zabbix_export: version: '6.2' date: '2022-04-06T20:01:30Z' groups: - uuid: 3dcd5bbe90534f9e8eb5c2d53756af63 name: Templates/Power templates: - uuid: 8ec76aeb703747a5affdf435bc12f572 template: 'APC Smart-UPS SRT 5000 SNMP' name: 'APC Smart-UPS SRT 5000 SNMP' description: | Template Power APC Smart-UPS SRT 5000 MIBs used: PowerNet-MIB SNMPv2-MIB You can discuss this template or leave feedback on our forum https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups Template tooling version used: 0.41 groups: - name: Templates/Power items: - uuid: f5ca8610803e4aca8c6c3c8f6044ca43 name: 'Battery capacity' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.3.1.0 key: 'battery.capacity[upsHighPrecBatteryCapacity]' history: 7d value_type: FLOAT units: '%' description: | MIB: PowerNet-MIB The remaining battery capacity expressed as percentage of full capacity. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power triggers: - uuid: 0103da3d5f414d8ba1e9914d5c8d5f76 expression: 'last(/APC Smart-UPS SRT 5000 SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}' name: 'Battery has low capacity' event_name: 'Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%)' opdata: 'Current capacity: {ITEM.LASTVALUE1}' priority: HIGH tags: - tag: scope value: capacity - uuid: 7652aff14f644896be902fe18f3bb46a name: 'External battery packs count' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.2.5.0 key: 'battery.external_packs_count[upsAdvBatteryNumOfBattPacks]' delay: 1h history: 7d description: | MIB: PowerNet-MIB The number of external battery packs connected to the UPS. If the UPS does not use smart cells then the agent reports ERROR_NO_SUCH_NAME. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: inventory - uuid: ee059b1bb6ac486c8c5dd29654899d71 name: 'Battery last replace date' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.1.3.0 key: 'battery.last_replace_date[upsBasicBatteryLastReplaceDate]' delay: 1h history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB The date when the UPS system's batteries were last replaced in mm/dd/yy (or yyyy) format. For Smart-UPS models, this value is originally set at the factory. When the UPS batteries are replaced, this value should be reset by the administrator. For Symmetra PX 250/500 this OID is read-only and is configurable in the local display only. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: inventory - uuid: f4d790f93a1c4e75a7ebd3d89d0d9d90 name: 'Battery replace indicator' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.2.4.0 key: 'battery.replace_indicator[upsAdvBatteryReplaceIndicator]' history: 7d description: | MIB: PowerNet-MIB Indicates whether the UPS batteries need replacement. valuemap: name: 'PowerNet-MIB::upsAdvBatteryReplaceIndicator' preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power triggers: - uuid: 09573345f6ce4d648f56117c8755e368 expression: 'last(/APC Smart-UPS SRT 5000 SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2' name: 'Battery needs replacement' priority: HIGH description: 'A battery installed has an internal error condition.' tags: - tag: scope value: notice - uuid: 6aacf5a02a824b9d8b3c2676b126b186 name: 'Battery runtime remaining' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.2.3.0 key: 'battery.runtime_remaining[upsAdvBatteryRunTimeRemaining]' history: 7d value_type: FLOAT units: s description: | MIB: PowerNet-MIB The UPS battery run time remaining before battery exhaustion. preprocessing: - type: MULTIPLIER parameters: - '0.01' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - uuid: aebc8b49a97243038b97855c5d20edb7 name: 'Battery status' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.1.1.0 key: 'battery.status[upsBasicBatteryStatus]' history: 7d description: | MIB: PowerNet-MIB The status of the UPS batteries. A batteryLow(3) value indicates the UPS will be unable to sustain the current load, and its services will be lost if power is not restored. The amount of run time in reserve at the time of low battery can be configured by the upsAdvConfigLowBatteryRunTime. A batteryInFaultCondition(4)value indicates that a battery installed has an internal error condition. valuemap: name: 'PowerNet-MIB::upsBasicBatteryStatus' preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: health - tag: component value: power triggers: - uuid: 743aef1e53ee464da48d2953ddc3b85c expression: 'last(/APC Smart-UPS SRT 5000 SNMP/battery.status[upsBasicBatteryStatus])=4' name: 'Battery has an internal error condition' priority: AVERAGE description: 'A battery installed has an internal error condition.' tags: - tag: scope value: notice - uuid: d648d686ff994625bd17f959c311fddd expression: 'last(/APC Smart-UPS SRT 5000 SNMP/battery.status[upsBasicBatteryStatus])=3' name: 'Battery is Low' priority: AVERAGE description: 'The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.' tags: - tag: scope value: capacity - uuid: 48552e466ee54883ae3cbfd5e549ffc5 name: 'Battery temperature' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.3.2.0 key: 'battery.temperature[upsHighPrecBatteryTemperature]' history: 7d value_type: FLOAT units: ℃ description: | MIB: PowerNet-MIB The current internal UPS temperature in Celsius. Temperatures below zero read as 0. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: temperature triggers: - uuid: e47ba98e74c94bd3886ac65cd1075359 expression: 'min(/APC Smart-UPS SRT 5000 SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}' name: 'Battery has high temperature' event_name: 'Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD})' opdata: 'Current temperature: {ITEM.LASTVALUE1}' priority: HIGH tags: - tag: scope value: notice - uuid: 560031163d54444cb5ead172e9e238d2 name: 'Battery voltage' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.3.4.0 key: 'battery.voltage[upsHighPrecBatteryActualVoltage]' history: 7d value_type: FLOAT units: V description: | MIB: PowerNet-MIB The actual battery bus voltage in Volts. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - uuid: 09f34437ff2e422bb62d7ba44b05657c name: 'Input fail cause' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.3.2.5.0 key: 'input.fail[upsAdvInputLineFailCause]' history: 7d description: | MIB: PowerNet-MIB The reason for the occurrence of the last transfer to UPS battery power. The variable is set to: - noTransfer(1) -- if there is no transfer yet. - highLineVoltage(2) -- if the transfer to battery is caused by an over voltage greater than the high transfer voltage. - brownout(3) -- if the duration of the outage is greater than five seconds and the line voltage is between 40% of the rated output voltage and the low transfer voltage. - blackout(4) -- if the duration of the outage is greater than five seconds and the line voltage is between 40% of the rated output voltage and ground. - smallMomentarySag(5) -- if the duration of the outage is less than five seconds and the line voltage is between 40% of the rated output voltage and the low transfer voltage. - deepMomentarySag(6) -- if the duration of the outage is less than five seconds and the line voltage is between 40% of the rated output voltage and ground. The variable is set to - smallMomentarySpike(7) -- if the line failure is caused by a rate of change of input voltage less than ten volts per cycle. - largeMomentarySpike(8) -- if the line failure is caused by a rate of change of input voltage greater than ten volts per cycle. - selfTest(9) -- if the UPS was commanded to do a self test. - rateOfVoltageChange(10) -- if the failure is due to the rate of change of the line voltage. valuemap: name: 'PowerNet-MIB::upsAdvInputLineFailCause' preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - uuid: fb816e1a6ff640d69a5465e78febc03e name: 'Input frequency' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.3.3.4.0 key: 'input.frequency[upsHighPrecInputFrequency]' history: 7d value_type: FLOAT units: Hz description: | MIB: PowerNet-MIB The current input frequency to the UPS system in Hz. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power triggers: - uuid: 3fa853edcebe42eba858e45f1a4465ee expression: 'min(/APC Smart-UPS SRT 5000 SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS SRT 5000 SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC Smart-UPS SRT 5000 SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})' name: 'Unacceptable input frequency' event_name: 'Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD})' opdata: 'Current frequency: {ITEM.LASTVALUE1}' priority: HIGH tags: - tag: scope value: notice - uuid: 65acc805ec7f4a2883d28f51b32054cc name: 'Input voltage' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.3.3.1.0 key: 'input.voltage[upsHighPrecInputLineVoltage]' history: 7d value_type: FLOAT units: V description: | MIB: PowerNet-MIB The current utility line voltage in VAC. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power triggers: - uuid: 74b42439050b48b6bf41abb5bb39808b expression: 'min(/APC Smart-UPS SRT 5000 SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS SRT 5000 SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS SRT 5000 SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})' name: 'Unacceptable input voltage' event_name: 'Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})' opdata: 'Current voltage: {ITEM.LASTVALUE1}' priority: HIGH tags: - tag: scope value: notice - uuid: b0d66c706be8457cbf794171253dd927 name: 'Output current' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.4.3.4.0 key: 'output.current[upsHighPrecOutputCurrent]' history: 7d value_type: FLOAT units: A description: | MIB: PowerNet-MIB The current in amperes drawn by the load on the UPS. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - uuid: 5427a9b46ea54920b3fcc7d8ca413e0e name: 'Output load' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.4.3.3.0 key: 'output.load[upsHighPrecOutputLoad]' history: 7d value_type: FLOAT units: '%' description: | MIB: PowerNet-MIB The current UPS load expressed as percentage of rated capacity. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power triggers: - uuid: e099efa7266f44008819979830147665 expression: 'min(/APC Smart-UPS SRT 5000 SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}' name: 'Output load is high' event_name: 'Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD})' opdata: 'Current load: {ITEM.LASTVALUE1}' priority: HIGH description: 'A battery installed has an internal error condition.' tags: - tag: scope value: notice - uuid: c87c096a38284b82bb0fd8c9dfe871ef name: 'Output status' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.4.1.1.0 key: 'output.status[upsBasicOutputStatus]' history: 7d description: | MIB: PowerNet-MIB The current state of the UPS. If the UPS is unable to determine the state of the UPS this variable is set to unknown(1). During self-test most UPSes report onBattery(3) but some that support it will report onBatteryTest(15). To determine self-test status across all UPSes, refer to the upsBasicStateOutputState OID. valuemap: name: 'PowerNet-MIB::upsBasicOutputStatus' preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: health - tag: component value: power triggers: - uuid: edcc1dc962fa4a228b2f5cd3617efbc6 expression: 'last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=16' name: 'UPS is Emergency Static Bypass' priority: AVERAGE tags: - tag: scope value: notice - uuid: 869fed8cdd5a4f369e3b1ff2474280de expression: 'last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=10' name: 'UPS is Hardware Failure Bypass' priority: AVERAGE tags: - tag: scope value: notice - uuid: 378a246b34454d73b2248757be60a7ea expression: 'last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=7' name: 'UPS is Off' priority: AVERAGE tags: - tag: scope value: notice - uuid: 286dc25a245f45c3bdcc64925b41aef6 expression: 'last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=3' name: 'UPS is on battery' priority: AVERAGE tags: - tag: scope value: notice - uuid: 4d02a4c4f25a4efda7bd30def8364972 expression: 'last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=4' name: 'UPS is on Smart Boost' priority: AVERAGE tags: - tag: scope value: notice - uuid: ae91f99b089748cdaeb0185e31ffe82e expression: 'last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=12' name: 'UPS is On Smart Trim' priority: AVERAGE tags: - tag: scope value: notice - uuid: 0bb0ef56d82e4c2a9414468c61fb3a96 expression: 'last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=8' name: 'UPS is Rebooting' priority: AVERAGE tags: - tag: scope value: notice - uuid: 6a5a7e4b17384131a337619ec4a9c1e6 expression: 'last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=11' name: 'UPS is Sleeping Until Power Return' priority: AVERAGE tags: - tag: scope value: notice - uuid: 232c98b7ca654c91a20d52ce6f21d7a1 expression: 'last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=6' name: 'UPS is Software Bypass' priority: AVERAGE tags: - tag: scope value: notice - uuid: 65b8d109db8d4448a7ead131581fcbbe expression: 'last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=9' name: 'UPS is Switched Bypass' priority: AVERAGE tags: - tag: scope value: notice - uuid: 917c1f3c82e044a89f2f56a2c8a602a6 expression: 'last(/APC Smart-UPS SRT 5000 SNMP/output.status[upsBasicOutputStatus])=5' name: 'UPS is Timed Sleeping' priority: AVERAGE tags: - tag: scope value: notice - uuid: 998d1322a2274da19abe10cdcb3c52e0 name: 'Output voltage' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.4.3.1.0 key: 'output.voltage[upsHighPrecOutputVoltage]' history: 7d value_type: FLOAT units: V description: | MIB: PowerNet-MIB The output voltage of the UPS system in VAC. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - uuid: 3892c18baef54c598dc78035f5a7540a name: 'SNMP traps (fallback)' type: SNMP_TRAP key: snmptrap.fallback history: 2w trends: '0' value_type: LOG description: 'The item is used to collect all SNMP traps unmatched by other snmptrap items' logtimefmt: 'hh:mm:sszyyyy/MM/dd' tags: - tag: component value: network - uuid: 7485fd42dd2749028a2d67f315888723 name: 'System contact details' type: SNMP_AGENT snmp_oid: 1.3.6.1.2.1.1.4.0 key: 'system.contact[sysContact.0]' delay: 15m history: 2w trends: '0' value_type: CHAR description: | MIB: SNMPv2-MIB The textual identification of the contact person for this managed node, together with information on how to contact this person. If no contact information is known, the value is the zero-length string. inventory_link: CONTACT preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 12h tags: - tag: component value: system - uuid: 0617c89b47454dbd833fcc2b8d570db8 name: 'System description' type: SNMP_AGENT snmp_oid: 1.3.6.1.2.1.1.1.0 key: 'system.descr[sysDescr.0]' delay: 15m history: 2w trends: '0' value_type: CHAR description: | MIB: SNMPv2-MIB A textual description of the entity. This value should include the full name and version identification of the system's hardware type, software operating-system, and networking software. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 12h tags: - tag: component value: system - uuid: a57de4a9da144c2aa880253e4e2b46f9 name: 'System location' type: SNMP_AGENT snmp_oid: 1.3.6.1.2.1.1.6.0 key: 'system.location[sysLocation.0]' delay: 15m history: 2w trends: '0' value_type: CHAR description: | MIB: SNMPv2-MIB The physical location of this node (e.g., `telephone closet, 3rd floor'). If the location is unknown, the value is the zero-length string. inventory_link: LOCATION preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: system - uuid: 7e81f54bbbdd41ca8f9e010dbddc485f name: Model type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.1.1.1.0 key: 'system.model[upsBasicIdentModel]' delay: 15m history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB The UPS model name (e.g. 