zabbix_export: version: '6.2' date: '2022-04-06T20:01:28Z' groups: - uuid: 3dcd5bbe90534f9e8eb5c2d53756af63 name: Templates/Power templates: - uuid: 32d3c78ff44c4c3c9ff5b893ad7f5fc9 template: 'APC Smart-UPS RT 1000 XL SNMP' name: 'APC Smart-UPS RT 1000 XL SNMP' description: | Template Power APC Smart-UPS RT 1000 XL MIBs used: PowerNet-MIB SNMPv2-MIB You can discuss this template or leave feedback on our forum https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups Template tooling version used: 0.41 groups: - name: Templates/Power items: - uuid: 6ac68411ef214cc7aa49d39d58ce3c6a name: 'Battery capacity' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.3.1.0 key: 'battery.capacity[upsHighPrecBatteryCapacity]' history: 7d value_type: FLOAT units: '%' description: | MIB: PowerNet-MIB The remaining battery capacity expressed as percentage of full capacity. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power triggers: - uuid: b5d618c6090447429191fe4d07e85afa expression: 'last(/APC Smart-UPS RT 1000 XL SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}' name: 'Battery has low capacity' event_name: 'Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%)' opdata: 'Current capacity: {ITEM.LASTVALUE1}' priority: HIGH tags: - tag: scope value: capacity - uuid: 7f3b05afa58142d5b8670c40c196baf8 name: 'External battery packs count' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.2.5.0 key: 'battery.external_packs_count[upsAdvBatteryNumOfBattPacks]' delay: 1h history: 7d description: | MIB: PowerNet-MIB The number of external battery packs connected to the UPS. If the UPS does not use smart cells then the agent reports ERROR_NO_SUCH_NAME. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: inventory - uuid: 87b91005f5ff4ba5b0086e25eaa799bd name: 'Battery last replace date' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.1.3.0 key: 'battery.last_replace_date[upsBasicBatteryLastReplaceDate]' delay: 1h history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB The date when the UPS system's batteries were last replaced in mm/dd/yy (or yyyy) format. For Smart-UPS models, this value is originally set at the factory. When the UPS batteries are replaced, this value should be reset by the administrator. For Symmetra PX 250/500 this OID is read-only and is configurable in the local display only. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: inventory - uuid: 44a33eba233e4bd7ac51ca2dcabf2939 name: 'Battery replace indicator' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.2.4.0 key: 'battery.replace_indicator[upsAdvBatteryReplaceIndicator]' history: 7d description: | MIB: PowerNet-MIB Indicates whether the UPS batteries need replacement. valuemap: name: 'PowerNet-MIB::upsAdvBatteryReplaceIndicator' preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power triggers: - uuid: dc92c19a5b7e43a4b155d6d51912aaf8 expression: 'last(/APC Smart-UPS RT 1000 XL SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2' name: 'Battery needs replacement' priority: HIGH description: 'A battery installed has an internal error condition.' tags: - tag: scope value: notice - uuid: 95749270e6234d6cbd1edb0c5e1118e0 name: 'Battery runtime remaining' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.2.3.0 key: 'battery.runtime_remaining[upsAdvBatteryRunTimeRemaining]' history: 7d value_type: FLOAT units: s description: | MIB: PowerNet-MIB The UPS battery run time remaining before battery exhaustion. preprocessing: - type: MULTIPLIER parameters: - '0.01' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - uuid: 047a5a3a957949d288588eb11f36f25e name: 'Battery status' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.1.1.0 key: 'battery.status[upsBasicBatteryStatus]' history: 7d description: | MIB: PowerNet-MIB The status of the UPS batteries. A batteryLow(3) value indicates the UPS will be unable to sustain the current load, and its services will be lost if power is not restored. The amount of run time in reserve at the time of low battery can be configured by the upsAdvConfigLowBatteryRunTime. A batteryInFaultCondition(4)value indicates that a battery installed has an internal error condition. valuemap: name: 'PowerNet-MIB::upsBasicBatteryStatus' preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: health - tag: component value: power triggers: - uuid: 70c32834ea40487c8f13a55b7ed7c88f expression: 'last(/APC Smart-UPS RT 1000 XL SNMP/battery.status[upsBasicBatteryStatus])=4' name: 'Battery has an internal error condition' priority: AVERAGE description: 'A battery installed has an internal error condition.' tags: - tag: scope value: notice - uuid: e7aeaae896664729b66b42a94f626f9b expression: 'last(/APC Smart-UPS RT 1000 XL SNMP/battery.status[upsBasicBatteryStatus])=3' name: 'Battery is Low' priority: AVERAGE description: 'The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.' tags: - tag: scope value: capacity - uuid: 04cd5e06823846b58ad57e2c358f346e name: 'Battery temperature' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.3.2.0 key: 'battery.temperature[upsHighPrecBatteryTemperature]' history: 7d value_type: FLOAT units: ℃ description: | MIB: PowerNet-MIB The current internal UPS temperature in Celsius. Temperatures below zero read as 0. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: temperature triggers: - uuid: 33695c02cf6141f78e21ca899af10c03 expression: 'min(/APC Smart-UPS RT 1000 XL SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}' name: 'Battery has high temperature' event_name: 'Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD})' opdata: 'Current temperature: {ITEM.LASTVALUE1}' priority: HIGH tags: - tag: scope value: notice - uuid: 8ee98deaf4bf46afb06f694d19757237 name: 'Battery voltage' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.3.4.0 key: 'battery.voltage[upsHighPrecBatteryActualVoltage]' history: 7d value_type: FLOAT units: V description: | MIB: PowerNet-MIB The actual battery bus voltage in Volts. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - uuid: 4cb80c94f3d14674bc7a3933c7571eac name: 'Input fail cause' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.3.2.5.0 key: 'input.fail[upsAdvInputLineFailCause]' history: 7d description: | MIB: PowerNet-MIB The reason for the occurrence of the last transfer to UPS battery power. The variable is set to: - noTransfer(1) -- if there is no transfer yet. - highLineVoltage(2) -- if the transfer to battery is caused by an over voltage greater than the high transfer voltage. - brownout(3) -- if the duration of the outage is greater than five seconds and the line voltage is between 40% of the rated output voltage and the low transfer voltage. - blackout(4) -- if the duration of the outage is greater than five seconds and the line voltage is between 40% of the rated output voltage and ground. - smallMomentarySag(5) -- if the duration of the outage is less than five seconds and the line voltage is between 40% of the rated output voltage and the low transfer voltage. - deepMomentarySag(6) -- if the duration of the outage is less than five seconds and the line voltage is between 40% of the rated output voltage and ground. The variable is set to - smallMomentarySpike(7) -- if the line failure is caused by a rate of change of input voltage less than ten volts per cycle. - largeMomentarySpike(8) -- if the line failure is caused by a rate of change of input voltage greater than ten volts per cycle. - selfTest(9) -- if the UPS was commanded to do a self test. - rateOfVoltageChange(10) -- if the failure is due to the rate of change of the line voltage. valuemap: name: 'PowerNet-MIB::upsAdvInputLineFailCause' preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - uuid: 700a78a4ab3c441496ecafc5ddde6a9d name: 'Input frequency' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.3.3.4.0 key: 'input.frequency[upsHighPrecInputFrequency]' history: 7d value_type: FLOAT units: Hz description: | MIB: PowerNet-MIB The current input frequency to the UPS system in Hz. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power triggers: - uuid: 167de2d832984944878767571b0b5fe4 expression: 'min(/APC Smart-UPS RT 1000 XL SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS RT 1000 XL SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC Smart-UPS RT 1000 XL SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})' name: 'Unacceptable input frequency' event_name: 'Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD})' opdata: 'Current frequency: {ITEM.LASTVALUE1}' priority: HIGH tags: - tag: scope value: notice - uuid: e2b5b824c4704293ad68185971e9fb03 name: 'Input voltage' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.3.3.1.0 key: 'input.voltage[upsHighPrecInputLineVoltage]' history: 7d value_type: FLOAT units: V description: | MIB: PowerNet-MIB The current utility line voltage in VAC. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power triggers: - uuid: b8741bc0081a4a9db2824c9f93ecb399 expression: 'min(/APC Smart-UPS RT 1000 XL SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS RT 1000 XL SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS RT 1000 XL SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})' name: 'Unacceptable input voltage' event_name: 'Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})' opdata: 'Current voltage: {ITEM.LASTVALUE1}' priority: HIGH tags: - tag: scope value: notice - uuid: 861757e4bb1a4dc6ac1c8ef94d973328 name: 'Output current' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.4.3.4.0 key: 'output.current[upsHighPrecOutputCurrent]' history: 7d value_type: FLOAT units: A description: | MIB: PowerNet-MIB The current in amperes drawn by the load on the UPS. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - uuid: 1d9d7ef724ff41eda4fd536df6af93cb name: 'Output load' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.4.3.3.0 key: 'output.load[upsHighPrecOutputLoad]' history: 7d value_type: FLOAT units: '%' description: | MIB: PowerNet-MIB The current UPS load expressed as percentage of rated capacity. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power triggers: - uuid: a4faec3975134cd59e83f1ca7fa3ef7d expression: 'min(/APC Smart-UPS RT 1000 XL SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}' name: 'Output load is high' event_name: 'Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD})' opdata: 'Current load: {ITEM.LASTVALUE1}' priority: HIGH description: 'A battery installed has an internal error condition.' tags: - tag: scope value: notice - uuid: 3edf5e7776ae4cc6aebcedcbf4ab8d78 name: 'Output status' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.4.1.1.0 key: 'output.status[upsBasicOutputStatus]' history: 7d description: | MIB: PowerNet-MIB The current state of the UPS. If the UPS is unable to determine the state of the UPS this variable is set to unknown(1). During self-test most UPSes report onBattery(3) but some that support it will report onBatteryTest(15). To determine self-test status across all UPSes, refer to the upsBasicStateOutputState OID. valuemap: name: 'PowerNet-MIB::upsBasicOutputStatus' preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: health - tag: component value: power triggers: - uuid: deedd977f1ed4b9fbb5cc161dde0c116 expression: 'last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=16' name: 'UPS is Emergency Static Bypass' priority: AVERAGE tags: - tag: scope value: notice - uuid: a7bbe6ca410743919f7c611a6faec9ba expression: 'last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=10' name: 'UPS is Hardware Failure Bypass' priority: AVERAGE tags: - tag: scope value: notice - uuid: 974042a124b945068c6c16c4a01433dc expression: 'last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=7' name: 'UPS is Off' priority: AVERAGE tags: - tag: scope value: notice - uuid: 90e810043e41467b8460278fc7923397 expression: 'last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=3' name: 'UPS is on battery' priority: AVERAGE tags: - tag: scope value: notice - uuid: 656ae233f3a946799c3ed3d48914c0b0 expression: 'last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=4' name: 'UPS is on Smart Boost' priority: AVERAGE tags: - tag: scope value: notice - uuid: 3fcbd14931854831ac603a254ffea0c3 expression: 'last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=12' name: 'UPS is On Smart Trim' priority: AVERAGE tags: - tag: scope value: notice - uuid: 65085178eef54189afdaf4937de49177 expression: 'last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=8' name: 'UPS is Rebooting' priority: AVERAGE tags: - tag: scope value: notice - uuid: 0aa402907ee446c0a13fa086b500fa87 expression: 'last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=11' name: 'UPS is Sleeping Until Power Return' priority: AVERAGE tags: - tag: scope value: notice - uuid: be6cdd1fc22a4f0eacdbce4361cd6788 expression: 'last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=6' name: 'UPS is Software Bypass' priority: AVERAGE tags: - tag: scope value: notice - uuid: b4375fc980ae4bee87531d18ea9a5397 expression: 'last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=9' name: 'UPS is Switched Bypass' priority: AVERAGE tags: - tag: scope value: notice - uuid: 7ae9e31ac32944928065d1cefb2c4e2f expression: 'last(/APC Smart-UPS RT 1000 XL SNMP/output.status[upsBasicOutputStatus])=5' name: 'UPS is Timed Sleeping' priority: AVERAGE tags: - tag: scope value: notice - uuid: bcb28618699448ea8d9d056bad203a0e name: 'Output voltage' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.4.3.1.0 key: 'output.voltage[upsHighPrecOutputVoltage]' history: 7d value_type: FLOAT units: V description: | MIB: PowerNet-MIB The output voltage of the UPS system in VAC. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - uuid: d633cd3273e74209a1b0c6b761028e0a name: 'SNMP traps (fallback)' type: SNMP_TRAP key: snmptrap.fallback history: 2w trends: '0' value_type: LOG description: 'The item is used to collect all SNMP traps unmatched by other snmptrap items' logtimefmt: 'hh:mm:sszyyyy/MM/dd' tags: - tag: component value: network - uuid: 50cc8e7cea0c40948c006623dfa94dae name: 'System contact details' type: SNMP_AGENT snmp_oid: 1.3.6.1.2.1.1.4.0 key: 'system.contact[sysContact.0]' delay: 15m history: 2w trends: '0' value_type: CHAR description: | MIB: SNMPv2-MIB The textual identification of the contact person for this managed node, together with information on how to contact this person. If no contact information is known, the value is the zero-length string. inventory_link: CONTACT preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 12h tags: - tag: component value: system - uuid: e0d638ab398f40e8a9555925cd8ba907 name: 'System description' type: SNMP_AGENT snmp_oid: 1.3.6.1.2.1.1.1.0 key: 'system.descr[sysDescr.0]' delay: 15m history: 2w trends: '0' value_type: CHAR description: | MIB: SNMPv2-MIB A textual description of the entity. This value should include the full name and version identification of the system's hardware type, software operating-system, and networking software. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 12h tags: - tag: component value: system - uuid: 031b9d385cae4641b9ecfb76c4174262 name: 'System location' type: SNMP_AGENT snmp_oid: 1.3.6.1.2.1.1.6.0 key: 'system.location[sysLocation.0]' delay: 15m history: 2w trends: '0' value_type: CHAR description: | MIB: SNMPv2-MIB The physical location of this node (e.g., `telephone closet, 3rd floor'). If the location is unknown, the value is the zero-length string. inventory_link: LOCATION preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: system - uuid: 320221ba30744ca78b8dce03dccd549b name: Model type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.1.1.1.0 key: 'system.model[upsBasicIdentModel]' delay: 15m history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB The UPS model name (e.g. 