# APC Smart-UPS RT 1000 XL SNMP ## Overview For Zabbix version: 6.2 and higher The template to monitor APC Smart-UPS RT 1000 XL by Zabbix SNMP agent. Note: please, use the latest version of the firmware for your NMC in order for the template to work correctly. This template was tested on: - APC Smart-UPS RT 1000 XL ## Setup > See [Zabbix template operation](https://www.zabbix.com/documentation/6.2/manual/config/templates_out_of_the_box/network_devices) for basic instructions. 1\. Create a host for APC Smart-UPS RT 1000 XL management IP as SNMPv2 interface. 2\. Link the template to the host. 3\. Customize macro values if needed. ## Zabbix configuration No specific Zabbix configuration is required. ### Macros used |Name|Description|Default| |----|-----------|-------| |{$BATTERY.CAPACITY.MIN.WARN} |
Minimum battery capacity percentage for trigger expression.
|`50` | |{$BATTERY.TEMP.MAX.WARN} |Maximum battery temperature for trigger expression.
|`55` | |{$SNMP.TIMEOUT} |The time interval for SNMP agent availability trigger expression.
|`5m` | |{$TIME.PERIOD} |Time period for trigger expression.
|`15m` | |{$UPS.INPUT_FREQ.MAX.WARN} |Maximum input frequency for trigger expression.
|`50.3` | |{$UPS.INPUT_FREQ.MIN.WARN} |Minimum input frequency for trigger expression.
|`49.7` | |{$UPS.INPUT_VOLT.MAX.WARN} |Maximum input voltage for trigger expression.
|`243` | |{$UPS.INPUT_VOLT.MIN.WARN} |Minimum input voltage for trigger expression.
|`197` | |{$UPS.OUTPUT.MAX.WARN} |Maximum output load in % for trigger expression.
|`80` | ## Template links There are no template links in this template. ## Discovery rules |Name|Description|Type|Key and additional info| |----|-----------|----|----| |External bad battery packs discovery |Discovery of the number of external defective battery packs.
|SNMP |battery.packs.bad.discovery | |External battery packs discovery |-
|SNMP |battery.packs.discovery**Filter**:
AND- {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX `^$`
| |External sensor port 1 discovery |uioSensorStatusTable
|SNMP |external.sensor1.discovery**Overrides:**
Temp
- {#EXTERNAL_SENSOR1_NAME} MATCHES_REGEX `Temp`
- ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER
uioSensorStatusTable
|SNMP |external.sensor2.discovery**Overrides:**
Temp
- {#EXTERNAL_SENSOR2_NAME} MATCHES_REGEX `Temp`
- ITEM_PROTOTYPE LIKE `Humidity` - NO_DISCOVER
The input phase identifier. OID upsPhaseInputPhaseIndex.1.1
|SNMP |input.phases.discovery | |Output phases discovery |The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1
|SNMP |output.phases.discovery | ## Items collected |Group|Name|Description|Type|Key and additional info| |-----|----|-----------|----|---------------------| |General |Model |MIB: PowerNet-MIB
The UPS model name (e.g. 'APC Smart-UPS 600').
|SNMP |system.model[upsBasicIdentModel]**Preprocessing**:
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |General |Serial number |MIB: PowerNet-MIB
An 8-character string identifying the serial number of
the UPS internal microprocessor. This number is set at
the factory. NOTE: This number does NOT correspond to
the serial number on the rear of the UPS.
|SNMP |system.sn[upsAdvIdentSerialNumber]**Preprocessing**:
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |General |SNMP traps (fallback) |The item is used to collect all SNMP traps unmatched by other snmptrap items
|SNMP_TRAP |snmptrap.fallback | |General |System location |MIB: SNMPv2-MIB
The physical location of this node (e.g., `telephone closet,
3rd floor'). If the location is unknown, the value is the zero-length string.
|SNMP |system.location[sysLocation.0]**Preprocessing**:
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |General |System contact details |MIB: SNMPv2-MIB
The textual identification of the contact person for this managed
node, together with information on how to contact this person. If no contact
information is known, the value is the zero-length string.
|SNMP |system.contact[sysContact.0]**Preprocessing**:
- DISCARD_UNCHANGED_HEARTBEAT: `12h`
| |General |System object ID |MIB: SNMPv2-MIB
The vendor's authoritative identification of the network management
subsystem contained in the entity. This value is allocated within the SMI enterprises
subtree (1.3.6.1.4.1) and provides an easy and unambiguous means for determining`what
kind of box' is being managed. For example, if vendor`Flintstones, Inc.' was
assigned the subtree1.3.6.1.4.1.4242, it could assign the identifier 1.3.6.1.4.1.4242.1.1
to its `Fred Router'.
