery replace indicator'
@@ -121,7 +124,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: a1bd434a249b48b2ac0ef69ede417a72
@@ -153,7 +157,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: c1d818ee115343c8bb41bedb8de7f2bd
name: 'Battery status'
@@ -179,7 +184,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 955d79a0cf5447dd9a11d4608758e983
@@ -217,7 +223,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 5b43659a10644a51861282bc72116f9f
@@ -248,7 +255,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 13c0d202d19f4b64a52141062c4be6bb
name: 'Input fail cause'
@@ -291,7 +299,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 05ccf5bd85414ee9b5860c80f6e8323f
name: 'Input frequency'
@@ -315,7 +324,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 94a5c26b89e2416f96b61bbfc6e60a97
@@ -346,7 +356,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 2b640b94d48446609802ce6e57c7bd46
@@ -377,7 +388,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: d27e991fc0f64b4f9704fb8183567e8d
name: 'Output load'
@@ -402,7 +414,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 34562b5c734d492c89c386902dfd6e90
@@ -436,7 +449,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 6ade2b9fb9ad432596d16b3df6237ec4
@@ -516,7 +530,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 102179b315b548e289df3459bc5860c1
name: 'SNMP traps (fallback)'
@@ -525,18 +540,19 @@ zabbix_export:
history: 2w
trends: '0'
value_type: LOG
- description: 'Item is used to collect all SNMP traps unmatched by other snmptrap items'
+ description: 'The item is used to collect all SNMP traps unmatched by other snmptrap items'
logtimefmt: 'hh:mm:sszyyyy/MM/dd'
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 8dd800fbbcde431aa421eeb5a33eb798
name: 'System contact details'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.2.1.1.4.0
key: 'system.contact[sysContact.0]'
- delay: 1h
+ delay: 15m
history: 2w
trends: '0'
value_type: CHAR
@@ -550,17 +566,18 @@ zabbix_export:
-
type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- - 1d
+ - 12h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: e8c576f27f4c49ef9acd1ba7198ffbb6
name: 'System description'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.2.1.1.1.0
key: 'system.descr[sysDescr.0]'
- delay: 1h
+ delay: 15m
history: 2w
trends: '0'
value_type: CHAR
@@ -573,10 +590,11 @@ zabbix_export:
-
type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- - 1d
+ - 12h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 6a06715ef4c44534a0ebc45f4e5adb5b
name: 'System location'
@@ -599,7 +617,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 64d56d199021432886452fff5a4c6d22
name: Model
@@ -620,7 +639,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: b15628c68d4c4e8ca761ad9fa7e40a1c
name: 'System name'
@@ -644,7 +664,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
triggers:
-
uuid: 61d0836efd33437894e1edd595373f1e
@@ -678,7 +699,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 3f61bd561e7d42fbb55b71df9ea3b5b1
name: 'Serial number'
@@ -702,7 +724,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 0810681a8ae74ad8b28ea38119a93f59
name: Uptime
@@ -724,7 +747,8 @@ zabbix_export:
- '0.01'
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 9d0c32f93c0c44f69b54c91fabfa1529
@@ -743,6 +767,12 @@ zabbix_export:
type: INTERNAL
key: 'zabbix[host,snmp,available]'
history: 7d
+ description: |
+ Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list.
+ Possible value:
+ 0 - not available
+ 1 - available
+ 2 - unknown
valuemap:
name: zabbix.host.available
preprocessing:
@@ -752,7 +782,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: aeaaa7e2bd2d46a481f9d8b33ec18cb5
@@ -791,7 +822,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 168bfbfc58ca46509caf54ae3562f0bc
name: 'External battery packs discovery'
@@ -828,7 +860,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: b49b4836472f45e3b4947048dcd64cf8
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery pack cartridge health'
@@ -855,7 +888,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 2ea1a8d2bd3746dabafed72e1f6216fd
@@ -903,7 +937,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 3870634ad8c1414dabeebc10c510fba3
@@ -948,7 +983,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 730bdb68d90f4bc6aaf6cb22e04e1845
@@ -976,7 +1012,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 598521a7c59d425d9deb58c9829e344e
name: 'External sensor port 1 discovery'
@@ -1007,7 +1044,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 6182750c55f24110b076d95c2cdbd1fa
name: '{#EXTERNAL_SENSOR1_NAME}: Sensor alarm status'
@@ -1031,7 +1069,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 97b4078788d244d0b501e9465c659ff7
@@ -1071,7 +1110,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
overrides:
-
name: Temp
@@ -1119,7 +1159,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: ecc2e5c49b004027bb9ccd5498e3d169
name: '{#EXTERNAL_SENSOR2_NAME}: Sensor alarm status'
@@ -1143,7 +1184,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 3155c8cf446c40d896755a25a46ec90b
@@ -1183,7 +1225,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
overrides:
-
name: Temp
@@ -1234,7 +1277,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 080719150b424168999c21ff597e6948
name: '{#PHASEINDEX}: Phase input voltage'
@@ -1255,7 +1299,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 90e3258375e047b594deb0ecf7300c22
@@ -1297,7 +1342,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 7b0f22672b38492e92c8551c3009baef
name: '{#PHASEINDEX}: Phase output load, %'
@@ -1319,7 +1365,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: a590ab8671574e119fe3335110fdee49
name: '{#PHASEINDEX}: Phase output voltage'
@@ -1340,7 +1387,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: b8c42d5d66d9403eba697920439ae956
diff --git a/templates/power/apc/apc_ups_symmetra_rm_snmp/README.md b/templates/power/apc/apc_ups_symmetra_rm_snmp/README.md
index f63005595f5..bf3e8d79e40 100644
--- a/templates/power/apc/apc_ups_symmetra_rm_snmp/README.md
+++ b/templates/power/apc/apc_ups_symmetra_rm_snmp/README.md
@@ -55,8 +55,8 @@ There are no template links in this template.
|Output phases discovery |<p>The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1</p> |SNMP |output.phases.discovery |
|External battery packs discovery | |SNMP |battery.packs.discovery<p>**Filter**:</p>AND <p>- A: {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`</p> |
|External bad battery packs discovery |<p>Discovery of the number of external defective battery packs.</p> |SNMP |battery.packs.bad.discovery |
-|External sensor port 1 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor1.discovery |
-|External sensor port 2 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor2.discovery |
+|External sensor port 1 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor1.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR1_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
+|External sensor port 2 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor2.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR2_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
## Items collected
@@ -64,12 +64,12 @@ There are no template links in this template.
