zabbix_export: version: '6.2' date: '2022-04-06T20:01:32Z' groups: - uuid: 3dcd5bbe90534f9e8eb5c2d53756af63 name: Templates/Power templates: - uuid: 0b9a899ff8f1467c9fdf999d02b9fd77 template: 'APC UPS Symmetra LX SNMP' name: 'APC UPS Symmetra LX SNMP' description: | Template Power APC UPS Symmetra LX MIBs used: PowerNet-MIB SNMPv2-MIB You can discuss this template or leave feedback on our forum https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups Template tooling version used: 0.41 groups: - name: Templates/Power items: - uuid: 560d838206844447b8f79fd4500557b2 name: 'Battery capacity' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.3.1.0 key: 'battery.capacity[upsHighPrecBatteryCapacity]' history: 7d value_type: FLOAT units: '%' description: | MIB: PowerNet-MIB The remaining battery capacity expressed as percentage of full capacity. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power triggers: - uuid: fdece80f2fc44ac1974fafe190ce186f expression: 'last(/APC UPS Symmetra LX SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}' name: 'Battery has low capacity' event_name: 'Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%)' opdata: 'Current capacity: {ITEM.LASTVALUE1}' priority: HIGH tags: - tag: scope value: capacity - uuid: 3fea9d328d5342b5bae6b643a0b45495 name: 'External battery packs count' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.2.5.0 key: 'battery.external_packs_count[upsAdvBatteryNumOfBattPacks]' delay: 1h history: 7d description: | MIB: PowerNet-MIB The number of external battery packs connected to the UPS. If the UPS does not use smart cells then the agent reports ERROR_NO_SUCH_NAME. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: inventory - uuid: f4bd3a4a637640e29f50ebd36fb510e5 name: 'Battery last replace date' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.1.3.0 key: 'battery.last_replace_date[upsBasicBatteryLastReplaceDate]' delay: 1h history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB The date when the UPS system's batteries were last replaced in mm/dd/yy (or yyyy) format. For Smart-UPS models, this value is originally set at the factory. When the UPS batteries are replaced, this value should be reset by the administrator. For Symmetra PX 250/500 this OID is read-only and is configurable in the local display only. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: inventory - uuid: 731d350450f742d880d81ff2be69e67e name: 'Battery replace indicator' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.2.4.0 key: 'battery.replace_indicator[upsAdvBatteryReplaceIndicator]' history: 7d description: | MIB: PowerNet-MIB Indicates whether the UPS batteries need replacement. valuemap: name: 'PowerNet-MIB::upsAdvBatteryReplaceIndicator' preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power triggers: - uuid: a1bd434a249b48b2ac0ef69ede417a72 expression: 'last(/APC UPS Symmetra LX SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2' name: 'Battery needs replacement' priority: HIGH description: 'A battery installed has an internal error condition.' tags: - tag: scope value: notice - uuid: 8340b775b76f4e8aad6d3984c63632e9 name: 'Battery runtime remaining' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.2.3.0 key: 'battery.runtime_remaining[upsAdvBatteryRunTimeRemaining]' history: 7d value_type: FLOAT units: s description: | MIB: PowerNet-MIB The UPS battery run time remaining before battery exhaustion. preprocessing: - type: MULTIPLIER parameters: - '0.01' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - uuid: c1d818ee115343c8bb41bedb8de7f2bd name: 'Battery status' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.1.1.0 key: 'battery.status[upsBasicBatteryStatus]' history: 7d description: | MIB: PowerNet-MIB The status of the UPS batteries. A batteryLow(3) value indicates the UPS will be unable to sustain the current load, and its services will be lost if power is not restored. The amount of run time in reserve at the time of low battery can be configured by the upsAdvConfigLowBatteryRunTime. A batteryInFaultCondition(4)value indicates that a battery installed has an internal error condition. valuemap: name: 'PowerNet-MIB::upsBasicBatteryStatus' preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: health - tag: component value: power triggers: - uuid: 955d79a0cf5447dd9a11d4608758e983 expression: 'last(/APC UPS Symmetra LX SNMP/battery.status[upsBasicBatteryStatus])=4' name: 'Battery has an internal error condition' priority: AVERAGE description: 'A battery installed has an internal error condition.' tags: - tag: scope value: notice - uuid: 3ca8156ecc1c4ee4b5623c4a085b993f expression: 'last(/APC UPS Symmetra LX SNMP/battery.status[upsBasicBatteryStatus])=3' name: 'Battery is Low' priority: AVERAGE description: 'The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.' tags: - tag: scope value: capacity - uuid: 6d581eae836342bb8280eb09d7894533 name: 'Battery temperature' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.3.2.0 key: 'battery.temperature[upsHighPrecBatteryTemperature]' history: 7d value_type: FLOAT units: ℃ description: | MIB: PowerNet-MIB The current internal UPS temperature in Celsius. Temperatures below zero read as 0. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: temperature triggers: - uuid: 5b43659a10644a51861282bc72116f9f expression: 'min(/APC UPS Symmetra LX SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}' name: 'Battery has high temperature' event_name: 'Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD})' opdata: 'Current temperature: {ITEM.LASTVALUE1}' priority: HIGH tags: - tag: scope value: notice - uuid: ab0f5d86a40b421ba136506f7854bbbd name: 'Battery voltage' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.3.4.0 key: 'battery.voltage[upsHighPrecBatteryActualVoltage]' history: 7d value_type: FLOAT units: V description: | MIB: PowerNet-MIB The actual battery bus voltage in Volts. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - uuid: 13c0d202d19f4b64a52141062c4be6bb name: 'Input fail cause' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.3.2.5.0 key: 'input.fail[upsAdvInputLineFailCause]' history: 7d description: | MIB: PowerNet-MIB The reason for the occurrence of the last transfer to UPS battery power. The variable is set to: - noTransfer(1) -- if there is no transfer yet. - highLineVoltage(2) -- if the transfer to battery is caused by an over voltage greater than the high transfer voltage. - brownout(3) -- if the duration of the outage is greater than five seconds and the line voltage is between 40% of the rated output voltage and the low transfer voltage. - blackout(4) -- if the duration of the outage is greater than five seconds and the line voltage is between 40% of the rated output voltage and ground. - smallMomentarySag(5) -- if the duration of the outage is less than five seconds and the line voltage is between 40% of the rated output voltage and the low transfer voltage. - deepMomentarySag(6) -- if the duration of the outage is less than five seconds and the line voltage is between 40% of the rated output voltage and ground. The variable is set to - smallMomentarySpike(7) -- if the line failure is caused by a rate of change of input voltage less than ten volts per cycle. - largeMomentarySpike(8) -- if the line failure is caused by a rate of change of input voltage greater than ten volts per cycle. - selfTest(9) -- if the UPS was commanded to do a self test. - rateOfVoltageChange(10) -- if the failure is due to the rate of change of the line voltage. valuemap: name: 'PowerNet-MIB::upsAdvInputLineFailCause' preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - uuid: 05ccf5bd85414ee9b5860c80f6e8323f name: 'Input frequency' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.3.3.4.0 key: 'input.frequency[upsHighPrecInputFrequency]' history: 7d value_type: FLOAT units: Hz description: | MIB: PowerNet-MIB The current input frequency to the UPS system in Hz. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power triggers: - uuid: 94a5c26b89e2416f96b61bbfc6e60a97 expression: 'min(/APC UPS Symmetra LX SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC UPS Symmetra LX SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC UPS Symmetra LX SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})' name: 'Unacceptable input frequency' event_name: 'Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD})' opdata: 'Current frequency: {ITEM.LASTVALUE1}' priority: HIGH tags: - tag: scope value: notice - uuid: 5764182c547143b3b044ec1adb54c1ce name: 'Input voltage' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.3.3.1.0 key: 'input.voltage[upsHighPrecInputLineVoltage]' history: 7d value_type: FLOAT units: V description: | MIB: PowerNet-MIB The current utility line voltage in VAC. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power triggers: - uuid: 2b640b94d48446609802ce6e57c7bd46 expression: 'min(/APC UPS Symmetra LX SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC UPS Symmetra LX SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra LX SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})' name: 'Unacceptable input voltage' event_name: 'Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})' opdata: 'Current voltage: {ITEM.LASTVALUE1}' priority: HIGH tags: - tag: scope value: notice - uuid: bbb33508be95488680bcb644a44626ef name: 'Output current' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.4.3.4.0 key: 'output.current[upsHighPrecOutputCurrent]' history: 7d value_type: FLOAT units: A description: | MIB: PowerNet-MIB The current in amperes drawn by the load on the UPS. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - uuid: d27e991fc0f64b4f9704fb8183567e8d name: 'Output load' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.4.3.3.0 key: 'output.load[upsHighPrecOutputLoad]' history: 7d value_type: FLOAT units: '%' description: | MIB: PowerNet-MIB The current UPS load expressed as percentage of rated capacity. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power triggers: - uuid: 34562b5c734d492c89c386902dfd6e90 expression: 'min(/APC UPS Symmetra LX SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}' name: 'Output load is high' event_name: 'Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD})' opdata: 'Current load: {ITEM.LASTVALUE1}' priority: HIGH description: 'A battery installed has an internal error condition.' tags: - tag: scope value: notice - uuid: 978a7ee6923c40cd8097afb60c81244f name: 'Output status' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.4.1.1.0 key: 'output.status[upsBasicOutputStatus]' history: 7d description: | MIB: PowerNet-MIB The current state of the UPS. If the UPS is unable to determine the state of the UPS this variable is set to unknown(1). During self-test most UPSes report onBattery(3) but some that support it will report onBatteryTest(15). To determine self-test status across all UPSes, refer to the upsBasicStateOutputState OID. valuemap: name: 'PowerNet-MIB::upsBasicOutputStatus' preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: health - tag: component value: power triggers: - uuid: 6ade2b9fb9ad432596d16b3df6237ec4 expression: 'last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=16' name: 'UPS is Emergency Static Bypass' priority: AVERAGE tags: - tag: scope value: notice - uuid: da9a0fa7669e454b8ba44c0458a94ea8 expression: 'last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=10' name: 'UPS is Hardware Failure Bypass' priority: AVERAGE tags: - tag: scope value: notice - uuid: 01a2bcb5f20b4fe889a48e4bed2a2a63 expression: 'last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=7' name: 'UPS is Off' priority: AVERAGE tags: - tag: scope value: notice - uuid: d0b154dd92424af8bb841d91d4e7ddd5 expression: 'last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=3' name: 'UPS is on battery' priority: AVERAGE tags: - tag: scope value: notice - uuid: afc071d0ccfb4226a3c5ee3058270937 expression: 'last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=4' name: 'UPS is on Smart Boost' priority: AVERAGE tags: - tag: scope value: notice - uuid: 12259f4a961a40b39de12d0202d41c56 expression: 'last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=12' name: 'UPS is On Smart Trim' priority: AVERAGE tags: - tag: scope value: notice - uuid: ef9d1e4b1ec244f6bcf36d19a9e7c9c7 expression: 'last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=8' name: 'UPS is Rebooting' priority: AVERAGE tags: - tag: scope value: notice - uuid: c673928e7b764b5db0fa3168edd2cc67 expression: 'last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=11' name: 'UPS is Sleeping Until Power Return' priority: AVERAGE tags: - tag: scope value: notice - uuid: c9b24aa16e124d8c9cd6cfb188ded816 expression: 'last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=6' name: 'UPS is Software Bypass' priority: AVERAGE tags: - tag: scope value: notice - uuid: 02904426801d4d42b3f634267f8697e7 expression: 'last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=9' name: 'UPS is Switched Bypass' priority: AVERAGE tags: - tag: scope value: notice - uuid: fa08f8a60c2c4d88a3f9ebf317fcd06e expression: 'last(/APC UPS Symmetra LX SNMP/output.status[upsBasicOutputStatus])=5' name: 'UPS is Timed Sleeping' priority: AVERAGE tags: - tag: scope value: notice - uuid: 9cf495d14fdf4059b6c35e7857d7a18c name: 'Output voltage' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.4.3.1.0 key: 'output.voltage[upsHighPrecOutputVoltage]' history: 7d value_type: FLOAT units: V description: | MIB: PowerNet-MIB The output voltage of the UPS system in VAC. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - uuid: 102179b315b548e289df3459bc5860c1 name: 'SNMP traps (fallback)' type: SNMP_TRAP key: snmptrap.fallback history: 2w trends: '0' value_type: LOG description: 'The item is used to collect all SNMP traps unmatched by other snmptrap items' logtimefmt: 'hh:mm:sszyyyy/MM/dd' tags: - tag: component value: network - uuid: 8dd800fbbcde431aa421eeb5a33eb798 name: 'System contact details' type: SNMP_AGENT snmp_oid: 1.3.6.1.2.1.1.4.0 key: 'system.contact[sysContact.0]' delay: 15m history: 2w trends: '0' value_type: CHAR description: | MIB: SNMPv2-MIB The textual identification of the contact person for this managed node, together with information on how to contact this person. If no contact information is known, the value is the zero-length string. inventory_link: CONTACT preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 12h tags: - tag: component value: system - uuid: e8c576f27f4c49ef9acd1ba7198ffbb6 name: 'System description' type: SNMP_AGENT snmp_oid: 1.3.6.1.2.1.1.1.0 key: 'system.descr[sysDescr.0]' delay: 15m history: 2w trends: '0' value_type: CHAR description: | MIB: SNMPv2-MIB A textual description of the entity. This value should include the full name and version identification of the system's hardware type, software operating-system, and networking software. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 12h tags: - tag: component value: system - uuid: 6a06715ef4c44534a0ebc45f4e5adb5b name: 'System location' type: SNMP_AGENT snmp_oid: 1.3.6.1.2.1.1.6.0 key: 'system.location[sysLocation.0]' delay: 15m history: 2w trends: '0' value_type: CHAR description: | MIB: SNMPv2-MIB The physical location of this node (e.g., `telephone closet, 3rd floor'). If the location is unknown, the value is the zero-length string. inventory_link: LOCATION preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: system - uuid: 64d56d199021432886452fff5a4c6d22 name: Model type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.1.1.1.0 key: 'system.model[upsBasicIdentModel]' delay: 15m history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB The UPS model name (e.g. 