|SNMP |system.objectid[sysObjectID.0]**Preprocessing**:
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |General |System name |MIB: SNMPv2-MIB
An administratively-assigned name for this managed node.By
convention, this is the node's fully-qualified domain name. If the name is unknown,
the value is the zero-length string.
|SNMP |system.name[sysName.0]**Preprocessing**:
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |General |System description |MIB: SNMPv2-MIB
A textual description of the entity. This value should
include the full name and version identification of the system's hardware type, software operating-system, and
networking software.
|SNMP |system.descr[sysDescr.0]**Preprocessing**:
- DISCARD_UNCHANGED_HEARTBEAT: `12h`
| |General |{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Serial number |MIB: PowerNet-MIB
The battery pack serial number.
|SNMP |system.sn[upsHighPrecBatteryPackSerialNumber.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]**Preprocessing**:
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |Status |Battery status |MIB: PowerNet-MIB
The status of the UPS batteries. A batteryLow(3) value
indicates the UPS will be unable to sustain the current
load, and its services will be lost if power is not restored.
The amount of run time in reserve at the time of low battery
can be configured by the upsAdvConfigLowBatteryRunTime.
A batteryInFaultCondition(4)value indicates that a battery
installed has an internal error condition.
|SNMP |battery.status[upsBasicBatteryStatus]**Preprocessing**:
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |Status |Battery capacity |MIB: PowerNet-MIB
The remaining battery capacity expressed as
percentage of full capacity.
|SNMP |battery.capacity[upsHighPrecBatteryCapacity]**Preprocessing**:
- MULTIPLIER: `0.1`
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |Status |Battery runtime remaining |MIB: PowerNet-MIB
The UPS battery run time remaining before battery
exhaustion.
|SNMP |battery.runtime_remaining[upsAdvBatteryRunTimeRemaining]**Preprocessing**:
- MULTIPLIER: `0.01`
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |Status |Battery voltage |MIB: PowerNet-MIB
The actual battery bus voltage in Volts.
|SNMP |battery.voltage[upsHighPrecBatteryActualVoltage]**Preprocessing**:
- MULTIPLIER: `0.1`
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |Status |Battery last replace date |MIB: PowerNet-MIB
The date when the UPS system's batteries were last replaced
in mm/dd/yy (or yyyy) format. For Smart-UPS models, this value
is originally set at the factory. When the UPS batteries
are replaced, this value should be reset by the administrator.
For Symmetra PX 250/500 this OID is read-only and is configurable in the local display only.
|SNMP |battery.last_replace_date[upsBasicBatteryLastReplaceDate]**Preprocessing**:
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |Status |Battery replace indicator |MIB: PowerNet-MIB
Indicates whether the UPS batteries need replacement.
|SNMP |battery.replace_indicator[upsAdvBatteryReplaceIndicator]**Preprocessing**:
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |Status |External battery packs count |MIB: PowerNet-MIB
The number of external battery packs connected to the UPS. If
the UPS does not use smart cells then the agent reports
ERROR_NO_SUCH_NAME.
|SNMP |battery.external_packs_count[upsAdvBatteryNumOfBattPacks]**Preprocessing**:
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |Status |Battery temperature |MIB: PowerNet-MIB
The current internal UPS temperature in Celsius.
Temperatures below zero read as 0.
|SNMP |battery.temperature[upsHighPrecBatteryTemperature]**Preprocessing**:
- MULTIPLIER: `0.1`
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |Status |Input voltage |MIB: PowerNet-MIB
The current utility line voltage in VAC.
|SNMP |input.voltage[upsHighPrecInputLineVoltage]**Preprocessing**:
- MULTIPLIER: `0.1`
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |Status |Input frequency |MIB: PowerNet-MIB
The current input frequency to the UPS system in Hz.
|SNMP |input.frequency[upsHighPrecInputFrequency]**Preprocessing**:
- MULTIPLIER: `0.1`
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |Status |Input fail cause |MIB: PowerNet-MIB
The reason for the occurrence of the last transfer to UPS
battery power. The variable is set to:
- noTransfer(1) -- if there is no transfer yet.
- highLineVoltage(2) -- if the transfer to battery is caused
by an over voltage greater than the high transfer voltage.
- brownout(3) -- if the duration of the outage is greater than
five seconds and the line voltage is between 40% of the
rated output voltage and the low transfer voltage.