|-----|----|-----------|----|---------------------|
|General |Model |<p>MIB: PowerNet-MIB</p><p>The UPS model name (e.g. 'APC Smart-UPS 600').</p> |SNMP |system.model[upsBasicIdentModel]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|General |Serial number |<p>MIB: PowerNet-MIB</p><p>An 8-character string identifying the serial number of</p><p> the UPS internal microprocessor. This number is set at</p><p> the factory. NOTE: This number does NOT correspond to</p><p> the serial number on the rear of the UPS.</p> |SNMP |system.sn[upsAdvIdentSerialNumber]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
-|General |SNMP traps (fallback) |<p>Item is used to collect all SNMP traps unmatched by other snmptrap items</p> |SNMP_TRAP |snmptrap.fallback |
+|General |SNMP traps (fallback) |<p>The item is used to collect all SNMP traps unmatched by other snmptrap items</p> |SNMP_TRAP |snmptrap.fallback |
|General |System location |<p>MIB: SNMPv2-MIB</p><p>The physical location of this node (e.g., `telephone closet,</p><p>3rd floor'). If the location is unknown, the value is the zero-length string.</p> |SNMP |system.location[sysLocation.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
-|General |System contact details |<p>MIB: SNMPv2-MIB</p><p>The textual identification of the contact person for this managed</p><p>node, together with information on how to contact this person. If no contact</p><p>information is known, the value is the zero-length string.</p> |SNMP |system.contact[sysContact.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `1d`</p> |
+|General |System contact details |<p>MIB: SNMPv2-MIB</p><p>The textual identification of the contact person for this managed</p><p>node, together with information on how to contact this person. If no contact</p><p>information is known, the value is the zero-length string.</p> |SNMP |system.contact[sysContact.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `12h`</p> |
|General |System object ID |<p>MIB: SNMPv2-MIB</p><p>The vendor's authoritative identification of the network management</p><p>subsystem contained in the entity. This value is allocated within the SMI enterprises</p><p>subtree (1.3.6.1.4.1) and provides an easy and unambiguous means for determining`what</p><p>kind of box' is being managed. For example, if vendor`Flintstones, Inc.' was</p><p>assigned the subtree1.3.6.1.4.1.4242, it could assign the identifier 1.3.6.1.4.1.4242.1.1</p><p>to its `Fred Router'.</p> |SNMP |system.objectid[sysObjectID.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|General |System name |<p>MIB: SNMPv2-MIB</p><p>An administratively-assigned name for this managed node.By</p><p>convention, this is the node's fully-qualified domain name. If the name is unknown,</p><p>the value is the zero-length string.</p> |SNMP |system.name[sysName.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
-|General |System description |<p>MIB: SNMPv2-MIB</p><p>A textual description of the entity. This value should</p><p>include the full name and version identification of the system's hardware type, software operating-system, and</p><p>networking software.</p> |SNMP |system.descr[sysDescr.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `1d`</p> |
+|General |System description |<p>MIB: SNMPv2-MIB</p><p>A textual description of the entity. This value should</p><p>include the full name and version identification of the system's hardware type, software operating-system, and</p><p>networking software.</p> |SNMP |system.descr[sysDescr.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `12h`</p> |
|General |{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Serial number |<p>MIB: PowerNet-MIB</p><p>The battery pack serial number.</p> |SNMP |system.sn[upsHighPrecBatteryPackSerialNumber.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Battery status |<p>MIB: PowerNet-MIB</p><p>The status of the UPS batteries. A batteryLow(3) value</p><p> indicates the UPS will be unable to sustain the current</p><p> load, and its services will be lost if power is not restored.</p><p> The amount of run time in reserve at the time of low battery</p><p> can be configured by the upsAdvConfigLowBatteryRunTime.</p><p> A batteryInFaultCondition(4)value indicates that a battery</p><p> installed has an internal error condition.</p> |SNMP |battery.status[upsBasicBatteryStatus]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Battery capacity |<p>MIB: PowerNet-MIB</p><p>The remaining battery capacity expressed as</p><p> percentage of full capacity.</p> |SNMP |battery.capacity[upsHighPrecBatteryCapacity]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
@@ -87,7 +87,7 @@ There are no template links in this template.
|Status |Output current |<p>MIB: PowerNet-MIB</p><p>The current in amperes drawn by the load on the UPS.</p> |SNMP |output.current[upsHighPrecOutputCurrent]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Output status |<p>MIB: PowerNet-MIB</p><p>The current state of the UPS. If the UPS is unable to</p><p> determine the state of the UPS this variable is set</p><p> to unknown(1).</p><p>During self-test most UPSes report onBattery(3) but</p><p> some that support it will report onBatteryTest(15).</p><p> To determine self-test status across all UPSes, refer</p><p> to the upsBasicStateOutputState OID.</p> |SNMP |output.status[upsBasicOutputStatus]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Uptime |<p>MIB: SNMPv2-MIB</p><p>The time (in hundredths of a second) since the network management</p><p>portion of the system was last re-initialized.</p> |SNMP |system.uptime[sysUpTime.0]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.01`</p> |
-|Status |SNMP agent availability |<p>-</p> |INTERNAL |zabbix[host,snmp,available]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
+|Status |SNMP agent availability |<p>Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list.</p><p>Possible value:</p><p>0 - not available</p><p>1 - available</p><p>2 - unknown</p> |INTERNAL |zabbix[host,snmp,available]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |{#PHASEINDEX}: Phase input voltage |<p>MIB: PowerNet-MIB</p><p>The input voltage in VAC, or -1 if it's unsupported</p><p> by this UPS.</p> |SNMP |phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |{#PHASEINDEX}: Phase input current |<p>MIB: PowerNet-MIB</p><p>The input current in 0.1 amperes, or -0.1 if it's</p><p> unsupported by this UPS.</p> |SNMP |phase.input.current[upsPhaseInputCurrent.1.1.{#PHASEINDEX}]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |{#PHASEINDEX}: Phase output voltage |<p>MIB: PowerNet-MIB</p><p>The output voltage in VAC, or -1 if it's unsupported</p><p> by this UPS.</p> |SNMP |phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
@@ -109,39 +109,39 @@ There are no template links in this template.