'APC Smart-UPS 600'). preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: inventory - uuid: e4d9441075954c068b6fd92bbff49cef name: 'System name' type: SNMP_AGENT snmp_oid: 1.3.6.1.2.1.1.5.0 key: 'system.name[sysName.0]' delay: 15m history: 2w trends: '0' value_type: CHAR description: | MIB: SNMPv2-MIB An administratively-assigned name for this managed node.By convention, this is the node's fully-qualified domain name. If the name is unknown, the value is the zero-length string. inventory_link: NAME preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: system triggers: - uuid: 31bb0ff1ea334cd59d9f8b8f489611ef expression: 'last(/APC Smart-UPS RT 1000 XL SNMP/system.name[sysName.0],#1)<>last(/APC Smart-UPS RT 1000 XL SNMP/system.name[sysName.0],#2) and length(last(/APC Smart-UPS RT 1000 XL SNMP/system.name[sysName.0]))>0' name: 'System name has changed' event_name: 'System name has changed (new name: {ITEM.VALUE})' priority: INFO description: 'System name has changed. Ack to close.' manual_close: 'YES' tags: - tag: scope value: notice - tag: scope value: security - uuid: 4e7a9b6aa8dd4371b83bf47f8246cebf name: 'System object ID' type: SNMP_AGENT snmp_oid: 1.3.6.1.2.1.1.2.0 key: 'system.objectid[sysObjectID.0]' delay: 15m history: 2w trends: '0' value_type: CHAR description: | MIB: SNMPv2-MIB The vendor's authoritative identification of the network management subsystem contained in the entity. This value is allocated within the SMI enterprises subtree (1.3.6.1.4.1) and provides an easy and unambiguous means for determining`what kind of box' is being managed. For example, if vendor`Flintstones, Inc.' was assigned the subtree1.3.6.1.4.1.4242, it could assign the identifier 1.3.6.1.4.1.4242.1.1 to its `Fred Router'. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: system - uuid: 9ebb979a5e4a45fd9acf956df034f9be name: 'Serial number' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.1.2.3.0 key: 'system.sn[upsAdvIdentSerialNumber]' delay: 15m history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB An 8-character string identifying the serial number of the UPS internal microprocessor. This number is set at the factory. NOTE: This number does NOT correspond to the serial number on the rear of the UPS. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: inventory - uuid: bbcb555846df4169bc7aead77403e8eb name: Uptime type: SNMP_AGENT snmp_oid: 1.3.6.1.2.1.1.3.0 key: 'system.uptime[sysUpTime.0]' delay: 30s history: 2w trends: 0d units: uptime description: | MIB: SNMPv2-MIB The time (in hundredths of a second) since the network management portion of the system was last re-initialized. preprocessing: - type: MULTIPLIER parameters: - '0.01' tags: - tag: component value: system triggers: - uuid: 860d3beb50c0400283a71c2c4b4ea5e2 expression: 'last(/APC Smart-UPS RT 1000 XL SNMP/system.uptime[sysUpTime.0])<10m' name: 'has been restarted' event_name: '{HOST.NAME} has been restarted (uptime < 10m)' priority: WARNING description: 'Uptime is less than 10 minutes' manual_close: 'YES' dependencies: - name: 'No SNMP data collection' expression: 'max(/APC Smart-UPS RT 1000 XL SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0' tags: - tag: scope value: notice - uuid: f24fc7ed9ffa4884891a01a0f1565fc4 name: 'SNMP agent availability' type: INTERNAL key: 'zabbix[host,snmp,available]' history: 7d description: | Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list. Possible value: 0 - not available 1 - available 2 - unknown valuemap: name: zabbix.host.available preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: health - tag: component value: network triggers: - uuid: 21fc3a198f3b423fa14676278f53a4be expression: 'max(/APC Smart-UPS RT 1000 XL SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0' name: 'No SNMP data collection' opdata: 'Current state: {ITEM.LASTVALUE1}' priority: WARNING description: 'SNMP is not available for polling. Please check device connectivity and SNMP settings.' tags: - tag: scope value: availability discovery_rules: - uuid: 9389b159502e4242b02a11104124bae5 name: 'External bad battery packs discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#EXTERNAL_PACKS},1.3.6.1.4.1.318.1.1.1.2.2.6]' key: battery.packs.bad.discovery delay: 1h description: 'Discovery of the number of external defective battery packs.' item_prototypes: - uuid: 202a5c9f91c64011a915157a07245a6d name: '{#SNMPINDEX}: External battery packs bad' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.2.6.0 key: 'battery.external_packs_bad[upsAdvBatteryNumOfBadBattPacks.{#SNMPINDEX}]' delay: 15m history: 7d description: | MIB: PowerNet-MIB The number of external battery packs connected to the UPS that are defective. If the UPS does not use smart cells then the agent reports ERROR_NO_SUCH_NAME. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: inventory - uuid: ec66331f2ae64801a3ef51d6dec5a00f name: 'External battery packs discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#CARTRIDGE_STATUS},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.7,{#BATTERY_PACK},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.1,{#CARTRIDGE_INDEX},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.2]' key: battery.packs.discovery delay: 1h filter: evaltype: AND conditions: - macro: '{#CARTRIDGE_STATUS}' value: ^$ operator: NOT_MATCHES_REGEX formulaid: A item_prototypes: - uuid: 8d1574f1c1d442529509580309153564 name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery estimated replace date' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.8.