- blackout(4) -- if the duration of the outage is greater than five
seconds and the line voltage is between 40% of the rated
output voltage and ground.
- smallMomentarySag(5) -- if the duration of the outage is less
than five seconds and the line voltage is between 40% of the
rated output voltage and the low transfer voltage.
- deepMomentarySag(6) -- if the duration of the outage is less
than five seconds and the line voltage is between 40% of the
rated output voltage and ground. The variable is set to
- smallMomentarySpike(7) -- if the line failure is caused by a
rate of change of input voltage less than ten volts per cycle.
- largeMomentarySpike(8) -- if the line failure is caused by
a rate of change of input voltage greater than ten volts per cycle.
- selfTest(9) -- if the UPS was commanded to do a self test.
- rateOfVoltageChange(10) -- if the failure is due to the rate of change of
the line voltage.
|SNMP |input.fail[upsAdvInputLineFailCause]**Preprocessing**:
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |Status |Output voltage |MIB: PowerNet-MIB
The output voltage of the UPS system in VAC.
|SNMP |output.voltage[upsHighPrecOutputVoltage]**Preprocessing**:
- MULTIPLIER: `0.1`
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |Status |Output load |MIB: PowerNet-MIB
The current UPS load expressed as percentage
of rated capacity.
|SNMP |output.load[upsHighPrecOutputLoad]**Preprocessing**:
- MULTIPLIER: `0.1`
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |Status |Output current |MIB: PowerNet-MIB
The current in amperes drawn by the load on the UPS.
|SNMP |output.current[upsHighPrecOutputCurrent]**Preprocessing**:
- MULTIPLIER: `0.1`
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |Status |Output status |MIB: PowerNet-MIB
The current state of the UPS. If the UPS is unable to
determine the state of the UPS this variable is set
to unknown(1).
During self-test most UPSes report onBattery(3) but
some that support it will report onBatteryTest(15).
To determine self-test status across all UPSes, refer
to the upsBasicStateOutputState OID.
|SNMP |output.status[upsBasicOutputStatus]**Preprocessing**:
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |Status |Uptime |MIB: SNMPv2-MIB
The time (in hundredths of a second) since the network management
portion of the system was last re-initialized.
|SNMP |system.uptime[sysUpTime.0]**Preprocessing**:
- MULTIPLIER: `0.01`
| |Status |SNMP agent availability |Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list.
Possible value:
0 - not available
1 - available
2 - unknown
|INTERNAL |zabbix[host,snmp,available]**Preprocessing**:
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |Status |{#PHASEINDEX}: Phase input voltage |MIB: PowerNet-MIB
The input voltage in VAC, or -1 if it's unsupported
by this UPS.
|SNMP |phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}]**Preprocessing**:
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |Status |{#PHASEINDEX}: Phase input current |MIB: PowerNet-MIB
The input current in 0.1 amperes, or -0.1 if it's
unsupported by this UPS.
|SNMP |phase.input.current[upsPhaseInputCurrent.1.1.{#PHASEINDEX}]**Preprocessing**:
- MULTIPLIER: `0.1`
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |Status |{#PHASEINDEX}: Phase output voltage |MIB: PowerNet-MIB
The output voltage in VAC, or -1 if it's unsupported
by this UPS.
|SNMP |phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}]**Preprocessing**:
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |Status |{#PHASEINDEX}: Phase output current |MIB: PowerNet-MIB
The output current in 0.1 amperes drawn
by the load on the UPS, or -1 if it's unsupported
by this UPS.
|SNMP |phase.output.current[upsPhaseOutputCurrent.1.1.{#PHASEINDEX}]**Preprocessing**:
- MULTIPLIER: `0.1`
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |Status |{#PHASEINDEX}: Phase output load, % |MIB: PowerNet-MIB
The percentage of the UPS load capacity in VA at
redundancy @ (n + x) presently being used on this
output phase, or -1 if it's unsupported by this UPS.
|SNMP |phase.output.load.percent[upsPhaseOutputPercentLoad.1.1.{#PHASEINDEX}]**Preprocessing**:
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |Status |{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status |MIB: PowerNet-MIB
The battery cartridge status.
bit 0 Disconnected
bit 1 Overvoltage
bit 2 NeedsReplacement
bit 3 OvertemperatureCritical
bit 4 Charger
bit 5 TemperatureSensor
bit 6 BusSoftStart
bit 7 OvertemperatureWarning
bit 8 GeneralError
bit 9 Communication
bit 10 DisconnectedFrame
bit 11 FirmwareMismatch
|SNMP |battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]**Preprocessing**:
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |Status |{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery temperature |MIB: PowerNet-MIB
The battery pack temperature in Celsius.