|Name|Description|Expression|Severity|Dependencies and additional info|
|----|-----------|----|----|----|
-|System name has changed (new name: {ITEM.VALUE}) |<p>System name has changed. Ack to close.</p> |`{TEMPLATE_NAME:system.name[sysName.0].diff()}=1 and {TEMPLATE_NAME:system.name[sysName.0].strlen()}>0` |INFO |<p>Manual close: YES</p> |
-|Battery has an internal error condition |<p>A battery installed has an internal error condition.</p> |`{TEMPLATE_NAME:battery.status[upsBasicBatteryStatus].last()}=4` |AVERAGE | |
-|Battery is Low |<p>The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.</p> |`{TEMPLATE_NAME:battery.status[upsBasicBatteryStatus].last()}=3` |AVERAGE | |
-|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) | |`{TEMPLATE_NAME:battery.capacity[upsHighPrecBatteryCapacity].last()} < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
-|Battery needs replacement |<p>A battery installed has an internal error condition.</p> |`{TEMPLATE_NAME:battery.replace_indicator[upsAdvBatteryReplaceIndicator].last()}=2` |HIGH | |
-|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:battery.temperature[upsHighPrecBatteryTemperature].min({$TIME.PERIOD})} > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
-|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:input.voltage[upsHighPrecInputLineVoltage].min({$TIME.PERIOD})} > 0 and ({TEMPLATE_NAME:input.voltage[upsHighPrecInputLineVoltage].min({$TIME.PERIOD})} > {$UPS.INPUT_VOLT.MAX.WARN} or {TEMPLATE_NAME:input.voltage[upsHighPrecInputLineVoltage].max({$TIME.PERIOD})} < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
-|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:input.frequency[upsHighPrecInputFrequency].min({$TIME.PERIOD})} > 0 and ({TEMPLATE_NAME:input.frequency[upsHighPrecInputFrequency].min({$TIME.PERIOD})} > {$UPS.INPUT_FREQ.MAX.WARN} or {TEMPLATE_NAME:input.frequency[upsHighPrecInputFrequency].max({$TIME.PERIOD})} < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
-|Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD}) |<p>A battery installed has an internal error condition.</p> |`{TEMPLATE_NAME:output.load[upsHighPrecOutputLoad].min({$TIME.PERIOD})} > {$UPS.OUTPUT.MAX.WARN}` |HIGH | |
-|UPS is Timed Sleeping | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=5` |AVERAGE | |
-|UPS is Switched Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=9` |AVERAGE | |
-|UPS is Software Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=6` |AVERAGE | |
-|UPS is Sleeping Until Power Return | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=11` |AVERAGE | |
-|UPS is Rebooting | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=8` |AVERAGE | |
-|UPS is On Smart Trim | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=12` |AVERAGE | |
-|UPS is on Smart Boost | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=4` |AVERAGE | |
-|UPS is on battery | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=3` |AVERAGE | |
-|UPS is Off | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=7` |AVERAGE | |
-|UPS is Emergency Static Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=16` |AVERAGE | |
-|UPS is Hardware Failure Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=10` |AVERAGE | |
-|{HOST.NAME} has been restarted (uptime < 10m) |<p>Uptime is less than 10 minutes</p> |`{TEMPLATE_NAME:system.uptime[sysUpTime.0].last()}<10m` |WARNING |<p>Manual close: YES</p><p>**Depends on**:</p><p>- No SNMP data collection</p> |
-|No SNMP data collection |<p>SNMP is not available for polling. Please check device connectivity and SNMP settings.</p> |`{TEMPLATE_NAME:zabbix[host,snmp,available].max({$SNMP.TIMEOUT})}=0` |WARNING | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}].min({$TIME.PERIOD})} > {$UPS.INPUT_VOLT.MAX.WARN} or {TEMPLATE_NAME:phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}].max({$TIME.PERIOD})} < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}].min({$TIME.PERIOD})} > {$UPS.INPUT_VOLT.MAX.WARN} or {TEMPLATE_NAME:phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}].max({$TIME.PERIOD})} < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |<p>The battery cartridge status:</p><p>bit 0 Disconnected</p><p>bit 1 Overvoltage</p><p>bit 2 NeedsReplacement</p><p>bit 3 OvertemperatureCritical</p><p>bit 4 Charger</p><p>bit 5 TemperatureSensor</p><p>bit 6 BusSoftStart</p><p>bit 7 OvertemperatureWarning</p><p>bit 8 GeneralError</p><p>bit 9 Communication</p><p>bit 10 DisconnectedFrame</p><p>bit 11 FirmwareMismatch</p> |`{TEMPLATE_NAME:battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}].regexp("^(0{16})$")}=0` |WARNING | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}].min({$TIME.PERIOD})} > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |<p>The battery cartridge health.</p><p> bit 0 Battery lifetime okay</p><p> bit 1 Battery lifetime near end, order replacement cartridge</p><p> bit 2 Battery lifetime exceeded, replace battery</p><p> bit 3 Battery lifetime near end acknowledged, order replacement cartridge</p><p> bit 4 Battery lifetime exceeded acknowledged, replace battery</p><p> bit 5 Battery measured lifetime near end, order replacement cartridge</p><p> bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge</p> |`{TEMPLATE_NAME:battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}].regexp("^(0)[0|1]{15}$")}=1` |WARNING | |
-|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}].last()}=4` |INFO | |
-|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}].last()}=2` |AVERAGE | |
-|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}].last()}=3` |HIGH | |
-|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}].last()}=4` |INFO | |
-|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}].last()}=2` |AVERAGE | |
-|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}].last()}=3` |HIGH | |
+|System name has changed (new name: {ITEM.VALUE}) |<p>System name has changed. Ack to close.</p> |`last(/APC UPS Symmetra RM SNMP/system.name[sysName.0],#1)<>last(/APC UPS Symmetra RM SNMP/system.name[sysName.0],#2) and length(last(/APC UPS Symmetra RM SNMP/system.name[sysName.0]))>0` |INFO |<p>Manual close: YES</p> |
+|Battery has an internal error condition |<p>A battery installed has an internal error condition.</p> |`last(/APC UPS Symmetra RM SNMP/battery.status[upsBasicBatteryStatus])=4` |AVERAGE | |
+|Battery is Low |<p>The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.</p> |`last(/APC UPS Symmetra RM SNMP/battery.status[upsBasicBatteryStatus])=3` |AVERAGE | |
+|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) | |`last(/APC UPS Symmetra RM SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
+|Battery needs replacement |<p>A battery installed has an internal error condition.</p> |`last(/APC UPS Symmetra RM SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2` |HIGH | |
+|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra RM SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra RM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC UPS Symmetra RM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra RM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
+|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra RM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC UPS Symmetra RM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC UPS Symmetra RM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
+|Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD}) |<p>A battery installed has an internal error condition.</p> |`min(/APC UPS Symmetra RM SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}` |HIGH | |
+|UPS is Timed Sleeping | |`last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | |
+|UPS is Switched Bypass | |`last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | |
+|UPS is Software Bypass | |`last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | |
+|UPS is Sleeping Until Power Return | |`last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | |
+|UPS is Rebooting | |`last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | |
+|UPS is On Smart Trim | |`last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | |
+|UPS is on Smart Boost | |`last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | |
+|UPS is on battery | |`last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | |
+|UPS is Off | |`last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | |
+|UPS is Emergency Static Bypass | |`last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | |
+|UPS is Hardware Failure Bypass | |`last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | |
+|{HOST.NAME} has been restarted (uptime < 10m) |<p>Uptime is less than 10 minutes</p> |`last(/APC UPS Symmetra RM SNMP/system.uptime[sysUpTime.0])<10m` |WARNING |<p>Manual close: YES</p><p>**Depends on**:</p><p>- No SNMP data collection</p> |
+|No SNMP data collection |<p>SNMP is not available for polling. Please check device connectivity and SNMP settings.</p> |`max(/APC UPS Symmetra RM SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0` |WARNING | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra RM SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra RM SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra RM SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra RM SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |<p>The battery cartridge status:</p><p>bit 0 Disconnected</p><p>bit 1 Overvoltage</p><p>bit 2 NeedsReplacement</p><p>bit 3 OvertemperatureCritical</p><p>bit 4 Charger</p><p>bit 5 TemperatureSensor</p><p>bit 6 BusSoftStart</p><p>bit 7 OvertemperatureWarning</p><p>bit 8 GeneralError</p><p>bit 9 Communication</p><p>bit 10 DisconnectedFrame</p><p>bit 11 FirmwareMismatch</p> |`find(/APC UPS Symmetra RM SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0` |WARNING | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra RM SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |<p>The battery cartridge health.</p><p> bit 0 Battery lifetime okay</p><p> bit 1 Battery lifetime near end, order replacement cartridge</p><p> bit 2 Battery lifetime exceeded, replace battery</p><p> bit 3 Battery lifetime near end acknowledged, order replacement cartridge</p><p> bit 4 Battery lifetime exceeded acknowledged, replace battery</p><p> bit 5 Battery measured lifetime near end, order replacement cartridge</p><p> bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge</p> |`find(/APC UPS Symmetra RM SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1` |WARNING | |
+|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`last(/APC UPS Symmetra RM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4` |INFO | |
+|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`last(/APC UPS Symmetra RM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2` |AVERAGE | |
+|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`last(/APC UPS Symmetra RM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=3` |HIGH | |
+|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`last(/APC UPS Symmetra RM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=4` |INFO | |
+|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`last(/APC UPS Symmetra RM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=2` |AVERAGE | |
+|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`last(/APC UPS Symmetra RM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=3` |HIGH | |
## Feedback
diff --git a/templates/power/apc/apc_ups_symmetra_rm_snmp/template_power_apc_ups_symmetra_rm_snmp.yaml b/templates/power/apc/apc_ups_symmetra_rm_snmp/template_power_apc_ups_symmetra_rm_snmp.yaml
index 35d292e8f8f..5ef223ce8cf 100644
--- a/templates/power/apc/apc_ups_symmetra_rm_snmp/template_power_apc_ups_symmetra_rm_snmp.yaml
+++ b/templates/power/apc/apc_ups_symmetra_rm_snmp/template_power_apc_ups_symmetra_rm_snmp.yaml
@@ -1,6 +1,6 @@
zabbix_export:
- version: '5.4'
- date: '2021-05-11T08:04:59Z'
+ version: '6.0'
+ date: '2021-10-28T08:23:11Z'
groups:
-
uuid: 3dcd5bbe90534f9e8eb5c2d53756af63
@@ -19,7 +19,7 @@ zabbix_export:
You can discuss this template or leave feedback on our forum https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups
- Template tooling version used: 0.38
+ Template tooling version used: 0.39
groups:
-
name: Templates/Power
@@ -48,7 +48,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: dbfdc4e6eaca4d65adcde13b0682c1c2
@@ -76,7 +77,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 138afef586634623974c1cefd45281e9
name: 'Battery last replace date'
@@ -101,7 +103,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: abb901813d91481baef234496ddece33
name: 'Battery replace indicator'
@@ -121,7 +124,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 0af287bae1ee44ba997a02ae585bdd4b
@@ -153,7 +157,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 322c3b48bcb74fa5829ef41015308d97
name: 'Battery status'
@@ -179,7 +184,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: aedb557acbe44390809a27b95919e10f
@@ -217,7 +223,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 0b4490eaaf964fdabf228d34d2992d30
@@ -248,7 +255,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 439c87539027462c9b8210a056887885
name: 'Input fail cause'
@@ -291,7 +299,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: e16be6095dc24b48bc541325b1675dd0
name: 'Input frequency'
@@ -315,7 +324,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: af166242e3674f2da489a232c7bba6f1
@@ -346,7 +356,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 3b51bbae66914b19a93e7a2da289b056
@@ -377,7 +388,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 0e5240e578d043609fba4024db8c8df1
name: 'Output load'
@@ -402,7 +414,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: a25499c49d0043cda248136eb6307ef9
@@ -436,7 +449,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: f7b0e2f05c9b4b14916f99ecb89fcd49
@@ -516,7 +530,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 39dd21c0f2194acaa9fddbdfccde05dd
name: 'SNMP traps (fallback)'
@@ -525,18 +540,19 @@ zabbix_export:
history: 2w
trends: '0'
value_type: LOG
- description: 'Item is used to collect all SNMP traps unmatched by other snmptrap items'
+ description: 'The item is used to collect all SNMP traps unmatched by other snmptrap items'
logtimefmt: 'hh:mm:sszyyyy/MM/dd'
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 2d22b58a5c9f4fedbd03862398113546
name: 'System contact details'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.2.1.1.4.0
key: 'system.contact[sysContact.0]'
- delay: 1h
+ delay: 15m
history: 2w
trends: '0'
value_type: CHAR
@@ -550,17 +566,18 @@ zabbix_export:
-
type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- - 1d
+ - 12h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 251cc61592f543e3929aef3cb46f1b34
name: 'System description'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.2.1.1.1.0
key: 'system.descr[sysDescr.0]'
- delay: 1h
+ delay: 15m
history: 2w
trends: '0'
value_type: CHAR
@@ -573,10 +590,11 @@ zabbix_export:
-
type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- - 1d
+ - 12h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 49b8ef5ff3a3400d8f412d4440040461
name: 'System location'
@@ -599,7 +617,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: bd0dc104ded94e4cbba3a8557e642caf
name: Model
@@ -620,7 +639,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 155feccece4a4625b98efa206ad5e0b1
name: 'System name'
@@ -644,7 +664,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
triggers:
-
uuid: e3cf119c19b54dddb3d26d9b789ea4f5
@@ -678,7 +699,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 64ab7fd8a79448d580ad24ecf488241c
name: 'Serial number'
@@ -702,7 +724,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: b4ca2f993709413b9a00fa1389ec9e3c
name: Uptime
@@ -724,7 +747,8 @@ zabbix_export:
- '0.01'
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: fb2b4e564040422da234cdb309163b7b
@@ -743,6 +767,12 @@ zabbix_export:
type: INTERNAL
key: 'zabbix[host,snmp,available]'
history: 7d
+ description: |
+ Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list.