'APC Smart-UPS 600'). preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: inventory - uuid: 5778610ee61d472d9dc8c8da94f9e301 name: 'System name' type: SNMP_AGENT snmp_oid: 1.3.6.1.2.1.1.5.0 key: 'system.name[sysName.0]' delay: 15m history: 2w trends: '0' value_type: CHAR description: | MIB: SNMPv2-MIB An administratively-assigned name for this managed node.By convention, this is the node's fully-qualified domain name. If the name is unknown, the value is the zero-length string. inventory_link: NAME preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: system triggers: - uuid: 154aad534c35473cb4513cb4e3d4a082 expression: 'last(/APC Smart-UPS SRT 5000 SNMP/system.name[sysName.0],#1)<>last(/APC Smart-UPS SRT 5000 SNMP/system.name[sysName.0],#2) and length(last(/APC Smart-UPS SRT 5000 SNMP/system.name[sysName.0]))>0' name: 'System name has changed' event_name: 'System name has changed (new name: {ITEM.VALUE})' priority: INFO description: 'System name has changed. Ack to close.' manual_close: 'YES' tags: - tag: scope value: notice - tag: scope value: security - uuid: 1782e98504114e7c847b6d127b3a3ae1 name: 'System object ID' type: SNMP_AGENT snmp_oid: 1.3.6.1.2.1.1.2.0 key: 'system.objectid[sysObjectID.0]' delay: 15m history: 2w trends: '0' value_type: CHAR description: | MIB: SNMPv2-MIB The vendor's authoritative identification of the network management subsystem contained in the entity. This value is allocated within the SMI enterprises subtree (1.3.6.1.4.1) and provides an easy and unambiguous means for determining`what kind of box' is being managed. For example, if vendor`Flintstones, Inc.' was assigned the subtree1.3.6.1.4.1.4242, it could assign the identifier 1.3.6.1.4.1.4242.1.1 to its `Fred Router'. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: system - uuid: a3069693d6e545978fb877d767dface5 name: 'Serial number' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.1.2.3.0 key: 'system.sn[upsAdvIdentSerialNumber]' delay: 15m history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB An 8-character string identifying the serial number of the UPS internal microprocessor. This number is set at the factory. NOTE: This number does NOT correspond to the serial number on the rear of the UPS. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: inventory - uuid: 1b9e4b13cfcb4680b25dd8974900fc17 name: Uptime type: SNMP_AGENT snmp_oid: 1.3.6.1.2.1.1.3.0 key: 'system.uptime[sysUpTime.0]' delay: 30s history: 2w trends: 0d units: uptime description: | MIB: SNMPv2-MIB The time (in hundredths of a second) since the network management portion of the system was last re-initialized. preprocessing: - type: MULTIPLIER parameters: - '0.01' tags: - tag: component value: system triggers: - uuid: 7793a5e111c6466584ef6610aae707c1 expression: 'last(/APC Smart-UPS SRT 5000 SNMP/system.uptime[sysUpTime.0])<10m' name: 'has been restarted' event_name: '{HOST.NAME} has been restarted (uptime < 10m)' priority: WARNING description: 'Uptime is less than 10 minutes' manual_close: 'YES' dependencies: - name: 'No SNMP data collection' expression: 'max(/APC Smart-UPS SRT 5000 SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0' tags: - tag: scope value: notice - uuid: 63079124c55f479dad013d0c15077577 name: 'SNMP agent availability' type: INTERNAL key: 'zabbix[host,snmp,available]' history: 7d description: | Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list. Possible value: 0 - not available 1 - available 2 - unknown valuemap: name: zabbix.host.available preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: health - tag: component value: network triggers: - uuid: 6e0f9b15effd4c9e9c416a99fd8f4517 expression: 'max(/APC Smart-UPS SRT 5000 SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0' name: 'No SNMP data collection' opdata: 'Current state: {ITEM.LASTVALUE1}' priority: WARNING description: 'SNMP is not available for polling. Please check device connectivity and SNMP settings.' tags: - tag: scope value: availability discovery_rules: - uuid: af4472b543b54699b6e812de51be2419 name: 'External bad battery packs discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#EXTERNAL_PACKS},1.3.6.1.4.1.318.1.1.1.2.2.6]' key: battery.packs.bad.discovery delay: 1h description: 'Discovery of the number of external defective battery packs.' item_prototypes: - uuid: a8a07270aac8499391fddfd1b6d517a3 name: '{#SNMPINDEX}: External battery packs bad' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.2.6.0 key: 'battery.external_packs_bad[upsAdvBatteryNumOfBadBattPacks.{#SNMPINDEX}]' delay: 15m history: 7d description: | MIB: PowerNet-MIB The number of external battery packs connected to the UPS that are defective. If the UPS does not use smart cells then the agent reports ERROR_NO_SUCH_NAME. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: inventory - uuid: a3716fb0833e4655b63ec4ccc5736950 name: 'External battery packs discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#CARTRIDGE_STATUS},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.7,{#BATTERY_PACK},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.1,{#CARTRIDGE_INDEX},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.2]' key: battery.packs.discovery delay: 1h filter: evaltype: AND conditions: - macro: '{#CARTRIDGE_STATUS}' value: ^$ operator: NOT_MATCHES_REGEX formulaid: A item_prototypes: - uuid: b68c1b0a33bf4d2c94bd46e25a6b5e46 name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery estimated replace date' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.8.{#SNMPINDEX}' key: 'battery.estimated_replace_date[upsHighPrecBatteryPackCartridgeReplaceDate.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]' delay: 1h history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB The battery cartridge estimated battery replace date. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: inventory - tag: component value: power - uuid: 8629f478f8e44e079b69914b498ce2f5 name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery pack cartridge health' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.7.{#SNMPINDEX}' key: 'battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]' history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB The battery cartridge health. bit 0 Battery lifetime okay bit 1 Battery lifetime near end, order replacement cartridge bit 2 Battery lifetime exceeded, replace battery bit 3 Battery lifetime near end acknowledged, order replacement cartridge bit 4 Battery lifetime exceeded acknowledged, replace battery bit 5 Battery measured lifetime near end, order replacement cartridge bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: health - tag: component value: power trigger_prototypes: - uuid: b29f9bd2e80242be940682139f303121 expression: 'find(/APC Smart-UPS SRT 5000 SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1' name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay' opdata: 'Current bit set: {ITEM.LASTVALUE1}' priority: WARNING description: | The battery cartridge health. bit 0 Battery lifetime okay bit 1 Battery lifetime near end, order replacement cartridge bit 2 Battery lifetime exceeded, replace battery bit 3 Battery lifetime near end acknowledged, order replacement cartridge bit 4 Battery lifetime exceeded acknowledged, replace battery bit 5 Battery measured lifetime near end, order replacement cartridge bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge tags: - tag: scope value: notice - uuid: fd2d784d618a4ad883a4afb8a9b94940 name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.10.{#SNMPINDEX}' key: 'battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]' history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB The battery cartridge status. bit 0 Disconnected bit 1 Overvoltage bit 2 NeedsReplacement bit 3 OvertemperatureCritical bit 4 Charger bit 5 TemperatureSensor bit 6 BusSoftStart bit 7 OvertemperatureWarning bit 8 GeneralError bit 9 Communication bit 10 DisconnectedFrame bit 11 FirmwareMismatch preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: health - tag: component value: power trigger_prototypes: - uuid: 0a96a9726cdd4431ad6e6d52e7461d69 expression: 'find(/APC Smart-UPS SRT 5000 SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0' name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay' opdata: 'Current bit set: {ITEM.LASTVALUE1}' priority: WARNING description: | The battery cartridge status: bit 0 Disconnected bit 1 Overvoltage bit 2 NeedsReplacement bit 3 OvertemperatureCritical bit 4 Charger bit 5 TemperatureSensor bit 6 BusSoftStart bit 7 OvertemperatureWarning bit 8 GeneralError bit 9 Communication bit 10 DisconnectedFrame bit 11 FirmwareMismatch tags: - tag: scope value: notice - uuid: 6b20217de8474cc08ca3818784804109 name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery temperature' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.5.{#SNMPINDEX}' key: 'battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]' history: 7d value_type: FLOAT units: ℃ description: | MIB: PowerNet-MIB The battery pack temperature in Celsius. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: temperature trigger_prototypes: - uuid: dbb191572a17451296ae4ee8d3aeec73 expression: 'min(/APC Smart-UPS SRT 5000 SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}' name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature' event_name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD})' opdata: 'Current temperature: {ITEM.LASTVALUE1}' priority: HIGH tags: - tag: scope value: notice - uuid: 7757bd184a7c4c0bbd442c7a3013f6d9 name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Serial number' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.4.{#SNMPINDEX}' key: 'system.sn[upsHighPrecBatteryPackSerialNumber.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]' delay: 15m history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB The battery pack serial number. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: inventory - uuid: e858b8966abc444a914ef60c1708b835 name: 'External sensor port 1 discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#EXTERNAL_SENSOR1_NAME},1.3.6.1.4.1.318.1.1.25.1.2.1.3]' key: external.sensor1.discovery delay: 1h description: uioSensorStatusTable item_prototypes: - uuid: bddad787e7df427b8b225c9af517c3c1 name: '{#EXTERNAL_SENSOR1_NAME}: Humidity sensor' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.1.7.1.1 key: 'external.sensor.humidity[uioSensorStatusHumidity.1.{#SNMPINDEX}]' history: 7d value_type: FLOAT units: '%' description: | MIB: PowerNet-MIB The sensor's current humidity reading - a relative humidity percentage. -1 indicates an invalid reading due to either a sensor that doesn't read humidity or lost communications. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: humidity - tag: component value: power - uuid: 5cab24d2166244fd9528930edbafa677 name: '{#EXTERNAL_SENSOR1_NAME}: Sensor alarm status' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.1.9.1.1 key: 'external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}]' history: 7d description: | MIB: PowerNet-MIB The alarm status of the sensor. Possible values: uioNormal (1), uioWarning (2), uioCritical (3), sensorStatusNotApplicable (4) valuemap: name: 'PowerNet-MIB::uioSensorStatusAlarmStatus' preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: health - tag: component value: power trigger_prototypes: - uuid: fc448a3d2ae4462a903863364bec836d expression: 'last(/APC Smart-UPS SRT 5000 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=3' name: '{#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical' priority: HIGH description: 'The external sensor has returned a value greater than the critical threshold.' tags: - tag: scope value: notice - uuid: 3340123b060949a4b806a5a757862026 expression: 'last(/APC Smart-UPS SRT 5000 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4' name: '{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable' priority: INFO description: 'The external sensor does not work or is not connected.' tags: - tag: scope value: notice - uuid: 5ac7c47c37804492947716e5857275c4 expression: 'last(/APC Smart-UPS SRT 5000 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2' name: '{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning' priority: AVERAGE description: 'The external sensor has returned a value greater than the warning threshold.' tags: - tag: scope value: notice - uuid: af55c3c3bc2f45ec9f735de0fb5a4285 name: '{#EXTERNAL_SENSOR1_NAME}: Temperature sensor' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.1.6.1.1 key: 'external.sensor.temperature[uioSensorStatusTemperatureDegC.1.{#SNMPINDEX}]' history: 7d value_type: FLOAT units: ℃ description: | MIB: PowerNet-MIB The sensor's current temperature reading in Celsius. -1 indicates an invalid reading due to lost communications. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - tag: component value: temperature overrides: - name: Temp step: '1' filter: conditions: - macro: '{#EXTERNAL_SENSOR1_NAME}' value: Temp formulaid: A operations: - operationobject: ITEM_PROTOTYPE operator: LIKE value: Humidity status: ENABLED discover: NO_DISCOVER - uuid: 415a43bfe1d845f88f0ac15e80a0dc14 name: 'External sensor port 2 discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#EXTERNAL_SENSOR2_NAME},1.3.6.1.4.1.318.1.1.25.1.2.2.3]' key: external.sensor2.discovery delay: 1h description: uioSensorStatusTable item_prototypes: - uuid: 4a5c62571e0b4fdaa6c7b85645e06649 name: '{#EXTERNAL_SENSOR2_NAME}: Humidity sensor' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.2.7.1.1 key: 'external.sensor.humidity[uioSensorStatusHumidity.2.{#SNMPINDEX}]' history: 7d value_type: FLOAT units: '%' description: | MIB: PowerNet-MIB The sensor's current humidity reading - a relative humidity percentage. -1 indicates an invalid reading due to either a sensor that doesn't read humidity or lost communications. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: humidity - tag: component value: power - uuid: e09e9e197d2f4afc83231cb304a26b09 name: '{#EXTERNAL_SENSOR2_NAME}: Sensor alarm status' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.2.9.1.1 key: 'external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}]' history: 7d description: | MIB: PowerNet-MIB The alarm status of the sensor. Possible values: uioNormal (1), uioWarning (2), uioCritical (3), sensorStatusNotApplicable (4) valuemap: name: 'PowerNet-MIB::uioSensorStatusAlarmStatus' preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: health - tag: component value: power trigger_prototypes: - uuid: 8774e39abe784f6b9fe2f33c30f3fa05 expression: 'last(/APC Smart-UPS SRT 5000 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=3' name: '{#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical' priority: HIGH description: 'The external sensor has returned a value greater than the critical threshold.' tags: - tag: scope value: notice - uuid: d41c9de571ea4b48a1213f98a058c550 expression: 'last(/APC Smart-UPS SRT 5000 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=4' name: '{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable' priority: INFO description: 'The external sensor does not work or is not connected.' tags: - tag: scope value: notice - uuid: c9e751b9449f4616beeb36b51cf0a3b9 expression: 'last(/APC Smart-UPS SRT 5000 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=2' name: '{#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning' priority: AVERAGE description: 'The external sensor has returned a value greater than the warning threshold.' tags: - tag: scope value: notice - uuid: 7bc1fa7e114e40ffadd4336a3980e4c2 name: '{#EXTERNAL_SENSOR2_NAME}: Temperature sensor' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.2.6.1.1 key: 'external.sensor.temperature[uioSensorStatusTemperatureDegC.2.{#SNMPINDEX}]' history: 7d value_type: FLOAT units: ℃ description: | MIB: PowerNet-MIB The sensor's current temperature reading in Celsius. -1 indicates an invalid reading due to lost communications. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - tag: component value: temperature overrides: - name: Temp step: '1' filter: conditions: - macro: '{#EXTERNAL_SENSOR2_NAME}' value: Temp formulaid: A operations: - operationobject: ITEM_PROTOTYPE operator: LIKE value: Humidity status: ENABLED discover: NO_DISCOVER - uuid: 5971a05073b84056bf4e30dfa3e2e18e name: 'Input phases discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#PHASEINDEX},1.3.6.1.4.1.318.1.1.1.9.2.3.1.2.1.1]' key: input.phases.discovery delay: 1h description: 'The input phase identifier. OID upsPhaseInputPhaseIndex.1.1' item_prototypes: - uuid: 847e044ec924456daf41025d312334bf name: '{#PHASEINDEX}: Phase input current' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.9.2.3.1.6.1.1.{#PHASEINDEX}' key: 'phase.input.current[upsPhaseInputCurrent.1.1.{#PHASEINDEX}]' history: 7d value_type: FLOAT units: A description: | MIB: PowerNet-MIB The input current in 0.1 amperes, or -0.1 if it's unsupported by this UPS. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - uuid: 15de75236e9c44f1bb4bbf4c0425c9c2 name: '{#PHASEINDEX}: Phase input voltage' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.9.2.3.1.3.1.1.{#PHASEINDEX}' key: 'phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}]' history: 7d value_type: FLOAT units: V description: | MIB: PowerNet-MIB The input voltage in VAC, or -1 if it's unsupported by this UPS. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power trigger_prototypes: - uuid: b8d5cbee0bc14df58a217b33222aa75d expression: 'min(/APC Smart-UPS SRT 5000 SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS SRT 5000 SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}' name: '{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage' event_name: '{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})' opdata: 'Current phase {#PHASEINDEX} voltage: {ITEM.LASTVALUE1}' priority: HIGH tags: - tag: scope value: notice - uuid: e4f2cd7e1f004c4abd5be7e5fc28a9eb name: 'Output phases discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#PHASEINDEX},1.3.6.1.4.1.318.1.1.1.9.3.3.1.2.1.1]' key: output.phases.discovery delay: 1h description: 'The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1' item_prototypes: - uuid: 0e4b4159dd0543faa5d93969f8e5753b name: '{#PHASEINDEX}: Phase output current' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.9.3.3.1.4.1.1.{#PHASEINDEX}' key: 'phase.output.current[upsPhaseOutputCurrent.1.1.{#PHASEINDEX}]' history: 7d value_type: FLOAT units: A description: | MIB: PowerNet-MIB The output current in 0.1 amperes drawn by the load on the UPS, or -1 if it's unsupported by this UPS. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - uuid: 3d35f771f73545e2806153f33e747bc4 name: '{#PHASEINDEX}: Phase output load, %' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.9.3.3.1.10.1.1.{#PHASEINDEX}' key: 'phase.output.load.percent[upsPhaseOutputPercentLoad.1.1.{#PHASEINDEX}]' history: 7d value_type: FLOAT units: '%' description: | MIB: PowerNet-MIB The percentage of the UPS load capacity in VA at redundancy @ (n + x) presently being used on this output phase, or -1 if it's unsupported by this UPS. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - uuid: d27c63f29e9b453a9bbdac1c0c8065ae name: '{#PHASEINDEX}: Phase output voltage' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.9.3.3.1.3.1.1.{#PHASEINDEX}' key: 'phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}]' history: 7d value_type: FLOAT units: V description: | MIB: PowerNet-MIB The output voltage in VAC, or -1 if it's unsupported by this UPS. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power trigger_prototypes: - uuid: 176a3014124f4f23bedbad120cb2b69a expression: 'min(/APC Smart-UPS SRT 5000 SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS SRT 5000 SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}' name: '{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage' event_name: '{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})' opdata: 'Current phase {#PHASEINDEX} voltage: {ITEM.LASTVALUE1}' priority: HIGH tags: - tag: scope value: notice tags: - tag: class value: power - tag: target value: apc - tag: target value: apc-smart-ups-srt-5000 macros: - macro: '{$BATTERY.CAPACITY.MIN.WARN}' value: '50' description: 'Minimum battery capacity percentage for trigger expression.' - macro: '{$BATTERY.TEMP.MAX.WARN}' value: '55' description: 'Maximum battery temperature for trigger expression.' - macro: '{$SNMP.TIMEOUT}' value: 5m description: 'The time interval for SNMP agent availability trigger expression.' - macro: '{$TIME.PERIOD}' value: 15m description: 'Time period for trigger expression.' - macro: '{$UPS.INPUT_FREQ.MAX.WARN}' value: '50.3' description: 'Maximum input frequency for trigger expression.' - macro: '{$UPS.INPUT_FREQ.MIN.WARN}' value: '49.7' description: 'Minimum input frequency for trigger expression.' - macro: '{$UPS.INPUT_VOLT.MAX.WARN}' value: '243' description: 'Maximum input voltage for trigger expression.' - macro: '{$UPS.INPUT_VOLT.MIN.WARN}' value: '197' description: 'Minimum input voltage for trigger expression.' - macro: '{$UPS.OUTPUT.MAX.WARN}' value: '80' description: 'Maximum output load in % for trigger expression.' dashboards: - uuid: ceb28c7c39e44859a4c1076978a40788 name: 'UPS Summary' pages: - widgets: - type: PLAIN_TEXT width: '8' fields: - type: INTEGER name: show_lines value: '1' - type: INTEGER name: show_as_html value: '0' - type: ITEM