|SNMP |battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]**Preprocessing**:
- MULTIPLIER: `0.1`
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |Status |{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery estimated replace date |MIB: PowerNet-MIB
The battery cartridge estimated battery replace date.
|SNMP |battery.estimated_replace_date[upsHighPrecBatteryPackCartridgeReplaceDate.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]**Preprocessing**:
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |Status |{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery pack cartridge health |MIB: PowerNet-MIB
The battery cartridge health.
bit 0 Battery lifetime okay
bit 1 Battery lifetime near end, order replacement cartridge
bit 2 Battery lifetime exceeded, replace battery
bit 3 Battery lifetime near end acknowledged, order replacement cartridge
bit 4 Battery lifetime exceeded acknowledged, replace battery
bit 5 Battery measured lifetime near end, order replacement cartridge
bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge
|SNMP |battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]**Preprocessing**:
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |Status |{#SNMPINDEX}: External battery packs bad |MIB: PowerNet-MIB
The number of external battery packs connected to the UPS that
are defective. If the UPS does not use smart cells then the
agent reports ERROR_NO_SUCH_NAME.
|SNMP |battery.external_packs_bad[upsAdvBatteryNumOfBadBattPacks.{#SNMPINDEX}]**Preprocessing**:
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |Status |{#EXTERNAL_SENSOR1_NAME}: Temperature sensor |MIB: PowerNet-MIB
The sensor's current temperature reading in Celsius.
-1 indicates an invalid reading due to lost communications.
|SNMP |external.sensor.temperature[uioSensorStatusTemperatureDegC.1.{#SNMPINDEX}]**Preprocessing**:
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |Status |{#EXTERNAL_SENSOR1_NAME}: Humidity sensor |MIB: PowerNet-MIB
The sensor's current humidity reading - a relative humidity
percentage. -1 indicates an invalid reading due to either a
sensor that doesn't read humidity or lost communications.
|SNMP |external.sensor.humidity[uioSensorStatusHumidity.1.{#SNMPINDEX}]**Preprocessing**:
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |Status |{#EXTERNAL_SENSOR1_NAME}: Sensor alarm status |MIB: PowerNet-MIB
The alarm status of the sensor. Possible values:
uioNormal (1),
uioWarning (2),
uioCritical (3),
sensorStatusNotApplicable (4)
|SNMP |external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}]**Preprocessing**:
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |Status |{#EXTERNAL_SENSOR2_NAME}: Temperature sensor |MIB: PowerNet-MIB
The sensor's current temperature reading in Celsius.
-1 indicates an invalid reading due to lost communications.
|SNMP |external.sensor.temperature[uioSensorStatusTemperatureDegC.2.{#SNMPINDEX}]**Preprocessing**:
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |Status |{#EXTERNAL_SENSOR2_NAME}: Humidity sensor |MIB: PowerNet-MIB
The sensor's current humidity reading - a relative humidity
percentage. -1 indicates an invalid reading due to either a
sensor that doesn't read humidity or lost communications.
|SNMP |external.sensor.humidity[uioSensorStatusHumidity.2.{#SNMPINDEX}]**Preprocessing**:
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| |Status |{#EXTERNAL_SENSOR2_NAME}: Sensor alarm status |MIB: PowerNet-MIB
The alarm status of the sensor. Possible values:
uioNormal (1),
uioWarning (2),
uioCritical (3),
sensorStatusNotApplicable (4)
|SNMP |external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}]**Preprocessing**:
- DISCARD_UNCHANGED_HEARTBEAT: `6h`
| ## Triggers |Name|Description|Expression|Severity|Dependencies and additional info| |----|-----------|----|----|----| |System name has changed |System name has changed. Ack to close.
|`last(/APC Smart-UPS RT 1000 XL SNMP/system.name[sysName.0],#1)<>last(/APC Smart-UPS RT 1000 XL SNMP/system.name[sysName.0],#2) and length(last(/APC Smart-UPS RT 1000 XL SNMP/system.name[sysName.0]))>0` |INFO |Manual close: YES
| |Battery has an internal error condition |A battery installed has an internal error condition.
|`last(/APC Smart-UPS RT 1000 XL SNMP/battery.status[upsBasicBatteryStatus])=4` |AVERAGE | | |Battery is Low |The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.