'APC Smart-UPS 600'). preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: inventory - uuid: b15628c68d4c4e8ca761ad9fa7e40a1c name: 'System name' type: SNMP_AGENT snmp_oid: 1.3.6.1.2.1.1.5.0 key: 'system.name[sysName.0]' delay: 15m history: 2w trends: '0' value_type: CHAR description: | MIB: SNMPv2-MIB An administratively-assigned name for this managed node.By convention, this is the node's fully-qualified domain name. If the name is unknown, the value is the zero-length string. inventory_link: NAME preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: system triggers: - uuid: 61d0836efd33437894e1edd595373f1e expression: 'last(/APC UPS Symmetra LX SNMP/system.name[sysName.0],#1)<>last(/APC UPS Symmetra LX SNMP/system.name[sysName.0],#2) and length(last(/APC UPS Symmetra LX SNMP/system.name[sysName.0]))>0' name: 'System name has changed' event_name: 'System name has changed (new name: {ITEM.VALUE})' priority: INFO description: 'System name has changed. Ack to close.' manual_close: 'YES' tags: - tag: scope value: notice - tag: scope value: security - uuid: 9f858f7eaed545b8a35ac24e858b0826 name: 'System object ID' type: SNMP_AGENT snmp_oid: 1.3.6.1.2.1.1.2.0 key: 'system.objectid[sysObjectID.0]' delay: 15m history: 2w trends: '0' value_type: CHAR description: | MIB: SNMPv2-MIB The vendor's authoritative identification of the network management subsystem contained in the entity. This value is allocated within the SMI enterprises subtree (1.3.6.1.4.1) and provides an easy and unambiguous means for determining`what kind of box' is being managed. For example, if vendor`Flintstones, Inc.' was assigned the subtree1.3.6.1.4.1.4242, it could assign the identifier 1.3.6.1.4.1.4242.1.1 to its `Fred Router'. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: system - uuid: 3f61bd561e7d42fbb55b71df9ea3b5b1 name: 'Serial number' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.1.2.3.0 key: 'system.sn[upsAdvIdentSerialNumber]' delay: 15m history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB An 8-character string identifying the serial number of the UPS internal microprocessor. This number is set at the factory. NOTE: This number does NOT correspond to the serial number on the rear of the UPS. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: inventory - uuid: 0810681a8ae74ad8b28ea38119a93f59 name: Uptime type: SNMP_AGENT snmp_oid: 1.3.6.1.2.1.1.3.0 key: 'system.uptime[sysUpTime.0]' delay: 30s history: 2w trends: 0d units: uptime description: | MIB: SNMPv2-MIB The time (in hundredths of a second) since the network management portion of the system was last re-initialized. preprocessing: - type: MULTIPLIER parameters: - '0.01' tags: - tag: component value: system triggers: - uuid: 9d0c32f93c0c44f69b54c91fabfa1529 expression: 'last(/APC UPS Symmetra LX SNMP/system.uptime[sysUpTime.0])<10m' name: 'has been restarted' event_name: '{HOST.NAME} has been restarted (uptime < 10m)' priority: WARNING description: 'Uptime is less than 10 minutes' manual_close: 'YES' dependencies: - name: 'No SNMP data collection' expression: 'max(/APC UPS Symmetra LX SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0' tags: - tag: scope value: notice - uuid: 9562f60b1cbd4fe08614221e69efd811 name: 'SNMP agent availability' type: INTERNAL key: 'zabbix[host,snmp,available]' history: 7d description: | Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list. Possible value: 0 - not available 1 - available 2 - unknown valuemap: name: zabbix.host.available preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: health - tag: component value: network triggers: - uuid: aeaaa7e2bd2d46a481f9d8b33ec18cb5 expression: 'max(/APC UPS Symmetra LX SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0' name: 'No SNMP data collection' opdata: 'Current state: {ITEM.LASTVALUE1}' priority: WARNING description: 'SNMP is not available for polling. Please check device connectivity and SNMP settings.' tags: - tag: scope value: availability discovery_rules: - uuid: 35a885d8f181416db86f2ffe73a30f7f name: 'External bad battery packs discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#EXTERNAL_PACKS},1.3.6.1.4.1.318.1.1.1.2.2.6]' key: battery.packs.bad.discovery delay: 1h description: 'Discovery of the number of external defective battery packs.' item_prototypes: - uuid: b0b3bb219c534b40ad07f89ac8c43797 name: '{#SNMPINDEX}: External battery packs bad' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.2.6.0 key: 'battery.external_packs_bad[upsAdvBatteryNumOfBadBattPacks.{#SNMPINDEX}]' delay: 15m history: 7d description: | MIB: PowerNet-MIB The number of external battery packs connected to the UPS that are defective. If the UPS does not use smart cells then the agent reports ERROR_NO_SUCH_NAME. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: inventory - uuid: 168bfbfc58ca46509caf54ae3562f0bc name: 'External battery packs discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#CARTRIDGE_STATUS},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.7,{#BATTERY_PACK},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.1,{#CARTRIDGE_INDEX},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.2]' key: battery.packs.discovery delay: 1h filter: evaltype: AND conditions: - macro: '{#CARTRIDGE_STATUS}' value: ^$ operator: NOT_MATCHES_REGEX formulaid: A item_prototypes: - uuid: 3d2e62971cfb4b0a92b51ece740e1a58 name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery estimated replace date' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.8.