+ Possible value:
+ 0 - not available
+ 1 - available
+ 2 - unknown
valuemap:
name: zabbix.host.available
preprocessing:
@@ -752,7 +782,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 56f25581382a43efbddd4aba44aa86b3
@@ -791,7 +822,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: b615a0d1ef1e49678daa4de77b47623e
name: 'External battery packs discovery'
@@ -828,7 +860,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: ebaf443cd74f4be282939032a843dcef
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery pack cartridge health'
@@ -855,7 +888,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 002caa5fac72437187ab9711eb2fc7ad
@@ -903,7 +937,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 9ca2e1e1a81e4e2388f735c03f9bc1de
@@ -948,7 +983,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: b9a868a2f4a0410e9a03744eef9a5515
@@ -976,7 +1012,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 3adfddb03546462a9bcfdc5b059a29cc
name: 'External sensor port 1 discovery'
@@ -1007,7 +1044,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: e80af415f8384d0fa54c6954594b5794
name: '{#EXTERNAL_SENSOR1_NAME}: Sensor alarm status'
@@ -1031,7 +1069,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 1e6fa00989994e6f885c9ce2fde6ab24
@@ -1071,7 +1110,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
overrides:
-
name: Temp
@@ -1119,7 +1159,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: a140c9eaef4049278bc5f2bfd28d0339
name: '{#EXTERNAL_SENSOR2_NAME}: Sensor alarm status'
@@ -1143,7 +1184,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 97ef6f2fc4374174912b16db90b615a8
@@ -1183,7 +1225,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
overrides:
-
name: Temp
@@ -1234,7 +1277,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: e6d933f8a79248539fa9b5ce447813b5
name: '{#PHASEINDEX}: Phase input voltage'
@@ -1255,7 +1299,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 341c10188b984ce7aac7bb995847b69e
@@ -1297,7 +1342,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 177f5c2dcfac4bb997f778dcd58ba638
name: '{#PHASEINDEX}: Phase output load, %'
@@ -1319,7 +1365,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: cc7c08b1bf924507b6d15cd9105926a5
name: '{#PHASEINDEX}: Phase output voltage'
@@ -1340,7 +1387,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 85551dd4ca0b4ef6994348891ad77b57
diff --git a/templates/power/apc/apc_ups_symmetra_rx_snmp/README.md b/templates/power/apc/apc_ups_symmetra_rx_snmp/README.md
index 7d9d929f8bf..ff2a5e25822 100644
--- a/templates/power/apc/apc_ups_symmetra_rx_snmp/README.md
+++ b/templates/power/apc/apc_ups_symmetra_rx_snmp/README.md
@@ -51,8 +51,8 @@ There are no template links in this template.
|Output phases discovery |<p>The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1</p> |SNMP |output.phases.discovery |
|External battery packs discovery | |SNMP |battery.packs.discovery<p>**Filter**:</p>AND <p>- A: {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`</p> |
|External bad battery packs discovery |<p>Discovery of the number of external defective battery packs.</p> |SNMP |battery.packs.bad.discovery |
-|External sensor port 1 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor1.discovery |
-|External sensor port 2 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor2.discovery |
+|External sensor port 1 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor1.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR1_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
+|External sensor port 2 discovery |<p>uioSensorStatusTable</p> |SNMP |external.sensor2.discovery<p>**Overrides:**</p><p>Temp<br> - {#EXTERNAL_SENSOR2_NAME} MATCHES_REGEX `Temp`<br> - ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER</p> |
## Items collected
@@ -60,12 +60,12 @@ There are no template links in this template.
|-----|----|-----------|----|---------------------|
|General |Model |<p>MIB: PowerNet-MIB</p><p>The UPS model name (e.g. 'APC Smart-UPS 600').</p> |SNMP |system.model[upsBasicIdentModel]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|General |Serial number |<p>MIB: PowerNet-MIB</p><p>An 8-character string identifying the serial number of</p><p> the UPS internal microprocessor. This number is set at</p><p> the factory. NOTE: This number does NOT correspond to</p><p> the serial number on the rear of the UPS.</p> |SNMP |system.sn[upsAdvIdentSerialNumber]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
-|General |SNMP traps (fallback) |<p>Item is used to collect all SNMP traps unmatched by other snmptrap items</p> |SNMP_TRAP |snmptrap.fallback |
+|General |SNMP traps (fallback) |<p>The item is used to collect all SNMP traps unmatched by other snmptrap items</p> |SNMP_TRAP |snmptrap.fallback |
|General |System location |<p>MIB: SNMPv2-MIB</p><p>The physical location of this node (e.g., `telephone closet,</p><p>3rd floor'). If the location is unknown, the value is the zero-length string.</p> |SNMP |system.location[sysLocation.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
-|General |System contact details |<p>MIB: SNMPv2-MIB</p><p>The textual identification of the contact person for this managed</p><p>node, together with information on how to contact this person. If no contact</p><p>information is known, the value is the zero-length string.</p> |SNMP |system.contact[sysContact.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `1d`</p> |
+|General |System contact details |<p>MIB: SNMPv2-MIB</p><p>The textual identification of the contact person for this managed</p><p>node, together with information on how to contact this person. If no contact</p><p>information is known, the value is the zero-length string.</p> |SNMP |system.contact[sysContact.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `12h`</p> |
|General |System object ID |<p>MIB: SNMPv2-MIB</p><p>The vendor's authoritative identification of the network management</p><p>subsystem contained in the entity. This value is allocated within the SMI enterprises</p><p>subtree (1.3.6.1.4.1) and provides an easy and unambiguous means for determining`what</p><p>kind of box' is being managed. For example, if vendor`Flintstones, Inc.' was</p><p>assigned the subtree1.3.6.1.4.1.4242, it could assign the identifier 1.3.6.1.4.1.4242.1.1</p><p>to its `Fred Router'.</p> |SNMP |system.objectid[sysObjectID.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|General |System name |<p>MIB: SNMPv2-MIB</p><p>An administratively-assigned name for this managed node.By</p><p>convention, this is the node's fully-qualified domain name. If the name is unknown,</p><p>the value is the zero-length string.</p> |SNMP |system.name[sysName.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
-|General |System description |<p>MIB: SNMPv2-MIB</p><p>A textual description of the entity. This value should</p><p>include the full name and version identification of the system's hardware type, software operating-system, and</p><p>networking software.</p> |SNMP |system.descr[sysDescr.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `1d`</p> |
+|General |System description |<p>MIB: SNMPv2-MIB</p><p>A textual description of the entity. This value should</p><p>include the full name and version identification of the system's hardware type, software operating-system, and</p><p>networking software.</p> |SNMP |system.descr[sysDescr.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `12h`</p> |
|General |{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Serial number |<p>MIB: PowerNet-MIB</p><p>The battery pack serial number.</p> |SNMP |system.sn[upsHighPrecBatteryPackSerialNumber.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Battery status |<p>MIB: PowerNet-MIB</p><p>The status of the UPS batteries. A batteryLow(3) value</p><p> indicates the UPS will be unable to sustain the current</p><p> load, and its services will be lost if power is not restored.</p><p> The amount of run time in reserve at the time of low battery</p><p> can be configured by the upsAdvConfigLowBatteryRunTime.</p><p> A batteryInFaultCondition(4)value indicates that a battery</p><p> installed has an internal error condition.</p> |SNMP |battery.status[upsBasicBatteryStatus]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Battery capacity |<p>MIB: PowerNet-MIB</p><p>The remaining battery capacity expressed as</p><p> percentage of full capacity.</p> |SNMP |battery.capacity[upsHighPrecBatteryCapacity]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
@@ -83,7 +83,7 @@ There are no template links in this template.
|Status |Output current |<p>MIB: PowerNet-MIB</p><p>The current in amperes drawn by the load on the UPS.</p> |SNMP |output.current[upsHighPrecOutputCurrent]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Output status |<p>MIB: PowerNet-MIB</p><p>The current state of the UPS. If the UPS is unable to</p><p> determine the state of the UPS this variable is set</p><p> to unknown(1).</p><p>During self-test most UPSes report onBattery(3) but</p><p> some that support it will report onBatteryTest(15).</p><p> To determine self-test status across all UPSes, refer</p><p> to the upsBasicStateOutputState OID.</p> |SNMP |output.status[upsBasicOutputStatus]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |Uptime |<p>MIB: SNMPv2-MIB</p><p>The time (in hundredths of a second) since the network management</p><p>portion of the system was last re-initialized.</p> |SNMP |system.uptime[sysUpTime.0]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.01`</p> |
-|Status |SNMP agent availability |<p>-</p> |INTERNAL |zabbix[host,snmp,available]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
+|Status |SNMP agent availability |<p>Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list.</p><p>Possible value:</p><p>0 - not available</p><p>1 - available</p><p>2 - unknown</p> |INTERNAL |zabbix[host,snmp,available]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |{#PHASEINDEX}: Phase input voltage |<p>MIB: PowerNet-MIB</p><p>The input voltage in VAC, or -1 if it's unsupported</p><p> by this UPS.</p> |SNMP |phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |{#PHASEINDEX}: Phase input current |<p>MIB: PowerNet-MIB</p><p>The input current in 0.1 amperes, or -0.1 if it's</p><p> unsupported by this UPS.</p> |SNMP |phase.input.current[upsPhaseInputCurrent.1.1.{#PHASEINDEX}]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
|Status |{#PHASEINDEX}: Phase output voltage |<p>MIB: PowerNet-MIB</p><p>The output voltage in VAC, or -1 if it's unsupported</p><p> by this UPS.</p> |SNMP |phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `6h`</p> |
@@ -105,39 +105,39 @@ There are no template links in this template.
|Name|Description|Expression|Severity|Dependencies and additional info|
|----|-----------|----|----|----|
-|System name has changed (new name: {ITEM.VALUE}) |<p>System name has changed. Ack to close.</p> |`{TEMPLATE_NAME:system.name[sysName.0].diff()}=1 and {TEMPLATE_NAME:system.name[sysName.0].strlen()}>0` |INFO |<p>Manual close: YES</p> |
-|Battery has an internal error condition |<p>A battery installed has an internal error condition.</p> |`{TEMPLATE_NAME:battery.status[upsBasicBatteryStatus].last()}=4` |AVERAGE | |
-|Battery is Low |<p>The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.</p> |`{TEMPLATE_NAME:battery.status[upsBasicBatteryStatus].last()}=3` |AVERAGE | |
-|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) | |`{TEMPLATE_NAME:battery.capacity[upsHighPrecBatteryCapacity].last()} < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
-|Battery needs replacement |<p>A battery installed has an internal error condition.</p> |`{TEMPLATE_NAME:battery.replace_indicator[upsAdvBatteryReplaceIndicator].last()}=2` |HIGH | |
-|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:battery.temperature[upsHighPrecBatteryTemperature].min({$TIME.PERIOD})} > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
-|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:input.voltage[upsHighPrecInputLineVoltage].min({$TIME.PERIOD})} > 0 and ({TEMPLATE_NAME:input.voltage[upsHighPrecInputLineVoltage].min({$TIME.PERIOD})} > {$UPS.INPUT_VOLT.MAX.WARN} or {TEMPLATE_NAME:input.voltage[upsHighPrecInputLineVoltage].max({$TIME.PERIOD})} < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
-|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:input.frequency[upsHighPrecInputFrequency].min({$TIME.PERIOD})} > 0 and ({TEMPLATE_NAME:input.frequency[upsHighPrecInputFrequency].min({$TIME.PERIOD})} > {$UPS.INPUT_FREQ.MAX.WARN} or {TEMPLATE_NAME:input.frequency[upsHighPrecInputFrequency].max({$TIME.PERIOD})} < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
-|Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD}) |<p>A battery installed has an internal error condition.</p> |`{TEMPLATE_NAME:output.load[upsHighPrecOutputLoad].min({$TIME.PERIOD})} > {$UPS.OUTPUT.MAX.WARN}` |HIGH | |
-|UPS is Timed Sleeping | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=5` |AVERAGE | |
-|UPS is Switched Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=9` |AVERAGE | |
-|UPS is Software Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=6` |AVERAGE | |
-|UPS is Sleeping Until Power Return | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=11` |AVERAGE | |
-|UPS is Rebooting | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=8` |AVERAGE | |
-|UPS is On Smart Trim | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=12` |AVERAGE | |
-|UPS is on Smart Boost | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=4` |AVERAGE | |
-|UPS is on battery | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=3` |AVERAGE | |
-|UPS is Off | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=7` |AVERAGE | |
-|UPS is Emergency Static Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=16` |AVERAGE | |
-|UPS is Hardware Failure Bypass | |`{TEMPLATE_NAME:output.status[upsBasicOutputStatus].last()}=10` |AVERAGE | |
-|{HOST.NAME} has been restarted (uptime < 10m) |<p>Uptime is less than 10 minutes</p> |`{TEMPLATE_NAME:system.uptime[sysUpTime.0].last()}<10m` |WARNING |<p>Manual close: YES</p><p>**Depends on**:</p><p>- No SNMP data collection</p> |
-|No SNMP data collection |<p>SNMP is not available for polling. Please check device connectivity and SNMP settings.</p> |`{TEMPLATE_NAME:zabbix[host,snmp,available].max({$SNMP.TIMEOUT})}=0` |WARNING | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}].min({$TIME.PERIOD})} > {$UPS.INPUT_VOLT.MAX.WARN} or {TEMPLATE_NAME:phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}].max({$TIME.PERIOD})} < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
-|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}].min({$TIME.PERIOD})} > {$UPS.INPUT_VOLT.MAX.WARN} or {TEMPLATE_NAME:phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}].max({$TIME.PERIOD})} < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |<p>The battery cartridge status:</p><p>bit 0 Disconnected</p><p>bit 1 Overvoltage</p><p>bit 2 NeedsReplacement</p><p>bit 3 OvertemperatureCritical</p><p>bit 4 Charger</p><p>bit 5 TemperatureSensor</p><p>bit 6 BusSoftStart</p><p>bit 7 OvertemperatureWarning</p><p>bit 8 GeneralError</p><p>bit 9 Communication</p><p>bit 10 DisconnectedFrame</p><p>bit 11 FirmwareMismatch</p> |`{TEMPLATE_NAME:battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}].regexp("^(0{16})$")}=0` |WARNING | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`{TEMPLATE_NAME:battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}].min({$TIME.PERIOD})} > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
-|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |<p>The battery cartridge health.</p><p> bit 0 Battery lifetime okay</p><p> bit 1 Battery lifetime near end, order replacement cartridge</p><p> bit 2 Battery lifetime exceeded, replace battery</p><p> bit 3 Battery lifetime near end acknowledged, order replacement cartridge</p><p> bit 4 Battery lifetime exceeded acknowledged, replace battery</p><p> bit 5 Battery measured lifetime near end, order replacement cartridge</p><p> bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge</p> |`{TEMPLATE_NAME:battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}].regexp("^(0)[0|1]{15}$")}=1` |WARNING | |
-|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}].last()}=4` |INFO | |
-|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}].last()}=2` |AVERAGE | |
-|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}].last()}=3` |HIGH | |
-|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}].last()}=4` |INFO | |
-|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}].last()}=2` |AVERAGE | |
-|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`{TEMPLATE_NAME:external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}].last()}=3` |HIGH | |
+|System name has changed (new name: {ITEM.VALUE}) |<p>System name has changed. Ack to close.</p> |`last(/APC UPS Symmetra RX SNMP/system.name[sysName.0],#1)<>last(/APC UPS Symmetra RX SNMP/system.name[sysName.0],#2) and length(last(/APC UPS Symmetra RX SNMP/system.name[sysName.0]))>0` |INFO |<p>Manual close: YES</p> |
+|Battery has an internal error condition |<p>A battery installed has an internal error condition.</p> |`last(/APC UPS Symmetra RX SNMP/battery.status[upsBasicBatteryStatus])=4` |AVERAGE | |
+|Battery is Low |<p>The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.</p> |`last(/APC UPS Symmetra RX SNMP/battery.status[upsBasicBatteryStatus])=3` |AVERAGE | |
+|Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%) | |`last(/APC UPS Symmetra RX SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | |
+|Battery needs replacement |<p>A battery installed has an internal error condition.</p> |`last(/APC UPS Symmetra RX SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2` |HIGH | |
+|Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra RX SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra RX SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC UPS Symmetra RX SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra RX SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | |
+|Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra RX SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC UPS Symmetra RX SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC UPS Symmetra RX SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | |
+|Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD}) |<p>A battery installed has an internal error condition.</p> |`min(/APC UPS Symmetra RX SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}` |HIGH | |
+|UPS is Timed Sleeping | |`last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | |
+|UPS is Switched Bypass | |`last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | |
+|UPS is Software Bypass | |`last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | |
+|UPS is Sleeping Until Power Return | |`last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | |
+|UPS is Rebooting | |`last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | |
+|UPS is On Smart Trim | |`last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | |
+|UPS is on Smart Boost | |`last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | |
+|UPS is on battery | |`last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | |
+|UPS is Off | |`last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | |
+|UPS is Emergency Static Bypass | |`last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | |
+|UPS is Hardware Failure Bypass | |`last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | |
+|{HOST.NAME} has been restarted (uptime < 10m) |<p>Uptime is less than 10 minutes</p> |`last(/APC UPS Symmetra RX SNMP/system.uptime[sysUpTime.0])<10m` |WARNING |<p>Manual close: YES</p><p>**Depends on**:</p><p>- No SNMP data collection</p> |
+|No SNMP data collection |<p>SNMP is not available for polling. Please check device connectivity and SNMP settings.</p> |`max(/APC UPS Symmetra RX SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0` |WARNING | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra RX SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra RX SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra RX SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra RX SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |<p>The battery cartridge status:</p><p>bit 0 Disconnected</p><p>bit 1 Overvoltage</p><p>bit 2 NeedsReplacement</p><p>bit 3 OvertemperatureCritical</p><p>bit 4 Charger</p><p>bit 5 TemperatureSensor</p><p>bit 6 BusSoftStart</p><p>bit 7 OvertemperatureWarning</p><p>bit 8 GeneralError</p><p>bit 9 Communication</p><p>bit 10 DisconnectedFrame</p><p>bit 11 FirmwareMismatch</p> |`find(/APC UPS Symmetra RX SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0` |WARNING | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD}) | |`min(/APC UPS Symmetra RX SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | |
+|{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |<p>The battery cartridge health.</p><p> bit 0 Battery lifetime okay</p><p> bit 1 Battery lifetime near end, order replacement cartridge</p><p> bit 2 Battery lifetime exceeded, replace battery</p><p> bit 3 Battery lifetime near end acknowledged, order replacement cartridge</p><p> bit 4 Battery lifetime exceeded acknowledged, replace battery</p><p> bit 5 Battery measured lifetime near end, order replacement cartridge</p><p> bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge</p> |`find(/APC UPS Symmetra RX SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1` |WARNING | |
+|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`last(/APC UPS Symmetra RX SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4` |INFO | |
+|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`last(/APC UPS Symmetra RX SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2` |AVERAGE | |
+|{#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`last(/APC UPS Symmetra RX SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=3` |HIGH | |
+|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable |<p>The external sensor does not work or is not connected.</p> |`last(/APC UPS Symmetra RX SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=4` |INFO | |
+|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning |<p>The external sensor has returned a value greater than the warning threshold.</p> |`last(/APC UPS Symmetra RX SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=2` |AVERAGE | |
+|{#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical |<p>The external sensor has returned a value greater than the critical threshold.</p> |`last(/APC UPS Symmetra RX SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=3` |HIGH | |
## Feedback
diff --git a/templates/power/apc/apc_ups_symmetra_rx_snmp/template_power_apc_ups_symmetra_rx_snmp.yaml b/templates/power/apc/apc_ups_symmetra_rx_snmp/template_power_apc_ups_symmetra_rx_snmp.yaml
index 08fbe55ab6b..8856586e6a1 100644
--- a/templates/power/apc/apc_ups_symmetra_rx_snmp/template_power_apc_ups_symmetra_rx_snmp.yaml
+++ b/templates/power/apc/apc_ups_symmetra_rx_snmp/template_power_apc_ups_symmetra_rx_snmp.yaml
@@ -1,6 +1,6 @@
zabbix_export:
- version: '5.4'
- date: '2021-05-11T08:04:58Z'
+ version: '6.0'
+ date: '2021-10-28T08:23:04Z'
groups:
-
uuid: 3dcd5bbe90534f9e8eb5c2d53756af63
@@ -19,7 +19,7 @@ zabbix_export:
You can discuss this template or leave feedback on our forum https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups
- Template tooling version used: 0.38
+ Template tooling version used: 0.39
groups:
-
name: Templates/Power
@@ -48,7 +48,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 5626e87891ec4c28a17a6b5965b47e46
@@ -76,7 +77,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: c069bb03f58a47b981448a33a1663463
name: 'Battery last replace date'
@@ -101,7 +103,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 810c9cd371c14e44b8670ad3f4e003d5
name: 'Battery replace indicator'
@@ -121,7 +124,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: a74eccd4442c401a98ac3c80dd3baa13
@@ -153,7 +157,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: a5ccdee4e5ff49f183adab8a283e88a0
name: 'Battery status'
@@ -179,7 +184,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 107454c372cb413bad4d4a807c254ae0
@@ -217,7 +223,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 225ccc34992f4c718277b436bfecdc72
@@ -248,7 +255,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 598c1b4cc957455b84c2edcbe844e169
name: 'Input fail cause'
@@ -291,7 +299,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 8ab48c798ac94773b37228a8f725efd0
name: 'Input frequency'
@@ -315,7 +324,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 03b674d215604dc8acc3449610b05878
@@ -346,7 +356,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: bf495f3ffefd4e65af488d91b360539c
@@ -377,7 +388,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 3ac052b6b4e241d9af470b70212ab8d3
name: 'Output load'
@@ -402,7 +414,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: f2790aa869724c5bbeff6031561f2ca4
@@ -436,7 +449,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 48a2bee152664ede98bed55c05cc437d
@@ -516,7 +530,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: c892c7f2ddcd4e15b1d5ab907cd70dcf
name: 'SNMP traps (fallback)'
@@ -525,18 +540,19 @@ zabbix_export:
history: 2w
trends: '0'
value_type: LOG
- description: 'Item is used to collect all SNMP traps unmatched by other snmptrap items'
+ description: 'The item is used to collect all SNMP traps unmatched by other snmptrap items'
logtimefmt: 'hh:mm:sszyyyy/MM/dd'
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 1de71b45323b4eb5bc1a38315d56ce58
name: 'System contact details'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.2.1.1.4.0
key: 'system.contact[sysContact.0]'
- delay: 1h
+ delay: 15m
history: 2w
trends: '0'
value_type: CHAR
@@ -550,17 +566,18 @@ zabbix_export:
-
type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- - 1d
+ - 12h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 9bca97c1e308421b82f4769151f5177e
name: 'System description'
type: SNMP_AGENT
snmp_oid: 1.3.6.1.2.1.1.1.0
key: 'system.descr[sysDescr.0]'
- delay: 1h
+ delay: 15m
history: 2w
trends: '0'
value_type: CHAR
@@ -573,10 +590,11 @@ zabbix_export:
-
type: DISCARD_UNCHANGED_HEARTBEAT
parameters:
- - 1d
+ - 12h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: be1280a6b2d84393ad001113bf7c80f2
name: 'System location'
@@ -599,7 +617,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 5c5b88814e4c4dc9b90ed4a5e49a91ca
name: Model
@@ -620,7 +639,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 3c521e1e94da4dd2bd71719bf20e14b8
name: 'System name'
@@ -644,7 +664,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
triggers:
-
uuid: 5224767a1bee42738c49361ddabfed4b
@@ -678,7 +699,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 0e72609b44094aff8acfa58b63ca97ba
name: 'Serial number'
@@ -702,7 +724,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 4aac942cab30432d81c4df32e01af5e2
name: Uptime
@@ -724,7 +747,8 @@ zabbix_export:
- '0.01'
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: 990c0545543c42a78022589838a8a1ff
@@ -743,6 +767,12 @@ zabbix_export:
type: INTERNAL
key: 'zabbix[host,snmp,available]'
history: 7d
+ description: |
+ Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list.
+ Possible value:
+ 0 - not available
+ 1 - available
+ 2 - unknown
valuemap:
name: zabbix.host.available
preprocessing:
@@ -752,7 +782,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
triggers:
-
uuid: c0ad0941746546aeb6de2fee087c8252
@@ -791,7 +822,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 0c31de1650b94f8cabef339e2ef009e3
name: 'External battery packs discovery'
@@ -828,7 +860,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: c4a7061be8f64f398ad0f3c52db29bbd
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery pack cartridge health'
@@ -855,7 +888,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 3a48257337a84a2296db92410a8aed8c
@@ -903,7 +937,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 4498d376328e405bad7da5f1832cde8a
@@ -948,7 +983,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: f710e2b952054f35ab6e3e8e90ab7f83
@@ -976,7 +1012,8 @@ zabbix_export:
- 6h
tags:
-
- tag: General
+ tag: Application
+ value: General
-
uuid: 93941e38fd2d4b48bd8b50179692cb56
name: 'External sensor port 1 discovery'
@@ -1007,7 +1044,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 230f3e596bbc4cb6961eda599da74f5e
name: '{#EXTERNAL_SENSOR1_NAME}: Sensor alarm status'
@@ -1031,7 +1069,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 0de21ba7495d41f4834170122620c37d
@@ -1071,7 +1110,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
overrides:
-
name: Temp
@@ -1119,7 +1159,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: b8a37686d5374b4fa05717987e54c2f6
name: '{#EXTERNAL_SENSOR2_NAME}: Sensor alarm status'
@@ -1143,7 +1184,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: f27f80f391a04927bb138ba66d48d364
@@ -1183,7 +1225,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
overrides:
-
name: Temp
@@ -1234,7 +1277,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 6993631adffb41fabc7995bd9158e448
name: '{#PHASEINDEX}: Phase input voltage'
@@ -1255,7 +1299,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-
uuid: 212cf86650fc4c189115da565111f5d3
@@ -1297,7 +1342,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 5ec8aae1e2b24350b005d0177b164e6b
name: '{#PHASEINDEX}: Phase output load, %'
@@ -1319,7 +1365,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
-
uuid: 3da95223adfc4d638406c6908bba7063
name: '{#PHASEINDEX}: Phase output voltage'
@@ -1340,7 +1387,8 @@ zabbix_export:
- 6h
tags:
-
- tag: Status
+ tag: Application
+ value: Status
trigger_prototypes:
-