|`last(/APC Smart-UPS RT 1000 XL SNMP/battery.status[upsBasicBatteryStatus])=3` |AVERAGE | | |Battery has low capacity |-
|`last(/APC Smart-UPS RT 1000 XL SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}` |HIGH | | |Battery needs replacement |A battery installed has an internal error condition.
|`last(/APC Smart-UPS RT 1000 XL SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2` |HIGH | | |Battery has high temperature |-
|`min(/APC Smart-UPS RT 1000 XL SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | | |Unacceptable input voltage |-
|`min(/APC Smart-UPS RT 1000 XL SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS RT 1000 XL SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS RT 1000 XL SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})` |HIGH | | |Unacceptable input frequency |-
|`min(/APC Smart-UPS RT 1000 XL SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS RT 1000 XL SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC Smart-UPS RT 1000 XL SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})` |HIGH | | |Output load is high |A battery installed has an internal error condition.
|`min(/APC Smart-UPS RT 1000 XL SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}` |HIGH | | |UPS is Timed Sleeping |-
|`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=5` |AVERAGE | | |UPS is Switched Bypass |-
|`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=9` |AVERAGE | | |UPS is Software Bypass |-
|`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=6` |AVERAGE | | |UPS is Sleeping Until Power Return |-
|`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=11` |AVERAGE | | |UPS is Rebooting |-
|`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=8` |AVERAGE | | |UPS is On Smart Trim |-
|`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=12` |AVERAGE | | |UPS is on Smart Boost |-
|`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=4` |AVERAGE | | |UPS is on battery |-
|`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=3` |AVERAGE | | |UPS is Off |-
|`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=7` |AVERAGE | | |UPS is Emergency Static Bypass |-
|`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=16` |AVERAGE | | |UPS is Hardware Failure Bypass |-
|`last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=10` |AVERAGE | | |has been restarted |Uptime is less than 10 minutes.
|`last(/APC Smart-UPS RT 1000 XL SNMP/system.uptime[sysUpTime.0])<10m` |WARNING |Manual close: YES
**Depends on**:
- No SNMP data collection
| |No SNMP data collection |SNMP is not available for polling. Please check device connectivity and SNMP settings.
|`max(/APC Smart-UPS RT 1000 XL SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0` |WARNING | | |{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage |-
|`min(/APC Smart-UPS RT 1000 XL SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS RT 1000 XL SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | | |{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage |-
|`min(/APC Smart-UPS RT 1000 XL SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS RT 1000 XL SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}` |HIGH | | |{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay |The battery cartridge status:
bit 0 Disconnected
bit 1 Overvoltage
bit 2 NeedsReplacement
bit 3 OvertemperatureCritical
bit 4 Charger
bit 5 TemperatureSensor
bit 6 BusSoftStart
bit 7 OvertemperatureWarning
bit 8 GeneralError
bit 9 Communication
bit 10 DisconnectedFrame
bit 11 FirmwareMismatch
|`find(/APC Smart-UPS RT 1000 XL SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0` |WARNING | | |{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature |-
|`min(/APC Smart-UPS RT 1000 XL SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}` |HIGH | | |{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay |The battery cartridge health.
bit 0 Battery lifetime okay
bit 1 Battery lifetime near end, order replacement cartridge
bit 2 Battery lifetime exceeded, replace battery
bit 3 Battery lifetime near end acknowledged, order replacement cartridge
bit 4 Battery lifetime exceeded acknowledged, replace battery
bit 5 Battery measured lifetime near end, order replacement cartridge
bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge
|`find(/APC Smart-UPS RT 1000 XL SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1` |WARNING | | |{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable |The external sensor does not work or is not connected.
|`last(/APC Smart-UPS RT 1000 XL SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4` |INFO | | |{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning |The external sensor has returned a value greater than the warning threshold.
|`last(/APC Smart-UPS RT 1000 XL SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2` |AVERAGE | | |{#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical |The external sensor has returned a value greater than the critical threshold.
|`last(/APC Smart-UPS RT 1000 XL SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=3` |HIGH | | |{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable |The external sensor does not work or is not connected.
|`last(/APC Smart-UPS RT 1000 XL SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=4` |INFO | | |{#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning |The external sensor has returned a value greater than the warning threshold.
|`last(/APC Smart-UPS RT 1000 XL SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=2` |AVERAGE | | |{#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical |The external sensor has returned a value greater than the critical threshold.
|`last(/APC Smart-UPS RT 1000 XL SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=3` |HIGH | | ## Feedback Please report any issues with the template at https://support.zabbix.com You can also provide feedback, discuss the template or ask for help with it at [ZABBIX forums](https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups).