zabbix_export: version: '6.0' date: '2021-10-28T08:23:45Z' groups: - uuid: 3dcd5bbe90534f9e8eb5c2d53756af63 name: Templates/Power templates: - uuid: b3caafda8c5345cc832ac3be3cefa615 template: 'APC Smart-UPS SRT 8000 SNMP' name: 'APC Smart-UPS SRT 8000 SNMP' description: | Template Power APC Smart-UPS SRT 8000 MIBs used: PowerNet-MIB SNMPv2-MIB You can discuss this template or leave feedback on our forum https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups Template tooling version used: 0.39 groups: - name: Templates/Power items: - uuid: c4f4a85105f24292a3b566d0d1bcc090 name: 'Battery capacity' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.3.1.0 key: 'battery.capacity[upsHighPrecBatteryCapacity]' history: 7d value_type: FLOAT units: '%' description: | MIB: PowerNet-MIB The remaining battery capacity expressed as percentage of full capacity. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: Status triggers: - uuid: 92e6a65ffc6d4a6bae62303ee2796580 expression: 'last(/APC Smart-UPS SRT 8000 SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}' name: 'Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%)' opdata: 'Current capacity: {ITEM.LASTVALUE1}' priority: HIGH - uuid: 7d7c2b962e9843b8a6cf72c04ff1e479 name: 'External battery packs count' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.2.5.0 key: 'battery.external_packs_count[upsAdvBatteryNumOfBattPacks]' delay: 1h history: 7d description: | MIB: PowerNet-MIB The number of external battery packs connected to the UPS. If the UPS does not use smart cells then the agent reports ERROR_NO_SUCH_NAME. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: Status - uuid: 552e030c272d43a0998bc2648f15ae44 name: 'Battery last replace date' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.1.3.0 key: 'battery.last_replace_date[upsBasicBatteryLastReplaceDate]' delay: 1h history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB The date when the UPS system's batteries were last replaced in mm/dd/yy (or yyyy) format. For Smart-UPS models, this value is originally set at the factory. When the UPS batteries are replaced, this value should be reset by the administrator. For Symmetra PX 250/500 this OID is read-only and is configurable in the local display only. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: Status - uuid: 4cdd4bbff845477194a6d96a31431d23 name: 'Battery replace indicator' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.2.4.0 key: 'battery.replace_indicator[upsAdvBatteryReplaceIndicator]' history: 7d description: | MIB: PowerNet-MIB Indicates whether the UPS batteries need replacement. valuemap: name: 'PowerNet-MIB::upsAdvBatteryReplaceIndicator' preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: Status triggers: - uuid: 0e8030c0028144728361153c2b47016b expression: 'last(/APC Smart-UPS SRT 8000 SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2' name: 'Battery needs replacement' priority: HIGH description: 'A battery installed has an internal error condition.' - uuid: ae8a19896d21405ca99a5bfbd5de1f95 name: 'Battery runtime remaining' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.2.3.0 key: 'battery.runtime_remaining[upsAdvBatteryRunTimeRemaining]' history: 7d value_type: FLOAT units: s description: | MIB: PowerNet-MIB The UPS battery run time remaining before battery exhaustion. preprocessing: - type: MULTIPLIER parameters: - '0.01' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: Status - uuid: ceed5ddfc9964aabaebb0b97875b1bd9 name: 'Battery status' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.1.1.0 key: 'battery.status[upsBasicBatteryStatus]' history: 7d description: | MIB: PowerNet-MIB The status of the UPS batteries. A batteryLow(3) value indicates the UPS will be unable to sustain the current load, and its services will be lost if power is not restored. The amount of run time in reserve at the time of low battery can be configured by the upsAdvConfigLowBatteryRunTime. A batteryInFaultCondition(4)value indicates that a battery installed has an internal error condition. valuemap: name: 'PowerNet-MIB::upsBasicBatteryStatus' preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: Status triggers: - uuid: cf186014cfd94ccbad3cc4cbd22b6aa1 expression: 'last(/APC Smart-UPS SRT 8000 SNMP/battery.status[upsBasicBatteryStatus])=4' name: 'Battery has an internal error condition' priority: AVERAGE description: 'A battery installed has an internal error condition.' - uuid: e1957ee82be847e7bfb171560fc59293 expression: 'last(/APC Smart-UPS SRT 8000 SNMP/battery.status[upsBasicBatteryStatus])=3' name: 'Battery is Low' priority: AVERAGE description: 'The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.' - uuid: 533041b6831c451cb72991d3fdeca535 name: 'Battery temperature' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.3.2.0 key: 'battery.temperature[upsHighPrecBatteryTemperature]' history: 7d value_type: FLOAT units: ℃ description: | MIB: PowerNet-MIB The current internal UPS temperature in Celsius. Temperatures below zero read as 0. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: Status triggers: - uuid: 1e883961b65e445997c57870734a58ca expression: 'min(/APC Smart-UPS SRT 8000 SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}' name: 'Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD})' opdata: 'Current temperature: {ITEM.LASTVALUE1}' priority: HIGH - uuid: fa8256c826954defa82083ddc742624e name: 'Battery voltage' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.3.4.0 key: 'battery.voltage[upsHighPrecBatteryActualVoltage]' history: 7d value_type: FLOAT units: V description: | MIB: PowerNet-MIB The actual battery bus voltage in Volts. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: Status - uuid: 07754bb421d0435995abbc49d4597908 name: 'Input fail cause' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.3.2.5.0 key: 'input.fail[upsAdvInputLineFailCause]' history: 7d description: | MIB: PowerNet-MIB The reason for the occurrence of the last transfer to UPS battery power. The variable is set to: - noTransfer(1) -- if there is no transfer yet. - highLineVoltage(2) -- if the transfer to battery is caused by an over voltage greater than the high transfer voltage. - brownout(3) -- if the duration of the outage is greater than five seconds and the line voltage is between 40% of the rated output voltage and the low transfer voltage. - blackout(4) -- if the duration of the outage is greater than five seconds and the line voltage is between 40% of the rated output voltage and ground. - smallMomentarySag(5) -- if the duration of the outage is less than five seconds and the line voltage is between 40% of the rated output voltage and the low transfer voltage. - deepMomentarySag(6) -- if the duration of the outage is less than five seconds and the line voltage is between 40% of the rated output voltage and ground. The variable is set to - smallMomentarySpike(7) -- if the line failure is caused by a rate of change of input voltage less than ten volts per cycle. - largeMomentarySpike(8) -- if the line failure is caused by a rate of change of input voltage greater than ten volts per cycle. - selfTest(9) -- if the UPS was commanded to do a self test. - rateOfVoltageChange(10) -- if the failure is due to the rate of change of the line voltage. valuemap: name: 'PowerNet-MIB::upsAdvInputLineFailCause' preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: Status - uuid: 7574344f67544554804c4c68e39d3d72 name: 'Input frequency' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.3.3.4.0 key: 'input.frequency[upsHighPrecInputFrequency]' history: 7d value_type: FLOAT units: Hz description: | MIB: PowerNet-MIB The current input frequency to the UPS system in Hz. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: Status triggers: - uuid: b9a134c942da46ffba1acdf85a7832e4 expression: 'min(/APC Smart-UPS SRT 8000 SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS SRT 8000 SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC Smart-UPS SRT 8000 SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})' name: 'Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD})' opdata: 'Current frequency: {ITEM.LASTVALUE1}' priority: HIGH - uuid: c69418651f75413e95645c62fa3fee7f name: 'Input voltage' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.3.3.1.0 key: 'input.voltage[upsHighPrecInputLineVoltage]' history: 7d value_type: FLOAT units: V description: | MIB: PowerNet-MIB The current utility line voltage in VAC. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: Status triggers: - uuid: 694ab76079b1447b99ef510d80faab6a expression: 'min(/APC Smart-UPS SRT 8000 SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS SRT 8000 SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS SRT 8000 SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})' name: 'Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})' opdata: 'Current voltage: {ITEM.LASTVALUE1}' priority: HIGH - uuid: e4d76d857c4e46fd9b0e97405b17988a name: 'Output current' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.4.3.4.0 key: 'output.current[upsHighPrecOutputCurrent]' history: 7d value_type: FLOAT units: A description: | MIB: PowerNet-MIB The current in amperes drawn by the load on the UPS. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: Status - uuid: 0413f6ef89894dc6ba51e42f6a963f94 name: 'Output load' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.4.3.3.0 key: 'output.load[upsHighPrecOutputLoad]' history: 7d value_type: FLOAT units: '%' description: | MIB: PowerNet-MIB The current UPS load expressed as percentage of rated capacity. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: Status triggers: - uuid: 68f92026e7b345c88bf4aa679f9b642c expression: 'min(/APC Smart-UPS SRT 8000 SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}' name: 'Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD})' opdata: 'Current load: {ITEM.LASTVALUE1}' priority: HIGH description: 'A battery installed has an internal error condition.' - uuid: 11c1742beed041999375e5a1ede42546 name: 'Output status' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.4.1.1.0 key: 'output.status[upsBasicOutputStatus]' history: 7d description: | MIB: PowerNet-MIB The current state of the UPS. If the UPS is unable to determine the state of the UPS this variable is set to unknown(1). During self-test most UPSes report onBattery(3) but some that support it will report onBatteryTest(15). To determine self-test status across all UPSes, refer to the upsBasicStateOutputState OID. valuemap: name: 'PowerNet-MIB::upsBasicOutputStatus' preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: Status triggers: - uuid: 9952679fada845228bbbf05bcdada305 expression: 'last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=16' name: 'UPS is Emergency Static Bypass' priority: AVERAGE - uuid: ee306606159f4930bcf580b5084c846a expression: 'last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=10' name: 'UPS is Hardware Failure Bypass' priority: AVERAGE - uuid: c4623dc4c6ae4c5b9ff4bdf4f43ed8b2 expression: 'last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=7' name: 'UPS is Off' priority: AVERAGE - uuid: 26c0b9b62d864c1ead7b16e0076a7226 expression: 'last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=3' name: 'UPS is on battery' priority: AVERAGE - uuid: 5c8408069c03421cb60b388451869b6f expression: 'last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=4' name: 'UPS is on Smart Boost' priority: AVERAGE - uuid: 156c5260ed4444c19313ba491ce9352c expression: 'last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=12' name: 'UPS is On Smart Trim' priority: AVERAGE - uuid: c233bc86198140659ec3dd609c94ec94 expression: 'last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=8' name: 'UPS is Rebooting' priority: AVERAGE - uuid: 944e49d1b6d44adc8d720bd689d8c8cf expression: 'last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=11' name: 'UPS is Sleeping Until Power Return' priority: AVERAGE - uuid: 9b376dbd2d614878b681b42bb2c7fe4d expression: 'last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=6' name: 'UPS is Software Bypass' priority: AVERAGE - uuid: 499ac46836c1454dad3c1ffc5714c073 expression: 'last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=9' name: 'UPS is Switched Bypass' priority: AVERAGE - uuid: 8a0a5af39647494681e52595d179c336 expression: 'last(/APC Smart-UPS SRT 8000 SNMP/output.status[upsBasicOutputStatus])=5' name: 'UPS is Timed Sleeping' priority: AVERAGE - uuid: 07059c625de94e618925249492982fb7 name: 'Output voltage' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.4.3.1.0 key: 'output.voltage[upsHighPrecOutputVoltage]' history: 7d value_type: FLOAT units: V description: | MIB: PowerNet-MIB The output voltage of the UPS system in VAC. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: Status - uuid: ae4579b14c424c0492acbfcb5aa5dd67 name: 'SNMP traps (fallback)' type: SNMP_TRAP key: snmptrap.fallback history: 2w trends: '0' value_type: LOG description: 'The item is used to collect all SNMP traps unmatched by other snmptrap items' logtimefmt: 'hh:mm:sszyyyy/MM/dd' tags: - tag: Application value: General - uuid: e4995e72f6b442bd9b8c90f09eb54f16 name: 'System contact details' type: SNMP_AGENT snmp_oid: 1.3.6.1.2.1.1.4.0 key: 'system.contact[sysContact.0]' delay: 15m history: 2w trends: '0' value_type: CHAR description: | MIB: SNMPv2-MIB The textual identification of the contact person for this managed node, together with information on how to contact this person. If no contact information is known, the value is the zero-length string. inventory_link: CONTACT preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 12h tags: - tag: Application value: General - uuid: 13d3c18413a249d492272a7373ebd772 name: 'System description' type: SNMP_AGENT snmp_oid: 1.3.6.1.2.1.1.1.0 key: 'system.descr[sysDescr.0]' delay: 15m history: 2w trends: '0' value_type: CHAR description: | MIB: SNMPv2-MIB A textual description of the entity. This value should include the full name and version identification of the system's hardware type, software operating-system, and networking software. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 12h tags: - tag: Application value: General - uuid: 25aa469a757347089191eb8e364d4df9 name: 'System location' type: SNMP_AGENT snmp_oid: 1.3.6.1.2.1.1.6.0 key: 'system.location[sysLocation.0]' delay: 15m history: 2w trends: '0' value_type: CHAR description: | MIB: SNMPv2-MIB The physical location of this node (e.g., `telephone closet, 3rd floor'). If the location is unknown, the value is the zero-length string. inventory_link: LOCATION preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: General - uuid: 57f3c4c2aff04eef83b7a7a53fa9f95c name: Model type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.1.1.1.0 key: 'system.model[upsBasicIdentModel]' delay: 15m history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB The UPS model name (e.g. 'APC Smart-UPS 600'). preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: General - uuid: 13c26820947442f581c2234c38c052cc name: 'System name' type: SNMP_AGENT snmp_oid: 1.3.6.1.2.1.1.5.0 key: 'system.name[sysName.0]' delay: 15m history: 2w trends: '0' value_type: CHAR description: | MIB: SNMPv2-MIB An administratively-assigned name for this managed node.By convention, this is the node's fully-qualified domain name. If the name is unknown, the value is the zero-length string. inventory_link: NAME preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: General triggers: - uuid: 852083234a55441aa2fa57b202227bef expression: 'last(/APC Smart-UPS SRT 8000 SNMP/system.name[sysName.0],#1)<>last(/APC Smart-UPS SRT 8000 SNMP/system.name[sysName.0],#2) and length(last(/APC Smart-UPS SRT 8000 SNMP/system.name[sysName.0]))>0' name: 'System name has changed (new name: {ITEM.VALUE})' priority: INFO description: 'System name has changed. Ack to close.' manual_close: 'YES' - uuid: b59b3801f5584321a1fca9bdb466f191 name: 'System object ID' type: SNMP_AGENT snmp_oid: 1.3.6.1.2.1.1.2.0 key: 'system.objectid[sysObjectID.0]' delay: 15m history: 2w trends: '0' value_type: CHAR description: | MIB: SNMPv2-MIB The vendor's authoritative identification of the network management subsystem contained in the entity. This value is allocated within the SMI enterprises subtree (1.3.6.1.4.1) and provides an easy and unambiguous means for determining`what kind of box' is being managed. For example, if vendor`Flintstones, Inc.' was assigned the subtree1.3.6.1.4.1.4242, it could assign the identifier 1.3.6.1.4.1.4242.1.1 to its `Fred Router'. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: General - uuid: 63852531159c44f1beca7facd8f93fa2 name: 'Serial number' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.1.2.3.0 key: 'system.sn[upsAdvIdentSerialNumber]' delay: 15m history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB An 8-character string identifying the serial number of the UPS internal microprocessor. This number is set at the factory. NOTE: This number does NOT correspond to the serial number on the rear of the UPS. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: General - uuid: 320bdbfd8076411bb1dd63fccddec126 name: Uptime type: SNMP_AGENT snmp_oid: 1.3.6.1.2.1.1.3.0 key: 'system.uptime[sysUpTime.0]' delay: 30s history: 2w trends: 0d units: uptime description: | MIB: SNMPv2-MIB The time (in hundredths of a second) since the network management portion of the system was last re-initialized. preprocessing: - type: MULTIPLIER parameters: - '0.01' tags: - tag: Application value: Status triggers: - uuid: 6f0fbe74ad4945e987e7ffdfa741d92f expression: 'last(/APC Smart-UPS SRT 8000 SNMP/system.uptime[sysUpTime.0])<10m' name: '{HOST.NAME} has been restarted (uptime < 10m)' priority: WARNING description: 'Uptime is less than 10 minutes' manual_close: 'YES' dependencies: - name: 'No SNMP data collection' expression: 'max(/APC Smart-UPS SRT 8000 SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0' - uuid: 567996748402435d80aae37818d4125e name: 'SNMP agent availability' type: INTERNAL key: 'zabbix[host,snmp,available]' history: 7d description: | Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list. Possible value: 0 - not available 1 - available 2 - unknown valuemap: name: zabbix.host.available preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: Status triggers: - uuid: 9a0cb26712c14045a18a0e86de4cdd54 expression: 'max(/APC Smart-UPS SRT 8000 SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0' name: 'No SNMP data collection' opdata: 'Current state: {ITEM.LASTVALUE1}' priority: WARNING description: 'SNMP is not available for polling. Please check device connectivity and SNMP settings.' discovery_rules: - uuid: 912994ce460742ebbb91c89d28d87d73 name: 'External bad battery packs discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#EXTERNAL_PACKS},1.3.6.1.4.1.318.1.1.1.2.2.6]' key: battery.packs.bad.discovery delay: 1h description: 'Discovery of the number of external defective battery packs.' item_prototypes: - uuid: e74988ed369b429893ca495a57ae9a52 name: '{#SNMPINDEX}: External battery packs bad' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.2.6.0 key: 'battery.external_packs_bad[upsAdvBatteryNumOfBadBattPacks.{#SNMPINDEX}]' delay: 15m history: 7d description: | MIB: PowerNet-MIB The number of external battery packs connected to the UPS that are defective. If the UPS does not use smart cells then the agent reports ERROR_NO_SUCH_NAME. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: Status - uuid: abfe041a98dc4023b21ec6d9e829a94a name: 'External battery packs discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#CARTRIDGE_STATUS},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.7,{#BATTERY_PACK},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.1,{#CARTRIDGE_INDEX},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.2]' key: battery.packs.discovery delay: 1h filter: evaltype: AND conditions: - macro: '{#CARTRIDGE_STATUS}' value: ^$ operator: NOT_MATCHES_REGEX formulaid: A item_prototypes: - uuid: b3835f9b8e9c41c98a747c37feaedb50 name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery estimated replace date' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.8.{#SNMPINDEX}' key: 'battery.estimated_replace_date[upsHighPrecBatteryPackCartridgeReplaceDate.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]' delay: 1h history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB The battery cartridge estimated battery replace date. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: Status - uuid: 820d8eda050b41a3a9ba2889e290a28a name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery pack cartridge health' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.7.{#SNMPINDEX}' key: 'battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]' history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB The battery cartridge health. bit 0 Battery lifetime okay bit 1 Battery lifetime near end, order replacement cartridge bit 2 Battery lifetime exceeded, replace battery bit 3 Battery lifetime near end acknowledged, order replacement cartridge bit 4 Battery lifetime exceeded acknowledged, replace battery bit 5 Battery measured lifetime near end, order replacement cartridge bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: Status trigger_prototypes: - uuid: 2d9c4ef006994ebea581b895424203f3 expression: 'find(/APC Smart-UPS SRT 8000 SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1' name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay' opdata: 'Current bit set: {ITEM.LASTVALUE1}' priority: WARNING description: | The battery cartridge health. bit 0 Battery lifetime okay bit 1 Battery lifetime near end, order replacement cartridge bit 2 Battery lifetime exceeded, replace battery bit 3 Battery lifetime near end acknowledged, order replacement cartridge bit 4 Battery lifetime exceeded acknowledged, replace battery bit 5 Battery measured lifetime near end, order replacement cartridge bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge - uuid: cf709f051aa242799cf14ba923d9a0c0 name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.10.{#SNMPINDEX}' key: 'battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]' history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB The battery cartridge status. bit 0 Disconnected bit 1 Overvoltage bit 2 NeedsReplacement bit 3 OvertemperatureCritical bit 4 Charger bit 5 TemperatureSensor bit 6 BusSoftStart bit 7 OvertemperatureWarning bit 8 GeneralError bit 9 Communication bit 10 DisconnectedFrame bit 11 FirmwareMismatch preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: Status trigger_prototypes: - uuid: 5358b97f94aa47f59351be88673407a0 expression: 'find(/APC Smart-UPS SRT 8000 SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0' name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay' opdata: 'Current bit set: {ITEM.LASTVALUE1}' priority: WARNING description: | The battery cartridge status: bit 0 Disconnected bit 1 Overvoltage bit 2 NeedsReplacement bit 3 OvertemperatureCritical bit 4 Charger bit 5 TemperatureSensor bit 6 BusSoftStart bit 7 OvertemperatureWarning bit 8 GeneralError bit 9 Communication bit 10 DisconnectedFrame bit 11 FirmwareMismatch - uuid: 99c570ed628343e99ac086167cec51ee name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery temperature' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.5.{#SNMPINDEX}' key: 'battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]' history: 7d value_type: FLOAT units: ℃ description: | MIB: PowerNet-MIB The battery pack temperature in Celsius. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: Status trigger_prototypes: - uuid: b88678e600694bc19ebaf57472d8658f expression: 'min(/APC Smart-UPS SRT 8000 SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}' name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD})' opdata: 'Current temperature: {ITEM.LASTVALUE1}' priority: HIGH - uuid: 597b33ec3d4c4f79bc0acc36edaa6dec name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Serial number' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.4.{#SNMPINDEX}' key: 'system.sn[upsHighPrecBatteryPackSerialNumber.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]' delay: 15m history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB The battery pack serial number. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: General - uuid: 52e5451d8c7a41478ef9dde6a3c16378 name: 'External sensor port 1 discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#EXTERNAL_SENSOR1_NAME},1.3.6.1.4.1.318.1.1.25.1.2.1.3]' key: external.sensor1.discovery delay: 1h description: uioSensorStatusTable item_prototypes: - uuid: 418b37fbca594f6288eeccdbe272bad7 name: '{#EXTERNAL_SENSOR1_NAME}: Humidity sensor' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.1.7.1.1 key: 'external.sensor.humidity[uioSensorStatusHumidity.1.{#SNMPINDEX}]' history: 7d value_type: FLOAT units: '%' description: | MIB: PowerNet-MIB The sensor's current humidity reading - a relative humidity percentage. -1 indicates an invalid reading due to either a sensor that doesn't read humidity or lost communications. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: Status - uuid: 53102fe478cf47bd9fbe5240aab7cf65 name: '{#EXTERNAL_SENSOR1_NAME}: Sensor alarm status' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.1.9.1.1 key: 'external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}]' history: 7d description: | MIB: PowerNet-MIB The alarm status of the sensor. Possible values: uioNormal (1), uioWarning (2), uioCritical (3), sensorStatusNotApplicable (4) valuemap: name: 'PowerNet-MIB::uioSensorStatusAlarmStatus' preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: Status trigger_prototypes: - uuid: 33f4ac80a8d44752b97bc4f885a8c95f expression: 'last(/APC Smart-UPS SRT 8000 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=3' name: '{#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical' priority: HIGH description: 'The external sensor has returned a value greater than the critical threshold.' - uuid: 1a2080a561394f8c8a0dc639cbf2c812 expression: 'last(/APC Smart-UPS SRT 8000 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4' name: '{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable' priority: INFO description: 'The external sensor does not work or is not connected.' - uuid: a53d5dd33e8548d5bcb73ffb936af910 expression: 'last(/APC Smart-UPS SRT 8000 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2' name: '{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning' priority: AVERAGE description: 'The external sensor has returned a value greater than the warning threshold.' - uuid: 0f44bfc0e17b47919e83246046209bbf name: '{#EXTERNAL_SENSOR1_NAME}: Temperature sensor' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.1.6.1.1 key: 'external.sensor.temperature[uioSensorStatusTemperatureDegC.1.{#SNMPINDEX}]' history: 7d value_type: FLOAT units: ℃ description: | MIB: PowerNet-MIB The sensor's current temperature reading in Celsius. -1 indicates an invalid reading due to lost communications. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: Status overrides: - name: Temp step: '1' filter: conditions: - macro: '{#EXTERNAL_SENSOR1_NAME}' value: Temp formulaid: A operations: - operationobject: ITEM_PROTOTYPE operator: LIKE value: Humidity status: ENABLED discover: NO_DISCOVER - uuid: 39f516180a1b4727907b1e2974111fe1 name: 'External sensor port 2 discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#EXTERNAL_SENSOR2_NAME},1.3.6.1.4.1.318.1.1.25.1.2.2.3]' key: external.sensor2.discovery delay: 1h description: uioSensorStatusTable item_prototypes: - uuid: 2263b22a266a4db091f05522a024a1e4 name: '{#EXTERNAL_SENSOR2_NAME}: Humidity sensor' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.2.7.1.1 key: 'external.sensor.humidity[uioSensorStatusHumidity.2.{#SNMPINDEX}]' history: 7d value_type: FLOAT units: '%' description: | MIB: PowerNet-MIB The sensor's current humidity reading - a relative humidity percentage. -1 indicates an invalid reading due to either a sensor that doesn't read humidity or lost communications. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: Status - uuid: b7af85f894194cf39c369fcba0401cc5 name: '{#EXTERNAL_SENSOR2_NAME}: Sensor alarm status' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.2.9.1.1 key: 'external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}]' history: 7d description: | MIB: PowerNet-MIB The alarm status of the sensor. Possible values: uioNormal (1), uioWarning (2), uioCritical (3), sensorStatusNotApplicable (4) valuemap: name: 'PowerNet-MIB::uioSensorStatusAlarmStatus' preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: Status trigger_prototypes: - uuid: 9247973676c44377a4fa550990384eeb expression: 'last(/APC Smart-UPS SRT 8000 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=3' name: '{#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical' priority: HIGH description: 'The external sensor has returned a value greater than the critical threshold.' - uuid: 6b054505c2704c8d8e38b096885bbbe5 expression: 'last(/APC Smart-UPS SRT 8000 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=4' name: '{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable' priority: INFO description: 'The external sensor does not work or is not connected.' - uuid: f56f165d71084b75a716d04337f5fcb1 expression: 'last(/APC Smart-UPS SRT 8000 SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=2' name: '{#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning' priority: AVERAGE description: 'The external sensor has returned a value greater than the warning threshold.' - uuid: 84af771eee61470d9a61cede04718d88 name: '{#EXTERNAL_SENSOR2_NAME}: Temperature sensor' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.2.6.1.1 key: 'external.sensor.temperature[uioSensorStatusTemperatureDegC.2.{#SNMPINDEX}]' history: 7d value_type: FLOAT units: ℃ description: | MIB: PowerNet-MIB The sensor's current temperature reading in Celsius. -1 indicates an invalid reading due to lost communications. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: Status overrides: - name: Temp step: '1' filter: conditions: - macro: '{#EXTERNAL_SENSOR2_NAME}' value: Temp formulaid: A operations: - operationobject: ITEM_PROTOTYPE operator: LIKE value: Humidity status: ENABLED discover: NO_DISCOVER - uuid: 10363e965d97464a9344baa5fa7a2f53 name: 'Input phases discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#PHASEINDEX},1.3.6.1.4.1.318.1.1.1.9.2.3.1.2.1.1]' key: input.phases.discovery delay: 1h description: 'The input phase identifier. OID upsPhaseInputPhaseIndex.1.1' item_prototypes: - uuid: a275ab18a7064706bf721498ac7c5605 name: '{#PHASEINDEX}: Phase input current' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.9.2.3.1.6.1.1.{#PHASEINDEX}' key: 'phase.input.current[upsPhaseInputCurrent.1.1.{#PHASEINDEX}]' history: 7d value_type: FLOAT units: A description: | MIB: PowerNet-MIB The input current in 0.1 amperes, or -0.1 if it's unsupported by this UPS. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: Status - uuid: 113adf39a65548abab2da39aec20c169 name: '{#PHASEINDEX}: Phase input voltage' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.9.2.3.1.3.1.1.{#PHASEINDEX}' key: 'phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}]' history: 7d value_type: FLOAT units: V description: | MIB: PowerNet-MIB The input voltage in VAC, or -1 if it's unsupported by this UPS. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: Status trigger_prototypes: - uuid: 755f972a32904dbf81a6da77f4ba57f0 expression: 'min(/APC Smart-UPS SRT 8000 SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS SRT 8000 SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}' name: '{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})' opdata: 'Current phase {#PHASEINDEX} voltage: {ITEM.LASTVALUE1}' priority: HIGH - uuid: 0a3159e22ba640e2840789b63bee2bda name: 'Output phases discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#PHASEINDEX},1.3.6.1.4.1.318.1.1.1.9.3.3.1.2.1.1]' key: output.phases.discovery delay: 1h description: 'The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1' item_prototypes: - uuid: 3b625f8ab9f54dca882534d78ee0e584 name: '{#PHASEINDEX}: Phase output current' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.9.3.3.1.4.1.1.{#PHASEINDEX}' key: 'phase.output.current[upsPhaseOutputCurrent.1.1.{#PHASEINDEX}]' history: 7d value_type: FLOAT units: A description: | MIB: PowerNet-MIB The output current in 0.1 amperes drawn by the load on the UPS, or -1 if it's unsupported by this UPS. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: Status - uuid: 99357a267db04c8ca9385aaa15116b79 name: '{#PHASEINDEX}: Phase output load, %' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.9.3.3.1.10.1.1.{#PHASEINDEX}' key: 'phase.output.load.percent[upsPhaseOutputPercentLoad.1.1.{#PHASEINDEX}]' history: 7d value_type: FLOAT units: '%' description: | MIB: PowerNet-MIB The percentage of the UPS load capacity in VA at redundancy @ (n + x) presently being used on this output phase, or -1 if it's unsupported by this UPS. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: Status - uuid: 13315206a94948a09fbb4a9843d2e149 name: '{#PHASEINDEX}: Phase output voltage' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.9.3.3.1.3.1.1.{#PHASEINDEX}' key: 'phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}]' history: 7d value_type: FLOAT units: V description: | MIB: PowerNet-MIB The output voltage in VAC, or -1 if it's unsupported by this UPS. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: Application value: Status trigger_prototypes: - uuid: 5846a7a3d56f43de8394823ed64a11ae expression: 'min(/APC Smart-UPS SRT 8000 SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS SRT 8000 SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}' name: '{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})' opdata: 'Current phase {#PHASEINDEX} voltage: {ITEM.LASTVALUE1}' priority: HIGH macros: - macro: '{$BATTERY.CAPACITY.MIN.WARN}' value: '50' description: 'Minimum battery capacity percentage for trigger expression.' - macro: '{$BATTERY.TEMP.MAX.WARN}' value: '55' description: 'Maximum battery temperature for trigger expression.' - macro: '{$SNMP.TIMEOUT}' value: 5m description: 'The time interval for SNMP agent availability trigger expression.' - macro: '{$TIME.PERIOD}' value: 15m description: 'Time period for trigger expression.' - macro: '{$UPS.INPUT_FREQ.MAX.WARN}' value: '50.3' description: 'Maximum input frequency for trigger expression.' - macro: '{$UPS.INPUT_FREQ.MIN.WARN}' value: '49.7' description: 'Minimum input frequency for trigger expression.' - macro: '{$UPS.INPUT_VOLT.MAX.WARN}' value: '243' description: 'Maximum input voltage for trigger expression.' - macro: '{$UPS.INPUT_VOLT.MIN.WARN}' value: '197' description: 'Minimum input voltage for trigger expression.' - macro: '{$UPS.OUTPUT.MAX.WARN}' value: '80' description: 'Maximum output load in % for trigger expression.' valuemaps: - uuid: 864d59cbfcc8431cb334b812bf7ef3a3 name: 'PowerNet-MIB::uioSensorStatusAlarmStatus' mappings: - value: '1' newvalue: Normal - value: '2' newvalue: Warning - value: '3' newvalue: Critical - value: '4' newvalue: 'Not applicable' - uuid: cc42cb7a7fb4417fa1c143e214958c1d name: 'PowerNet-MIB::upsAdvBatteryReplaceIndicator' mappings: - value: '1' newvalue: 'no Battery Needs Replacing' - value: '2' newvalue: 'battery Needs Replacing' - uuid: a3bbd0be8c7c4dc1aa9accb9f22292c9 name: 'PowerNet-MIB::upsAdvInputLineFailCause' mappings: - value: '1' newvalue: 'no Transfer' - value: '2' newvalue: 'High Line Voltage' - value: '3' newvalue: Brownout - value: '4' newvalue: Blackout - value: '5' newvalue: 'Small Momentary Sag' - value: '6' newvalue: 'Deep Momentary Sag' - value: '7' newvalue: 'Small Momentary Spike' - value: '8' newvalue: 'Large Momentary Spike' - value: '9' newvalue: 'Self Test' - value: '10' newvalue: 'Rate of Voltage Change' - uuid: f801d4fb07c644e4be1f01e99ba48aa7 name: 'PowerNet-MIB::upsBasicBatteryStatus' mappings: - value: '1' newvalue: Unknown - value: '2' newvalue: Normal - value: '3' newvalue: Low - value: '4' newvalue: 'In Fault Condition' - uuid: 28964e9cf2b849fbb2f8d998cecdacda name: 'PowerNet-MIB::upsBasicOutputStatus' mappings: - value: '1' newvalue: Unknown - value: '2' newvalue: Online - value: '3' newvalue: 'On Battery' - value: '4' newvalue: 'On Smart Boost' - value: '5' newvalue: 'Timed Sleeping' - value: '6' newvalue: 'Software Bypass' - value: '7' newvalue: 'Off' - value: '8' newvalue: Rebooting - value: '9' newvalue: 'Switched Bypass' - value: '10' newvalue: 'Hardware Failure Bypass' - value: '11' newvalue: 'Sleeping Until Power Return' - value: '12' newvalue: 'On Smart Trim' - value: '13' newvalue: 'Eco Mode' - value: '14' newvalue: 'Hot Standby' - value: '15' newvalue: 'On Battery Test' - value: '16' newvalue: 'Emergency Static Bypass' - value: '17' newvalue: 'Static Bypass Standby' - value: '18' newvalue: 'Power Saving Mode' - value: '19' newvalue: 'Spot Mode' - value: '20' newvalue: E-Conversion - value: '21' newvalue: 'Charger Spotmode' - value: '22' newvalue: 'Inverter Spotmode' - value: '23' newvalue: 'Active Load' - value: '24' newvalue: 'Battery Discharge Spotmode' - value: '25' newvalue: 'Inverter Standby' - value: '26' newvalue: 'Charger Only' - uuid: 12058346f9e046388767c2939bbed2cf name: zabbix.host.available mappings: - value: '0' newvalue: 'not available' - value: '1' newvalue: available - value: '2' newvalue: unknown graphs: - uuid: e040a4ac7b024c4c878c8145b34969aa name: 'Capacity of the UPS batteries' type: PIE graph_items: - color: 1A7C11 item: host: 'APC Smart-UPS SRT 8000 SNMP' key: 'battery.capacity[upsHighPrecBatteryCapacity]' - uuid: 7cd3c6f5dcaf40e28cbc0ac9e3c35d7a name: Output graph_items: - color: 1A7C11 item: host: 'APC Smart-UPS SRT 8000 SNMP' key: 'output.current[upsHighPrecOutputCurrent]' - sortorder: '1' color: 2774A4 item: host: 'APC Smart-UPS SRT 8000 SNMP' key: 'output.load[upsHighPrecOutputLoad]' - uuid: 2fe4eba0af2745c994ad3d6abfe30140 name: Voltage graph_items: - color: 1A7C11 item: host: 'APC Smart-UPS SRT 8000 SNMP' key: 'input.voltage[upsHighPrecInputLineVoltage]' - sortorder: '1' color: 2774A4 item: host: 'APC Smart-UPS SRT 8000 SNMP' key: 'output.voltage[upsHighPrecOutputVoltage]'