{#SNMPINDEX}' key: 'battery.estimated_replace_date[upsHighPrecBatteryPackCartridgeReplaceDate.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]' delay: 1h history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB The battery cartridge estimated battery replace date. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: inventory - tag: component value: power - uuid: 3c829e3adec64fb39334dbacc03a3229 name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery pack cartridge health' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.7.{#SNMPINDEX}' key: 'battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]' history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB The battery cartridge health. bit 0 Battery lifetime okay bit 1 Battery lifetime near end, order replacement cartridge bit 2 Battery lifetime exceeded, replace battery bit 3 Battery lifetime near end acknowledged, order replacement cartridge bit 4 Battery lifetime exceeded acknowledged, replace battery bit 5 Battery measured lifetime near end, order replacement cartridge bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: health - tag: component value: power trigger_prototypes: - uuid: c353d8e0b0584c6c8ba81514f5c66995 expression: 'find(/APC Smart-UPS RT 1000 XL SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1' name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay' opdata: 'Current bit set: {ITEM.LASTVALUE1}' priority: WARNING description: | The battery cartridge health. bit 0 Battery lifetime okay bit 1 Battery lifetime near end, order replacement cartridge bit 2 Battery lifetime exceeded, replace battery bit 3 Battery lifetime near end acknowledged, order replacement cartridge bit 4 Battery lifetime exceeded acknowledged, replace battery bit 5 Battery measured lifetime near end, order replacement cartridge bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge tags: - tag: scope value: notice - uuid: 15f52cb076cb414fb794113e9981fdde name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.10.{#SNMPINDEX}' key: 'battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]' history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB The battery cartridge status. bit 0 Disconnected bit 1 Overvoltage bit 2 NeedsReplacement bit 3 OvertemperatureCritical bit 4 Charger bit 5 TemperatureSensor bit 6 BusSoftStart bit 7 OvertemperatureWarning bit 8 GeneralError bit 9 Communication bit 10 DisconnectedFrame bit 11 FirmwareMismatch preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: health - tag: component value: power trigger_prototypes: - uuid: 26535b11c27b4fbe92285b56cbbf5a73 expression: 'find(/APC Smart-UPS RT 1000 XL SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0' name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay' opdata: 'Current bit set: {ITEM.LASTVALUE1}' priority: WARNING description: | The battery cartridge status: bit 0 Disconnected bit 1 Overvoltage bit 2 NeedsReplacement bit 3 OvertemperatureCritical bit 4 Charger bit 5 TemperatureSensor bit 6 BusSoftStart bit 7 OvertemperatureWarning bit 8 GeneralError bit 9 Communication bit 10 DisconnectedFrame bit 11 FirmwareMismatch tags: - tag: scope value: notice - uuid: e0d8f68302264c1b9420284f3e3a0272 name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery temperature' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.5.{#SNMPINDEX}' key: 'battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]' history: 7d value_type: FLOAT units: ℃ description: | MIB: PowerNet-MIB The battery pack temperature in Celsius. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: temperature trigger_prototypes: - uuid: 7f8613d752524d588e60aa1cab2c60bd expression: 'min(/APC Smart-UPS RT 1000 XL SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}' name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature' event_name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD})' opdata: 'Current temperature: {ITEM.LASTVALUE1}' priority: HIGH tags: - tag: scope value: notice - uuid: bca352c952174256b9cfbcffb86fbf90 name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Serial number' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.4.{#SNMPINDEX}' key: 'system.sn[upsHighPrecBatteryPackSerialNumber.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]' delay: 15m history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB The battery pack serial number. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: inventory - uuid: 19379361227740c3bf8bc9852886538d name: 'External sensor port 1 discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#EXTERNAL_SENSOR1_NAME},1.3.6.1.4.1.318.1.1.25.1.2.1.3]' key: external.sensor1.discovery delay: 1h description: uioSensorStatusTable item_prototypes: - uuid: d9c8acbf3a90411582404c9d5cfa9f70 name: '{#EXTERNAL_SENSOR1_NAME}: Humidity sensor' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.1.7.1.1 key: 'external.sensor.humidity[uioSensorStatusHumidity.1.{#SNMPINDEX}]' history: 7d value_type: FLOAT units: '%' description: | MIB: PowerNet-MIB The sensor's current humidity reading - a relative humidity percentage. -1 indicates an invalid reading due to either a sensor that doesn't read humidity or lost communications. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: humidity - tag: component value: power - uuid: 1a475822bc324bbf8c4aa15c34734270 name: '{#EXTERNAL_SENSOR1_NAME}: Sensor alarm status' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.1.9.1.1 key: 'external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}]' history: 7d description: | MIB: PowerNet-MIB The alarm status of the sensor. Possible values: uioNormal (1), uioWarning (2), uioCritical (3), sensorStatusNotApplicable (4) valuemap: name: 'PowerNet-MIB::uioSensorStatusAlarmStatus' preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: health - tag: component value: power trigger_prototypes: - uuid: 40e22c5379f34edf87d1ea52ffae60b8 expression: 'last(/APC Smart-UPS RT 1000 XL SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=3' name: '{#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical' priority: HIGH description: 'The external sensor has returned a value greater than the critical threshold.' tags: - tag: scope value: notice - uuid: a482de04a5d34807874fc7a7c506dd40 expression: 'last(/APC Smart-UPS RT 1000 XL SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4' name: '{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable' priority: INFO description: 'The external sensor does not work or is not connected.' tags: - tag: scope value: notice - uuid: dca875c511b04dc1857de74223c4f27b expression: 'last(/APC Smart-UPS RT 1000 XL SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2' name: '{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning' priority: AVERAGE description: 'The external sensor has returned a value greater than the warning threshold.' tags: - tag: scope value: notice - uuid: 6d1005b2b6ad41369174d93b1ebe1959 name: '{#EXTERNAL_SENSOR1_NAME}: Temperature sensor' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.1.6.1.1 key: 'external.sensor.temperature[uioSensorStatusTemperatureDegC.1.{#SNMPINDEX}]' history: 7d value_type: FLOAT units: ℃ description: | MIB: PowerNet-MIB The sensor's current temperature reading in Celsius. -1 indicates an invalid reading due to lost communications. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - tag: component value: temperature overrides: - name: Temp step: '1' filter: conditions: - macro: '{#EXTERNAL_SENSOR1_NAME}' value: Temp formulaid: A operations: - operationobject: ITEM_PROTOTYPE operator: LIKE value: Humidity status: ENABLED discover: NO_DISCOVER - uuid: c4df3e0e0eba4585bdd01358f9d7f5d9 name: 'External sensor port 2 discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#EXTERNAL_SENSOR2_NAME},1.3.6.1.4.1.318.1.1.25.1.2.2.3]' key: external.sensor2.discovery delay: 1h description: uioSensorStatusTable item_prototypes: - uuid: 7d08e2a5df41454f863f5b50a911f819 name: '{#EXTERNAL_SENSOR2_NAME}: Humidity sensor' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.2.7.1.1 key: 'external.sensor.humidity[uioSensorStatusHumidity.2.{#SNMPINDEX}]' history: 7d value_type: FLOAT units: '%' description: | MIB: PowerNet-MIB The sensor's current humidity reading - a relative humidity percentage. -1 indicates an invalid reading due to either a sensor that doesn't read humidity or lost communications. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: humidity - tag: component value: power - uuid: 4774fd152aab49de9064490cf7ec1d0a name: '{#EXTERNAL_SENSOR2_NAME}: Sensor alarm status' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.2.9.1.1 key: 'external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}]' history: 7d description: | MIB: PowerNet-MIB The alarm status of the sensor. Possible values: uioNormal (1), uioWarning (2), uioCritical (3), sensorStatusNotApplicable (4) valuemap: name: 'PowerNet-MIB::uioSensorStatusAlarmStatus' preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: health - tag: component value: power trigger_prototypes: - uuid: 650a1d16e56c45188c6246e960d62857 expression: 'last(/APC Smart-UPS RT 1000 XL SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=3' name: '{#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical' priority: HIGH description: 'The external sensor has returned a value greater than the critical threshold.' tags: - tag: scope value: notice - uuid: 7518ae06e3a14866b9e6d90a224055f7 expression: 'last(/APC Smart-UPS RT 1000 XL SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=4' name: '{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable' priority: INFO description: 'The external sensor does not work or is not connected.' tags: - tag: scope value: notice - uuid: 65aa8a5380f141498dd9c718972110b3 expression: 'last(/APC Smart-UPS RT 1000 XL SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=2' name: '{#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning' priority: AVERAGE description: 'The external sensor has returned a value greater than the warning threshold.' tags: - tag: scope value: notice - uuid: d94425f2025045459af40e8fcb72734e name: '{#EXTERNAL_SENSOR2_NAME}: Temperature sensor' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.2.6.1.1 key: 'external.sensor.temperature[uioSensorStatusTemperatureDegC.2.{#SNMPINDEX}]' history: 7d value_type: FLOAT units: ℃ description: | MIB: PowerNet-MIB The sensor's current temperature reading in Celsius. -1 indicates an invalid reading due to lost communications. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - tag: component value: temperature overrides: - name: Temp step: '1' filter: conditions: - macro: '{#EXTERNAL_SENSOR2_NAME}' value: Temp formulaid: A operations: - operationobject: ITEM_PROTOTYPE operator: LIKE value: Humidity status: ENABLED discover: NO_DISCOVER - uuid: 68610f5b6df44229bcb0ad4b0fa1c3f8 name: 'Input phases discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#PHASEINDEX},1.3.6.1.4.1.318.1.1.1.9.2.3.1.2.1.1]' key: input.phases.discovery delay: 1h description: 'The input phase identifier. OID upsPhaseInputPhaseIndex.1.1' item_prototypes: - uuid: d17e9bb868b143dca508c4f79092cd6e name: '{#PHASEINDEX}: Phase input current' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.9.2.3.1.6.1.1.{#PHASEINDEX}' key: 'phase.input.current[upsPhaseInputCurrent.1.1.{#PHASEINDEX}]' history: 7d value_type: FLOAT units: A description: | MIB: PowerNet-MIB The input current in 0.1 amperes, or -0.1 if it's unsupported by this UPS. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - uuid: cf03abf328754a4082017f480051292f name: '{#PHASEINDEX}: Phase input voltage' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.9.2.3.1.3.1.1.{#PHASEINDEX}' key: 'phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}]' history: 7d value_type: FLOAT units: V description: | MIB: PowerNet-MIB The input voltage in VAC, or -1 if it's unsupported by this UPS. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power trigger_prototypes: - uuid: 8c9226411afb4b32ba3e9d6232ff4710 expression: 'min(/APC Smart-UPS RT 1000 XL SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS RT 1000 XL SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}' name: '{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage' event_name: '{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})' opdata: 'Current phase {#PHASEINDEX} voltage: {ITEM.LASTVALUE1}' priority: HIGH tags: - tag: scope value: notice - uuid: a7b39188df294ec182c3e1f2a2417154 name: 'Output phases discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#PHASEINDEX},1.3.6.1.4.1.318.1.1.1.9.3.3.1.2.1.1]' key: output.phases.discovery delay: 1h description: 'The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1' item_prototypes: - uuid: 638c63c2f4ad4cad8ed71a796d78705b name: '{#PHASEINDEX}: Phase output current' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.9.3.3.1.4.1.1.{#PHASEINDEX}' key: 'phase.output.current[upsPhaseOutputCurrent.1.1.{#PHASEINDEX}]' history: 7d value_type: FLOAT units: A description: | MIB: PowerNet-MIB The output current in 0.1 amperes drawn by the load on the UPS, or -1 if it's unsupported by this UPS. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - uuid: ba4a2ae8abea4e2692b9a43231783648 name: '{#PHASEINDEX}: Phase output load, %' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.9.3.3.1.10.1.1.{#PHASEINDEX}' key: 'phase.output.load.percent[upsPhaseOutputPercentLoad.1.1.{#PHASEINDEX}]' history: 7d value_type: FLOAT units: '%' description: | MIB: PowerNet-MIB The percentage of the UPS load capacity in VA at redundancy @ (n + x) presently being used on this output phase, or -1 if it's unsupported by this UPS. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - uuid: 4e22c7f6d7e14b20b3720e082042fd4f name: '{#PHASEINDEX}: Phase output voltage' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.9.3.3.1.3.1.1.{#PHASEINDEX}' key: 'phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}]' history: 7d value_type: FLOAT units: V description: | MIB: PowerNet-MIB The output voltage in VAC, or -1 if it's unsupported by this UPS. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power trigger_prototypes: - uuid: 58e0697a9a9147a4b1dfda251f2b593e expression: 'min(/APC Smart-UPS RT 1000 XL SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS RT 1000 XL SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}' name: '{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage' event_name: '{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})' opdata: 'Current phase {#PHASEINDEX} voltage: {ITEM.LASTVALUE1}' priority: HIGH tags: - tag: scope value: notice tags: - tag: class value: power - tag: target value: apc - tag: target value: apc-smart-ups-rt-1000-xl macros: - macro: '{$BATTERY.CAPACITY.MIN.WARN}' value: '50' description: 'Minimum battery capacity percentage for trigger expression.' - macro: '{$BATTERY.TEMP.MAX.WARN}' value: '55' description: 'Maximum battery temperature for trigger expression.' - macro: '{$SNMP.TIMEOUT}' value: 5m description: 'The time interval for SNMP agent availability trigger expression.' - macro: '{$TIME.PERIOD}' value: 15m description: 'Time period for trigger expression.' - macro: '{$UPS.INPUT_FREQ.MAX.WARN}' value: '50.3' description: 'Maximum input frequency for trigger expression.' - macro: '{$UPS.INPUT_FREQ.MIN.WARN}' value: '49.7' description: 'Minimum input frequency for trigger expression.' - macro: '{$UPS.INPUT_VOLT.MAX.WARN}' value: '243' description: 'Maximum input voltage for trigger expression.' - macro: '{$UPS.INPUT_VOLT.MIN.WARN}' value: '197' description: 'Minimum input voltage for trigger expression.' - macro: '{$UPS.OUTPUT.MAX.WARN}' value: '80' description: 'Maximum output load in % for trigger expression.' dashboards: - uuid: 8e5f02a3eab44a5f85011b7331696284 name: 'UPS Summary' pages: - widgets: - type: PLAIN_TEXT width: '8' fields: - type: INTEGER name: show_as_html value: '0' - type: INTEGER name: show_lines value: '1' - type: ITEM name: itemids value: key: 'system.uptime[sysUpTime.0]' host: 'APC Smart-UPS RT 1000 XL SNMP' - type: PLAIN_TEXT x: '8' width: '8' fields: - type: INTEGER name: show_as_html value: '0' - type: INTEGER name: show_lines value: '1' - type: ITEM name: itemids value: key: 'input.fail[upsAdvInputLineFailCause]' host: 'APC Smart-UPS RT 1000 XL SNMP' - type: PLAIN_TEXT x: '16' width: '8' fields: - type: INTEGER name: show_as_html value: '0' - type: INTEGER name: show_lines value: '1' - type: ITEM name: itemids value: key: 'output.status[upsBasicOutputStatus]' host: 'APC Smart-UPS RT 1000 XL SNMP' - type: PLAIN_TEXT 'y': '2' width: '8' fields: - type: INTEGER name: show_as_html value: '0' - type: INTEGER name: show_lines value: '1' - type: ITEM name: itemids value: key: 'battery.status[upsBasicBatteryStatus]' host: 'APC Smart-UPS RT 1000 XL SNMP' - type: PLAIN_TEXT x: '8' 'y': '2' width: '8' fields: - type: INTEGER name: show_as_html value: '0' - type: INTEGER name: show_lines value: '1' - type: ITEM name: itemids value: key: 'battery.runtime_remaining[upsAdvBatteryRunTimeRemaining]' host: 'APC Smart-UPS RT 1000 XL SNMP' - type: PLAIN_TEXT x: '16' 'y': '2' width: '8' fields: - type: INTEGER name: show_as_html value: '0' - type: INTEGER name: show_lines value: '1' - type: ITEM name: itemids value: key: 'battery.last_replace_date[upsBasicBatteryLastReplaceDate]' host: 'APC Smart-UPS RT 1000 XL SNMP' - type: GRAPH_CLASSIC 'y': '4' width: '8' height: '7' fields: - type: INTEGER name: source_type value: '0' - type: GRAPH name: graphid value: name: 'Capacity of the UPS batteries' host: 'APC Smart-UPS RT 1000 XL SNMP' - type: GRAPH_CLASSIC x: '8' 'y': '4' width: '8' height: '7' fields: - type: INTEGER name: source_type value: '0' - type: GRAPH name: graphid value: name: Voltage host: 'APC Smart-UPS RT 1000 XL SNMP' - type: GRAPH_CLASSIC x: '16' 'y': '4' width: '8' height: '7' fields: - type: INTEGER name: source_type value: '0' - type: GRAPH name: graphid value: name: Output host: 'APC Smart-UPS RT 1000 XL SNMP' valuemaps: - uuid: b2af1e2dcb874d43949c383f9b347f36 name: 'PowerNet-MIB::uioSensorStatusAlarmStatus' mappings: - value: '1' newvalue: Normal - value: '2' newvalue: Warning - value: '3' newvalue: Critical - value: '4' newvalue: 'Not applicable' - uuid: b06b54b07e6840e5a0c52ba7a6acf86a name: 'PowerNet-MIB::upsAdvBatteryReplaceIndicator' mappings: - value: '1' newvalue: 'no Battery Needs Replacing' - value: '2' newvalue: 'battery Needs Replacing' - uuid: a62f96735c47467da94b6bcf98cc013d name: 'PowerNet-MIB::upsAdvInputLineFailCause' mappings: - value: '1' newvalue: 'no Transfer' - value: '2' newvalue: 'High Line Voltage' - value: '3' newvalue: Brownout - value: '4' newvalue: Blackout - value: '5' newvalue: 'Small Momentary Sag' - value: '6' newvalue: 'Deep Momentary Sag' - value: '7' newvalue: 'Small Momentary Spike' - value: '8' newvalue: 'Large Momentary Spike' - value: '9' newvalue: 'Self Test' - value: '10' newvalue: 'Rate of Voltage Change' - uuid: ed12e8780c384caba8035fbb1c78e115 name: 'PowerNet-MIB::upsBasicBatteryStatus' mappings: - value: '1' newvalue: Unknown - value: '2' newvalue: Normal - value: '3' newvalue: Low - value: '4' newvalue: 'In Fault Condition' - uuid: ae2ed0c2c99a4ad496f7a35226e3d4f0 name: 'PowerNet-MIB::upsBasicOutputStatus' mappings: - value: '1' newvalue: Unknown - value: '2' newvalue: Online - value: '3' newvalue: 'On Battery' - value: '4' newvalue: 'On Smart Boost' - value: '5' newvalue: 'Timed Sleeping' - value: '6' newvalue: 'Software Bypass' - value: '7' newvalue: 'Off' - value: '8' newvalue: Rebooting - value: '9' newvalue: 'Switched Bypass' - value: '10' newvalue: 'Hardware Failure Bypass' - value: '11' newvalue: 'Sleeping Until Power Return' - value: '12' newvalue: 'On Smart Trim' - value: '13' newvalue: 'Eco Mode' - value: '14' newvalue: 'Hot Standby' - value: '15' newvalue: 'On Battery Test' - value: '16' newvalue: 'Emergency Static Bypass' - value: '17' newvalue: 'Static Bypass Standby' - value: '18' newvalue: 'Power Saving Mode' - value: '19' newvalue: 'Spot Mode' - value: '20' newvalue: E-Conversion - value: '21' newvalue: 'Charger Spotmode' - value: '22' newvalue: 'Inverter Spotmode' - value: '23' newvalue: 'Active Load' - value: '24' newvalue: 'Battery Discharge Spotmode' - value: '25' newvalue: 'Inverter Standby' - value: '26' newvalue: 'Charger Only' - uuid: 8cddc4f99ecb4866b1638b82b145ea8b name: zabbix.host.available mappings: - value: '0' newvalue: 'not available' - value: '1' newvalue: available - value: '2' newvalue: unknown graphs: - uuid: a0d8e0338b8d4fd2bd6fdf537373d63c name: 'Capacity of the UPS batteries' type: PIE graph_items: - color: 1A7C11 item: host: 'APC Smart-UPS RT 1000 XL SNMP' key: 'battery.capacity[upsHighPrecBatteryCapacity]' - uuid: 0817d2550d9642fe95ce182dce5cefd8 name: Output graph_items: - color: 1A7C11 item: host: 'APC Smart-UPS RT 1000 XL SNMP' key: 'output.current[upsHighPrecOutputCurrent]' - sortorder: '1' color: 2774A4 item: host: 'APC Smart-UPS RT 1000 XL SNMP' key: 'output.load[upsHighPrecOutputLoad]' - uuid: ce2f4070e7a14d8283d0a8aff0fcd5e6 name: Voltage graph_items: - color: 1A7C11 item: host: 'APC Smart-UPS RT 1000 XL SNMP' key: 'input.voltage[upsHighPrecInputLineVoltage]' - sortorder: '1' color: 2774A4 item: host: 'APC Smart-UPS RT 1000 XL SNMP' key: 'output.voltage[upsHighPrecOutputVoltage]'