{#SNMPINDEX}' key: 'battery.estimated_replace_date[upsHighPrecBatteryPackCartridgeReplaceDate.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]' delay: 1h history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB The battery cartridge estimated battery replace date. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: inventory - tag: component value: power - uuid: b49b4836472f45e3b4947048dcd64cf8 name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery pack cartridge health' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.7.{#SNMPINDEX}' key: 'battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]' history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB The battery cartridge health. bit 0 Battery lifetime okay bit 1 Battery lifetime near end, order replacement cartridge bit 2 Battery lifetime exceeded, replace battery bit 3 Battery lifetime near end acknowledged, order replacement cartridge bit 4 Battery lifetime exceeded acknowledged, replace battery bit 5 Battery measured lifetime near end, order replacement cartridge bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: health - tag: component value: power trigger_prototypes: - uuid: 2ea1a8d2bd3746dabafed72e1f6216fd expression: 'find(/APC UPS Symmetra LX SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1' name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay' opdata: 'Current bit set: {ITEM.LASTVALUE1}' priority: WARNING description: | The battery cartridge health. bit 0 Battery lifetime okay bit 1 Battery lifetime near end, order replacement cartridge bit 2 Battery lifetime exceeded, replace battery bit 3 Battery lifetime near end acknowledged, order replacement cartridge bit 4 Battery lifetime exceeded acknowledged, replace battery bit 5 Battery measured lifetime near end, order replacement cartridge bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge tags: - tag: scope value: notice - uuid: df73a5fd0d964c67857178a936c2dc7d name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.10.{#SNMPINDEX}' key: 'battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]' history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB The battery cartridge status. bit 0 Disconnected bit 1 Overvoltage bit 2 NeedsReplacement bit 3 OvertemperatureCritical bit 4 Charger bit 5 TemperatureSensor bit 6 BusSoftStart bit 7 OvertemperatureWarning bit 8 GeneralError bit 9 Communication bit 10 DisconnectedFrame bit 11 FirmwareMismatch preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: health - tag: component value: power trigger_prototypes: - uuid: 3870634ad8c1414dabeebc10c510fba3 expression: 'find(/APC UPS Symmetra LX SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0' name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay' opdata: 'Current bit set: {ITEM.LASTVALUE1}' priority: WARNING description: | The battery cartridge status: bit 0 Disconnected bit 1 Overvoltage bit 2 NeedsReplacement bit 3 OvertemperatureCritical bit 4 Charger bit 5 TemperatureSensor bit 6 BusSoftStart bit 7 OvertemperatureWarning bit 8 GeneralError bit 9 Communication bit 10 DisconnectedFrame bit 11 FirmwareMismatch tags: - tag: scope value: notice - uuid: 18c46e7d50ee4eefb669705d62e2224c name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery temperature' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.5.{#SNMPINDEX}' key: 'battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]' history: 7d value_type: FLOAT units: ℃ description: | MIB: PowerNet-MIB The battery pack temperature in Celsius. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: temperature trigger_prototypes: - uuid: 730bdb68d90f4bc6aaf6cb22e04e1845 expression: 'min(/APC UPS Symmetra LX SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}' name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature' event_name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD})' opdata: 'Current temperature: {ITEM.LASTVALUE1}' priority: HIGH tags: - tag: scope value: notice - uuid: 5fadf217f7444f58ba3dca52bc6cff76 name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Serial number' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.4.{#SNMPINDEX}' key: 'system.sn[upsHighPrecBatteryPackSerialNumber.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]' delay: 15m history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB The battery pack serial number. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: inventory - uuid: 598521a7c59d425d9deb58c9829e344e name: 'External sensor port 1 discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#EXTERNAL_SENSOR1_NAME},1.3.6.1.4.1.318.1.1.25.1.2.1.3]' key: external.sensor1.discovery delay: 1h description: uioSensorStatusTable item_prototypes: - uuid: 2db30af657574f8f9390002f94b7e249 name: '{#EXTERNAL_SENSOR1_NAME}: Humidity sensor' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.1.7.1.1 key: 'external.sensor.humidity[uioSensorStatusHumidity.1.{#SNMPINDEX}]' history: 7d value_type: FLOAT units: '%' description: | MIB: PowerNet-MIB The sensor's current humidity reading - a relative humidity percentage. -1 indicates an invalid reading due to either a sensor that doesn't read humidity or lost communications. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: humidity - tag: component value: power - uuid: 6182750c55f24110b076d95c2cdbd1fa name: '{#EXTERNAL_SENSOR1_NAME}: Sensor alarm status' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.1.9.1.1 key: 'external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}]' history: 7d description: | MIB: PowerNet-MIB The alarm status of the sensor. Possible values: uioNormal (1), uioWarning (2), uioCritical (3), sensorStatusNotApplicable (4) valuemap: name: 'PowerNet-MIB::uioSensorStatusAlarmStatus' preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: health - tag: component value: power trigger_prototypes: - uuid: 97b4078788d244d0b501e9465c659ff7 expression: 'last(/APC UPS Symmetra LX SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=3' name: '{#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical' priority: HIGH description: 'The external sensor has returned a value greater than the critical threshold.' tags: - tag: scope value: notice - uuid: 86cd9908372045618672d6ff82bca705 expression: 'last(/APC UPS Symmetra LX SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4' name: '{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable' priority: INFO description: 'The external sensor does not work or is not connected.' tags: - tag: scope value: notice - uuid: 4ba13efc27da411785410109340b6a26 expression: 'last(/APC UPS Symmetra LX SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2' name: '{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning' priority: AVERAGE description: 'The external sensor has returned a value greater than the warning threshold.' tags: - tag: scope value: notice - uuid: fc394520f4964a86ac93e87da2fc541b name: '{#EXTERNAL_SENSOR1_NAME}: Temperature sensor' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.1.6.1.1 key: 'external.sensor.temperature[uioSensorStatusTemperatureDegC.1.{#SNMPINDEX}]' history: 7d value_type: FLOAT units: ℃ description: | MIB: PowerNet-MIB The sensor's current temperature reading in Celsius. -1 indicates an invalid reading due to lost communications. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - tag: component value: temperature overrides: - name: Temp step: '1' filter: conditions: - macro: '{#EXTERNAL_SENSOR1_NAME}' value: Temp formulaid: A operations: - operationobject: ITEM_PROTOTYPE operator: LIKE value: Humidity status: ENABLED discover: NO_DISCOVER - uuid: 14e6acae826e4e87b68c04beee67a5cb name: 'External sensor port 2 discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#EXTERNAL_SENSOR2_NAME},1.3.6.1.4.1.318.1.1.25.1.2.2.3]' key: external.sensor2.discovery delay: 1h description: uioSensorStatusTable item_prototypes: - uuid: 5f5df15d6cc4455083f9fa6932d86656 name: '{#EXTERNAL_SENSOR2_NAME}: Humidity sensor' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.2.7.1.1 key: 'external.sensor.humidity[uioSensorStatusHumidity.2.{#SNMPINDEX}]' history: 7d value_type: FLOAT units: '%' description: | MIB: PowerNet-MIB The sensor's current humidity reading - a relative humidity percentage. -1 indicates an invalid reading due to either a sensor that doesn't read humidity or lost communications. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: humidity - tag: component value: power - uuid: ecc2e5c49b004027bb9ccd5498e3d169 name: '{#EXTERNAL_SENSOR2_NAME}: Sensor alarm status' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.2.9.1.1 key: 'external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}]' history: 7d description: | MIB: PowerNet-MIB The alarm status of the sensor. Possible values: uioNormal (1), uioWarning (2), uioCritical (3), sensorStatusNotApplicable (4) valuemap: name: 'PowerNet-MIB::uioSensorStatusAlarmStatus' preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: health - tag: component value: power trigger_prototypes: - uuid: 3155c8cf446c40d896755a25a46ec90b expression: 'last(/APC UPS Symmetra LX SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=3' name: '{#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical' priority: HIGH description: 'The external sensor has returned a value greater than the critical threshold.' tags: - tag: scope value: notice - uuid: 9ef9a4dc80c84087b44b5f0e8aa94202 expression: 'last(/APC UPS Symmetra LX SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=4' name: '{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable' priority: INFO description: 'The external sensor does not work or is not connected.' tags: - tag: scope value: notice - uuid: 74a3585b0cc74a4887eb3683fb1e6f64 expression: 'last(/APC UPS Symmetra LX SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=2' name: '{#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning' priority: AVERAGE description: 'The external sensor has returned a value greater than the warning threshold.' tags: - tag: scope value: notice - uuid: f2cd5bb0c8a64b09868ddff9b14e4cbd name: '{#EXTERNAL_SENSOR2_NAME}: Temperature sensor' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.2.6.1.1 key: 'external.sensor.temperature[uioSensorStatusTemperatureDegC.2.{#SNMPINDEX}]' history: 7d value_type: FLOAT units: ℃ description: | MIB: PowerNet-MIB The sensor's current temperature reading in Celsius. -1 indicates an invalid reading due to lost communications. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - tag: component value: temperature overrides: - name: Temp step: '1' filter: conditions: - macro: '{#EXTERNAL_SENSOR2_NAME}' value: Temp formulaid: A operations: - operationobject: ITEM_PROTOTYPE operator: LIKE value: Humidity status: ENABLED discover: NO_DISCOVER - uuid: b4f271299e9a47bf8543863a7d9be479 name: 'Input phases discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#PHASEINDEX},1.3.6.1.4.1.318.1.1.1.9.2.3.1.2.1.1]' key: input.phases.discovery delay: 1h description: 'The input phase identifier. OID upsPhaseInputPhaseIndex.1.1' item_prototypes: - uuid: 161257625bc84427be6cfcd86023c2ec name: '{#PHASEINDEX}: Phase input current' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.9.2.3.1.6.1.1.{#PHASEINDEX}' key: 'phase.input.current[upsPhaseInputCurrent.1.1.{#PHASEINDEX}]' history: 7d value_type: FLOAT units: A description: | MIB: PowerNet-MIB The input current in 0.1 amperes, or -0.1 if it's unsupported by this UPS. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - uuid: 080719150b424168999c21ff597e6948 name: '{#PHASEINDEX}: Phase input voltage' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.9.2.3.1.3.1.1.{#PHASEINDEX}' key: 'phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}]' history: 7d value_type: FLOAT units: V description: | MIB: PowerNet-MIB The input voltage in VAC, or -1 if it's unsupported by this UPS. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power trigger_prototypes: - uuid: 90e3258375e047b594deb0ecf7300c22 expression: 'min(/APC UPS Symmetra LX SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra LX SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}' name: '{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage' event_name: '{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})' opdata: 'Current phase {#PHASEINDEX} voltage: {ITEM.LASTVALUE1}' priority: HIGH tags: - tag: scope value: notice - uuid: 4232ad35daa3403da085f1ba6c7af348 name: 'Output phases discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#PHASEINDEX},1.3.6.1.4.1.318.1.1.1.9.3.3.1.2.1.1]' key: output.phases.discovery delay: 1h description: 'The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1' item_prototypes: - uuid: 2834306ba5464ffaa472c0adddc3d829 name: '{#PHASEINDEX}: Phase output current' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.9.3.3.1.4.1.1.{#PHASEINDEX}' key: 'phase.output.current[upsPhaseOutputCurrent.1.1.{#PHASEINDEX}]' history: 7d value_type: FLOAT units: A description: | MIB: PowerNet-MIB The output current in 0.1 amperes drawn by the load on the UPS, or -1 if it's unsupported by this UPS. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - uuid: 7b0f22672b38492e92c8551c3009baef name: '{#PHASEINDEX}: Phase output load, %' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.9.3.3.1.10.1.1.{#PHASEINDEX}' key: 'phase.output.load.percent[upsPhaseOutputPercentLoad.1.1.{#PHASEINDEX}]' history: 7d value_type: FLOAT units: '%' description: | MIB: PowerNet-MIB The percentage of the UPS load capacity in VA at redundancy @ (n + x) presently being used on this output phase, or -1 if it's unsupported by this UPS. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - uuid: a590ab8671574e119fe3335110fdee49 name: '{#PHASEINDEX}: Phase output voltage' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.9.3.3.1.3.1.1.{#PHASEINDEX}' key: 'phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}]' history: 7d value_type: FLOAT units: V description: | MIB: PowerNet-MIB The output voltage in VAC, or -1 if it's unsupported by this UPS. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power trigger_prototypes: - uuid: b8c42d5d66d9403eba697920439ae956 expression: 'min(/APC UPS Symmetra LX SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra LX SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}' name: '{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage' event_name: '{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})' opdata: 'Current phase {#PHASEINDEX} voltage: {ITEM.LASTVALUE1}' priority: HIGH tags: - tag: scope value: notice tags: - tag: class value: power - tag: target value: apc - tag: target value: apc-ups-symmetra-lx macros: - macro: '{$BATTERY.CAPACITY.MIN.WARN}' value: '50' description: 'Minimum battery capacity percentage for trigger expression.' - macro: '{$BATTERY.TEMP.MAX.WARN}' value: '55' description: 'Maximum battery temperature for trigger expression.' - macro: '{$SNMP.TIMEOUT}' value: 5m description: 'The time interval for SNMP agent availability trigger expression.' - macro: '{$TIME.PERIOD}' value: 15m description: 'Time period for trigger expression.' - macro: '{$UPS.INPUT_FREQ.MAX.WARN}' value: '50.3' description: 'Maximum input frequency for trigger expression.' - macro: '{$UPS.INPUT_FREQ.MIN.WARN}' value: '49.7' description: 'Minimum input frequency for trigger expression.' - macro: '{$UPS.INPUT_VOLT.MAX.WARN}' value: '243' description: 'Maximum input voltage for trigger expression.' - macro: '{$UPS.INPUT_VOLT.MIN.WARN}' value: '197' description: 'Minimum input voltage for trigger expression.' - macro: '{$UPS.OUTPUT.MAX.WARN}' value: '80' description: 'Maximum output load in % for trigger expression.' dashboards: - uuid: fbf5cb79251d48bdbe4bc7b81dbd2d65 name: 'UPS Summary' pages: - widgets: - type: PLAIN_TEXT width: '8' fields: - type: INTEGER name: show_as_html value: '0' - type: INTEGER name: show_lines