name: itemids value: key: 'system.uptime[sysUpTime.0]' host: 'APC Smart-UPS SRT 5000 SNMP' - type: PLAIN_TEXT x: '8' width: '8' fields: - type: INTEGER name: show_lines value: '1' - type: INTEGER name: show_as_html value: '0' - type: ITEM name: itemids value: key: 'input.fail[upsAdvInputLineFailCause]' host: 'APC Smart-UPS SRT 5000 SNMP' - type: PLAIN_TEXT x: '16' width: '8' fields: - type: INTEGER name: show_lines value: '1' - type: INTEGER name: show_as_html value: '0' - type: ITEM name: itemids value: key: 'output.status[upsBasicOutputStatus]' host: 'APC Smart-UPS SRT 5000 SNMP' - type: PLAIN_TEXT 'y': '2' width: '8' fields: - type: INTEGER name: show_lines value: '1' - type: INTEGER name: show_as_html value: '0' - type: ITEM name: itemids value: key: 'battery.status[upsBasicBatteryStatus]' host: 'APC Smart-UPS SRT 5000 SNMP' - type: PLAIN_TEXT x: '8' 'y': '2' width: '8' fields: - type: INTEGER name: show_lines value: '1' - type: INTEGER name: show_as_html value: '0' - type: ITEM name: itemids value: key: 'battery.runtime_remaining[upsAdvBatteryRunTimeRemaining]' host: 'APC Smart-UPS SRT 5000 SNMP' - type: PLAIN_TEXT x: '16' 'y': '2' width: '8' fields: - type: INTEGER name: show_lines value: '1' - type: INTEGER name: show_as_html value: '0' - type: ITEM name: itemids value: key: 'battery.last_replace_date[upsBasicBatteryLastReplaceDate]' host: 'APC Smart-UPS SRT 5000 SNMP' - type: GRAPH_CLASSIC 'y': '4' width: '8' height: '7' fields: - type: INTEGER name: source_type value: '0' - type: GRAPH name: graphid value: name: 'Capacity of the UPS batteries' host: 'APC Smart-UPS SRT 5000 SNMP' - type: GRAPH_CLASSIC x: '8' 'y': '4' width: '8' height: '7' fields: - type: INTEGER name: source_type value: '0' - type: GRAPH name: graphid value: name: Voltage host: 'APC Smart-UPS SRT 5000 SNMP' - type: GRAPH_CLASSIC x: '16' 'y': '4' width: '8' height: '7' fields: - type: INTEGER name: source_type value: '0' - type: GRAPH name: graphid value: name: Output host: 'APC Smart-UPS SRT 5000 SNMP' valuemaps: - uuid: 41e166e2a5f948488238198920ab4b17 name: 'PowerNet-MIB::uioSensorStatusAlarmStatus' mappings: - value: '1' newvalue: Normal - value: '2' newvalue: Warning - value: '3' newvalue: Critical - value: '4' newvalue: 'Not applicable' - uuid: 224af0a6a5db48ef9c8861bc61873ea9 name: 'PowerNet-MIB::upsAdvBatteryReplaceIndicator' mappings: - value: '1' newvalue: 'no Battery Needs Replacing' - value: '2' newvalue: 'battery Needs Replacing' - uuid: ded19296204545b9ab463d4fc65f3cfd name: 'PowerNet-MIB::upsAdvInputLineFailCause' mappings: - value: '1' newvalue: 'no Transfer' - value: '2' newvalue: 'High Line Voltage' - value: '3' newvalue: Brownout - value: '4' newvalue: Blackout - value: '5' newvalue: 'Small Momentary Sag' - value: '6' newvalue: 'Deep Momentary Sag' - value: '7' newvalue: 'Small Momentary Spike' - value: '8' newvalue: 'Large Momentary Spike' - value: '9' newvalue: 'Self Test' - value: '10' newvalue: 'Rate of Voltage Change' - uuid: 271d8f0594cf451a8aaa98c84850ebf7 name: 'PowerNet-MIB::upsBasicBatteryStatus' mappings: - value: '1' newvalue: Unknown - value: '2' newvalue: Normal - value: '3' newvalue: Low - value: '4' newvalue: 'In Fault Condition' - uuid: 171d4d5bf01442e391b04f9e448df5a0 name: 'PowerNet-MIB::upsBasicOutputStatus' mappings: - value: '1' newvalue: Unknown - value: '2' newvalue: Online - value: '3' newvalue: 'On Battery' - value: '4' newvalue: 'On Smart Boost' - value: '5' newvalue: 'Timed Sleeping' - value: '6' newvalue: 'Software Bypass' - value: '7' newvalue: 'Off' - value: '8' newvalue: Rebooting - value: '9' newvalue: 'Switched Bypass' - value: '10' newvalue: 'Hardware Failure Bypass' - value: '11' newvalue: 'Sleeping Until Power Return' - value: '12' newvalue: 'On Smart Trim' - value: '13' newvalue: 'Eco Mode' - value: '14' newvalue: 'Hot Standby' - value: '15' newvalue: 'On Battery Test' - value: '16' newvalue: 'Emergency Static Bypass' - value: '17' newvalue: 'Static Bypass Standby' - value: '18' newvalue: 'Power Saving Mode' - value: '19' newvalue: 'Spot Mode' - value: '20' newvalue: E-Conversion - value: '21' newvalue: 'Charger Spotmode' - value: '22' newvalue: 'Inverter Spotmode' - value: '23' newvalue: 'Active Load' - value: '24' newvalue: 'Battery Discharge Spotmode' - value: '25' newvalue: 'Inverter Standby' - value: '26' newvalue: 'Charger Only' - uuid: 8b4f199f5e704cbea67182d4abf9b8de name: zabbix.host.available mappings: - value: '0' newvalue: 'not available' - value: '1' newvalue: available - value: '2' newvalue: unknown graphs: - uuid: fb922a035a6748e28dc892af3331dae4 name: 'Capacity of the UPS batteries' type: PIE graph_items: - color: 1A7C11 item: host: 'APC Smart-UPS SRT 5000 SNMP' key: 'battery.capacity[upsHighPrecBatteryCapacity]' - uuid: 4317390560354b369a884abcbce9a026 name: Output graph_items: - color: 1A7C11 item: host: 'APC Smart-UPS SRT 5000 SNMP' key: 'output.current[upsHighPrecOutputCurrent]' - sortorder: '1' color: 2774A4 item: host: 'APC Smart-UPS SRT 5000 SNMP' key: 'output.load[upsHighPrecOutputLoad]' - uuid: 595018e4c5d8406a805aed647cd2f5d1 name: Voltage graph_items: - color: 1A7C11 item: host: 'APC Smart-UPS SRT 5000 SNMP' key: 'input.voltage[upsHighPrecInputLineVoltage]' - sortorder: '1' color: 2774A4 item: host: 'APC Smart-UPS SRT 5000 SNMP' key: 'output.voltage[upsHighPrecOutputVoltage]'