value: '1' - type: ITEM name: itemids value: key: 'system.uptime[sysUpTime.0]' host: 'APC UPS Symmetra LX SNMP' - type: PLAIN_TEXT x: '8' width: '8' fields: - type: INTEGER name: show_as_html value: '0' - type: INTEGER name: show_lines value: '1' - type: ITEM name: itemids value: key: 'input.fail[upsAdvInputLineFailCause]' host: 'APC UPS Symmetra LX SNMP' - type: PLAIN_TEXT x: '16' width: '8' fields: - type: INTEGER name: show_as_html value: '0' - type: INTEGER name: show_lines value: '1' - type: ITEM name: itemids value: key: 'output.status[upsBasicOutputStatus]' host: 'APC UPS Symmetra LX SNMP' - type: PLAIN_TEXT 'y': '2' width: '8' fields: - type: INTEGER name: show_as_html value: '0' - type: INTEGER name: show_lines value: '1' - type: ITEM name: itemids value: key: 'battery.status[upsBasicBatteryStatus]' host: 'APC UPS Symmetra LX SNMP' - type: PLAIN_TEXT x: '8' 'y': '2' width: '8' fields: - type: INTEGER name: show_as_html value: '0' - type: INTEGER name: show_lines value: '1' - type: ITEM name: itemids value: key: 'battery.runtime_remaining[upsAdvBatteryRunTimeRemaining]' host: 'APC UPS Symmetra LX SNMP' - type: PLAIN_TEXT x: '16' 'y': '2' width: '8' fields: - type: INTEGER name: show_as_html value: '0' - type: INTEGER name: show_lines value: '1' - type: ITEM name: itemids value: key: 'battery.last_replace_date[upsBasicBatteryLastReplaceDate]' host: 'APC UPS Symmetra LX SNMP' - type: GRAPH_CLASSIC 'y': '4' width: '8' height: '7' fields: - type: INTEGER name: source_type value: '0' - type: GRAPH name: graphid value: name: 'Capacity of the UPS batteries' host: 'APC UPS Symmetra LX SNMP' - type: GRAPH_CLASSIC x: '8' 'y': '4' width: '8' height: '7' fields: - type: INTEGER name: source_type value: '0' - type: GRAPH name: graphid value: name: Voltage host: 'APC UPS Symmetra LX SNMP' - type: GRAPH_CLASSIC x: '16' 'y': '4' width: '8' height: '7' fields: - type: INTEGER name: source_type value: '0' - type: GRAPH name: graphid value: name: Output host: 'APC UPS Symmetra LX SNMP' valuemaps: - uuid: aec3362485c242ec928cb8ecfe5e61cf name: 'PowerNet-MIB::uioSensorStatusAlarmStatus' mappings: - value: '1' newvalue: Normal - value: '2' newvalue: Warning - value: '3' newvalue: Critical - value: '4' newvalue: 'Not applicable' - uuid: 912d8834176b4fe4a2f6bd12ef3ee3c1 name: 'PowerNet-MIB::upsAdvBatteryReplaceIndicator' mappings: - value: '1' newvalue: 'no Battery Needs Replacing' - value: '2' newvalue: 'battery Needs Replacing' - uuid: e079fa8cc9614245b0fecf4b8f42feca name: 'PowerNet-MIB::upsAdvInputLineFailCause' mappings: - value: '1' newvalue: 'no Transfer' - value: '2' newvalue: 'High Line Voltage' - value: '3' newvalue: Brownout - value: '4' newvalue: Blackout - value: '5' newvalue: 'Small Momentary Sag' - value: '6' newvalue: 'Deep Momentary Sag' - value: '7' newvalue: 'Small Momentary Spike' - value: '8' newvalue: 'Large Momentary Spike' - value: '9' newvalue: 'Self Test' - value: '10' newvalue: 'Rate of Voltage Change' - uuid: 24229472978c42739cdbe7aa47e1d34c name: 'PowerNet-MIB::upsBasicBatteryStatus' mappings: - value: '1' newvalue: Unknown - value: '2' newvalue: Normal - value: '3' newvalue: Low - value: '4' newvalue: 'In Fault Condition' - uuid: 8c2c9721615c4408976f7632180ecfe3 name: 'PowerNet-MIB::upsBasicOutputStatus' mappings: - value: '1' newvalue: Unknown - value: '2' newvalue: Online - value: '3' newvalue: 'On Battery' - value: '4' newvalue: 'On Smart Boost' - value: '5' newvalue: 'Timed Sleeping' - value: '6' newvalue: 'Software Bypass' - value: '7' newvalue: 'Off' - value: '8' newvalue: Rebooting - value: '9' newvalue: 'Switched Bypass' - value: '10' newvalue: 'Hardware Failure Bypass' - value: '11' newvalue: 'Sleeping Until Power Return' - value: '12' newvalue: 'On Smart Trim' - value: '13' newvalue: 'Eco Mode' - value: '14' newvalue: 'Hot Standby' - value: '15' newvalue: 'On Battery Test' - value: '16' newvalue: 'Emergency Static Bypass' - value: '17' newvalue: 'Static Bypass Standby' - value: '18' newvalue: 'Power Saving Mode' - value: '19' newvalue: 'Spot Mode' - value: '20' newvalue: E-Conversion - value: '21' newvalue: 'Charger Spotmode' - value: '22' newvalue: 'Inverter Spotmode' - value: '23' newvalue: 'Active Load' - value: '24' newvalue: 'Battery Discharge Spotmode' - value: '25' newvalue: 'Inverter Standby' - value: '26' newvalue: 'Charger Only' - uuid: 625f28bd49f14e49a1a7a4da01429906 name: zabbix.host.available mappings: - value: '0' newvalue: 'not available' - value: '1' newvalue: available - value: '2' newvalue: unknown graphs: - uuid: 265f3050b3b94cbeae6fefdae02ea992 name: 'Capacity of the UPS batteries' type: PIE graph_items: - color: 1A7C11 item: host: 'APC UPS Symmetra LX SNMP' key: 'battery.capacity[upsHighPrecBatteryCapacity]' - uuid: 2ef61780d42c4d61bcb89faf08691d08 name: Output graph_items: - color: 1A7C11 item: host: 'APC UPS Symmetra LX SNMP' key: 'output.current[upsHighPrecOutputCurrent]' - sortorder: '1' color: 2774A4 item: host: 'APC UPS Symmetra LX SNMP' key: 'output.load[upsHighPrecOutputLoad]' - uuid: 4432ed7ca97d4d989b253383037f48ee name: Voltage graph_items: - color: 1A7C11 item: host: 'APC UPS Symmetra LX SNMP' key: 'input.voltage[upsHighPrecInputLineVoltage]' - sortorder: '1' color: 2774A4 item: host: 'APC UPS Symmetra LX SNMP' key: 'output.voltage[upsHighPrecOutputVoltage]'