zabbix_export: version: '6.2' date: '2022-04-06T20:01:33Z' groups: - uuid: 3dcd5bbe90534f9e8eb5c2d53756af63 name: Templates/Power templates: - uuid: 1dac0a88c3774315b90622a48031e369 template: 'APC UPS Symmetra RM SNMP' name: 'APC UPS Symmetra RM SNMP' description: | Template Power APC UPS Symmetra RM MIBs used: PowerNet-MIB SNMPv2-MIB You can discuss this template or leave feedback on our forum https://www.zabbix.com/forum/zabbix-suggestions-and-feedback/420730-discussion-thread-for-official-zabbix-template-apc-ups Template tooling version used: 0.41 groups: - name: Templates/Power items: - uuid: e8257d78c2e24e3cb152886d39bca4fe name: 'Battery capacity' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.3.1.0 key: 'battery.capacity[upsHighPrecBatteryCapacity]' history: 7d value_type: FLOAT units: '%' description: | MIB: PowerNet-MIB The remaining battery capacity expressed as percentage of full capacity. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power triggers: - uuid: dbfdc4e6eaca4d65adcde13b0682c1c2 expression: 'last(/APC UPS Symmetra RM SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}' name: 'Battery has low capacity' event_name: 'Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%)' opdata: 'Current capacity: {ITEM.LASTVALUE1}' priority: HIGH tags: - tag: scope value: capacity - uuid: d26227e3d5754d8493ddaa9c3f5f2b5a name: 'External battery packs count' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.2.5.0 key: 'battery.external_packs_count[upsAdvBatteryNumOfBattPacks]' delay: 1h history: 7d description: | MIB: PowerNet-MIB The number of external battery packs connected to the UPS. If the UPS does not use smart cells then the agent reports ERROR_NO_SUCH_NAME. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: inventory - uuid: 138afef586634623974c1cefd45281e9 name: 'Battery last replace date' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.1.3.0 key: 'battery.last_replace_date[upsBasicBatteryLastReplaceDate]' delay: 1h history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB The date when the UPS system's batteries were last replaced in mm/dd/yy (or yyyy) format. For Smart-UPS models, this value is originally set at the factory. When the UPS batteries are replaced, this value should be reset by the administrator. For Symmetra PX 250/500 this OID is read-only and is configurable in the local display only. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: inventory - uuid: abb901813d91481baef234496ddece33 name: 'Battery replace indicator' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.2.4.0 key: 'battery.replace_indicator[upsAdvBatteryReplaceIndicator]' history: 7d description: | MIB: PowerNet-MIB Indicates whether the UPS batteries need replacement. valuemap: name: 'PowerNet-MIB::upsAdvBatteryReplaceIndicator' preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power triggers: - uuid: 0af287bae1ee44ba997a02ae585bdd4b expression: 'last(/APC UPS Symmetra RM SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2' name: 'Battery needs replacement' priority: HIGH description: 'A battery installed has an internal error condition.' tags: - tag: scope value: notice - uuid: 80a4e6cf09a147a7b166755aa182fdcd name: 'Battery runtime remaining' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.2.3.0 key: 'battery.runtime_remaining[upsAdvBatteryRunTimeRemaining]' history: 7d value_type: FLOAT units: s description: | MIB: PowerNet-MIB The UPS battery run time remaining before battery exhaustion. preprocessing: - type: MULTIPLIER parameters: - '0.01' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - uuid: 322c3b48bcb74fa5829ef41015308d97 name: 'Battery status' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.1.1.0 key: 'battery.status[upsBasicBatteryStatus]' history: 7d description: | MIB: PowerNet-MIB The status of the UPS batteries. A batteryLow(3) value indicates the UPS will be unable to sustain the current load, and its services will be lost if power is not restored. The amount of run time in reserve at the time of low battery can be configured by the upsAdvConfigLowBatteryRunTime. A batteryInFaultCondition(4)value indicates that a battery installed has an internal error condition. valuemap: name: 'PowerNet-MIB::upsBasicBatteryStatus' preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: health - tag: component value: power triggers: - uuid: aedb557acbe44390809a27b95919e10f expression: 'last(/APC UPS Symmetra RM SNMP/battery.status[upsBasicBatteryStatus])=4' name: 'Battery has an internal error condition' priority: AVERAGE description: 'A battery installed has an internal error condition.' tags: - tag: scope value: notice - uuid: 1afe1859563f481faa623781028a38ca expression: 'last(/APC UPS Symmetra RM SNMP/battery.status[upsBasicBatteryStatus])=3' name: 'Battery is Low' priority: AVERAGE description: 'The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.' tags: - tag: scope value: capacity - uuid: 17ffb34351da46e59d2288cd291a7912 name: 'Battery temperature' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.3.2.0 key: 'battery.temperature[upsHighPrecBatteryTemperature]' history: 7d value_type: FLOAT units: ℃ description: | MIB: PowerNet-MIB The current internal UPS temperature in Celsius. Temperatures below zero read as 0. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: temperature triggers: - uuid: 0b4490eaaf964fdabf228d34d2992d30 expression: 'min(/APC UPS Symmetra RM SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}' name: 'Battery has high temperature' event_name: 'Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD})' opdata: 'Current temperature: {ITEM.LASTVALUE1}' priority: HIGH tags: - tag: scope value: notice - uuid: 9ab2309be6cc4eea8697f17e80b015d8 name: 'Battery voltage' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.3.4.0 key: 'battery.voltage[upsHighPrecBatteryActualVoltage]' history: 7d value_type: FLOAT units: V description: | MIB: PowerNet-MIB The actual battery bus voltage in Volts. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - uuid: 439c87539027462c9b8210a056887885 name: 'Input fail cause' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.3.2.5.0 key: 'input.fail[upsAdvInputLineFailCause]' history: 7d description: | MIB: PowerNet-MIB The reason for the occurrence of the last transfer to UPS battery power. The variable is set to: - noTransfer(1) -- if there is no transfer yet. - highLineVoltage(2) -- if the transfer to battery is caused by an over voltage greater than the high transfer voltage. - brownout(3) -- if the duration of the outage is greater than five seconds and the line voltage is between 40% of the rated output voltage and the low transfer voltage. - blackout(4) -- if the duration of the outage is greater than five seconds and the line voltage is between 40% of the rated output voltage and ground. - smallMomentarySag(5) -- if the duration of the outage is less than five seconds and the line voltage is between 40% of the rated output voltage and the low transfer voltage. - deepMomentarySag(6) -- if the duration of the outage is less than five seconds and the line voltage is between 40% of the rated output voltage and ground. The variable is set to - smallMomentarySpike(7) -- if the line failure is caused by a rate of change of input voltage less than ten volts per cycle. - largeMomentarySpike(8) -- if the line failure is caused by a rate of change of input voltage greater than ten volts per cycle. - selfTest(9) -- if the UPS was commanded to do a self test. - rateOfVoltageChange(10) -- if the failure is due to the rate of change of the line voltage. valuemap: name: 'PowerNet-MIB::upsAdvInputLineFailCause' preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - uuid: e16be6095dc24b48bc541325b1675dd0 name: 'Input frequency' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.3.3.4.0 key: 'input.frequency[upsHighPrecInputFrequency]' history: 7d value_type: FLOAT units: Hz description: | MIB: PowerNet-MIB The current input frequency to the UPS system in Hz. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power triggers: - uuid: af166242e3674f2da489a232c7bba6f1 expression: 'min(/APC UPS Symmetra RM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC UPS Symmetra RM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC UPS Symmetra RM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})' name: 'Unacceptable input frequency' event_name: 'Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD})' opdata: 'Current frequency: {ITEM.LASTVALUE1}' priority: HIGH tags: - tag: scope value: notice - uuid: c658b02eea284fcf8e302c20a2256cf0 name: 'Input voltage' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.3.3.1.0 key: 'input.voltage[upsHighPrecInputLineVoltage]' history: 7d value_type: FLOAT units: V description: | MIB: PowerNet-MIB The current utility line voltage in VAC. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power triggers: - uuid: 3b51bbae66914b19a93e7a2da289b056 expression: 'min(/APC UPS Symmetra RM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC UPS Symmetra RM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra RM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})' name: 'Unacceptable input voltage' event_name: 'Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})' opdata: 'Current voltage: {ITEM.LASTVALUE1}' priority: HIGH tags: - tag: scope value: notice - uuid: 9bcae00165414f4aa15a40bc078aa44d name: 'Output current' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.4.3.4.0 key: 'output.current[upsHighPrecOutputCurrent]' history: 7d value_type: FLOAT units: A description: | MIB: PowerNet-MIB The current in amperes drawn by the load on the UPS. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - uuid: 0e5240e578d043609fba4024db8c8df1 name: 'Output load' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.4.3.3.0 key: 'output.load[upsHighPrecOutputLoad]' history: 7d value_type: FLOAT units: '%' description: | MIB: PowerNet-MIB The current UPS load expressed as percentage of rated capacity. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power triggers: - uuid: a25499c49d0043cda248136eb6307ef9 expression: 'min(/APC UPS Symmetra RM SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}' name: 'Output load is high' event_name: 'Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD})' opdata: 'Current load: {ITEM.LASTVALUE1}' priority: HIGH description: 'A battery installed has an internal error condition.' tags: - tag: scope value: notice - uuid: 7655b8ff3d5e41f0a5409fcfd646933a name: 'Output status' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.4.1.1.0 key: 'output.status[upsBasicOutputStatus]' history: 7d description: | MIB: PowerNet-MIB The current state of the UPS. If the UPS is unable to determine the state of the UPS this variable is set to unknown(1). During self-test most UPSes report onBattery(3) but some that support it will report onBatteryTest(15). To determine self-test status across all UPSes, refer to the upsBasicStateOutputState OID. valuemap: name: 'PowerNet-MIB::upsBasicOutputStatus' preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: health - tag: component value: power triggers: - uuid: f7b0e2f05c9b4b14916f99ecb89fcd49 expression: 'last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=16' name: 'UPS is Emergency Static Bypass' priority: AVERAGE tags: - tag: scope value: notice - uuid: 77081726414047a5a1c698fcfbf19e73 expression: 'last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=10' name: 'UPS is Hardware Failure Bypass' priority: AVERAGE tags: - tag: scope value: notice - uuid: 87beb54ac57848e3896fd715a5918a88 expression: 'last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=7' name: 'UPS is Off' priority: AVERAGE tags: - tag: scope value: notice - uuid: 5f46c436fab741ec86cb32339e8bd7b4 expression: 'last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=3' name: 'UPS is on battery' priority: AVERAGE tags: - tag: scope value: notice - uuid: a7457e3d6c6f4e99a3ccc08a1436d34a expression: 'last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=4' name: 'UPS is on Smart Boost' priority: AVERAGE tags: - tag: scope value: notice - uuid: 976395b6acea4f5cb4f7f3d4f0bc67af expression: 'last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=12' name: 'UPS is On Smart Trim' priority: AVERAGE tags: - tag: scope value: notice - uuid: 72c9677a2157412ebd14004a5e024a3a expression: 'last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=8' name: 'UPS is Rebooting' priority: AVERAGE tags: - tag: scope value: notice - uuid: 75d189cd8b5944c4b7987931c834e949 expression: 'last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=11' name: 'UPS is Sleeping Until Power Return' priority: AVERAGE tags: - tag: scope value: notice - uuid: 24e1cfde22da48b0bf28ca2cdf8cd917 expression: 'last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=6' name: 'UPS is Software Bypass' priority: AVERAGE tags: - tag: scope value: notice - uuid: 4fff7b4a29b84cdea245b2704e357f5d expression: 'last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=9' name: 'UPS is Switched Bypass' priority: AVERAGE tags: - tag: scope value: notice - uuid: 647178a4cb674815a65517c073b4adee expression: 'last(/APC UPS Symmetra RM SNMP/output.status[upsBasicOutputStatus])=5' name: 'UPS is Timed Sleeping' priority: AVERAGE tags: - tag: scope value: notice - uuid: 8d93b482d7c549f593c41abb9380ce2f name: 'Output voltage' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.4.3.1.0 key: 'output.voltage[upsHighPrecOutputVoltage]' history: 7d value_type: FLOAT units: V description: | MIB: PowerNet-MIB The output voltage of the UPS system in VAC. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - uuid: 39dd21c0f2194acaa9fddbdfccde05dd name: 'SNMP traps (fallback)' type: SNMP_TRAP key: snmptrap.fallback history: 2w trends: '0' value_type: LOG description: 'The item is used to collect all SNMP traps unmatched by other snmptrap items' logtimefmt: 'hh:mm:sszyyyy/MM/dd' tags: - tag: component value: network - uuid: 2d22b58a5c9f4fedbd03862398113546 name: 'System contact details' type: SNMP_AGENT snmp_oid: 1.3.6.1.2.1.1.4.0 key: 'system.contact[sysContact.0]' delay: 15m history: 2w trends: '0' value_type: CHAR description: | MIB: SNMPv2-MIB The textual identification of the contact person for this managed node, together with information on how to contact this person. If no contact information is known, the value is the zero-length string. inventory_link: CONTACT preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 12h tags: - tag: component value: system - uuid: 251cc61592f543e3929aef3cb46f1b34 name: 'System description' type: SNMP_AGENT snmp_oid: 1.3.6.1.2.1.1.1.0 key: 'system.descr[sysDescr.0]' delay: 15m history: 2w trends: '0' value_type: CHAR description: | MIB: SNMPv2-MIB A textual description of the entity. This value should include the full name and version identification of the system's hardware type, software operating-system, and networking software. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 12h tags: - tag: component value: system - uuid: 49b8ef5ff3a3400d8f412d4440040461 name: 'System location' type: SNMP_AGENT snmp_oid: 1.3.6.1.2.1.1.6.0 key: 'system.location[sysLocation.0]' delay: 15m history: 2w trends: '0' value_type: CHAR description: | MIB: SNMPv2-MIB The physical location of this node (e.g., `telephone closet, 3rd floor'). If the location is unknown, the value is the zero-length string. inventory_link: LOCATION preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: system - uuid: bd0dc104ded94e4cbba3a8557e642caf name: Model type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.1.1.1.0 key: 'system.model[upsBasicIdentModel]' delay: 15m history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB The UPS model name (e.g. 'APC Smart-UPS 600'). preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: inventory - uuid: 155feccece4a4625b98efa206ad5e0b1 name: 'System name' type: SNMP_AGENT snmp_oid: 1.3.6.1.2.1.1.5.0 key: 'system.name[sysName.0]' delay: 15m history: 2w trends: '0' value_type: CHAR description: | MIB: SNMPv2-MIB An administratively-assigned name for this managed node.By convention, this is the node's fully-qualified domain name. If the name is unknown, the value is the zero-length string. inventory_link: NAME preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: system triggers: - uuid: e3cf119c19b54dddb3d26d9b789ea4f5 expression: 'last(/APC UPS Symmetra RM SNMP/system.name[sysName.0],#1)<>last(/APC UPS Symmetra RM SNMP/system.name[sysName.0],#2) and length(last(/APC UPS Symmetra RM SNMP/system.name[sysName.0]))>0' name: 'System name has changed' event_name: 'System name has changed (new name: {ITEM.VALUE})' priority: INFO description: 'System name has changed. Ack to close.' manual_close: 'YES' tags: - tag: scope value: notice - tag: scope value: security - uuid: f6bd69ea5df144c996f050ded122521e name: 'System object ID' type: SNMP_AGENT snmp_oid: 1.3.6.1.2.1.1.2.0 key: 'system.objectid[sysObjectID.0]' delay: 15m history: 2w trends: '0' value_type: CHAR description: | MIB: SNMPv2-MIB The vendor's authoritative identification of the network management subsystem contained in the entity. This value is allocated within the SMI enterprises subtree (1.3.6.1.4.1) and provides an easy and unambiguous means for determining`what kind of box' is being managed. For example, if vendor`Flintstones, Inc.' was assigned the subtree1.3.6.1.4.1.4242, it could assign the identifier 1.3.6.1.4.1.4242.1.1 to its `Fred Router'. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: system - uuid: 64ab7fd8a79448d580ad24ecf488241c name: 'Serial number' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.1.2.3.0 key: 'system.sn[upsAdvIdentSerialNumber]' delay: 15m history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB An 8-character string identifying the serial number of the UPS internal microprocessor. This number is set at the factory. NOTE: This number does NOT correspond to the serial number on the rear of the UPS. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: inventory - uuid: b4ca2f993709413b9a00fa1389ec9e3c name: Uptime type: SNMP_AGENT snmp_oid: 1.3.6.1.2.1.1.3.0 key: 'system.uptime[sysUpTime.0]' delay: 30s history: 2w trends: 0d units: uptime description: | MIB: SNMPv2-MIB The time (in hundredths of a second) since the network management portion of the system was last re-initialized. preprocessing: - type: MULTIPLIER parameters: - '0.01' tags: - tag: component value: system triggers: - uuid: fb2b4e564040422da234cdb309163b7b expression: 'last(/APC UPS Symmetra RM SNMP/system.uptime[sysUpTime.0])<10m' name: 'has been restarted' event_name: '{HOST.NAME} has been restarted (uptime < 10m)' priority: WARNING description: 'Uptime is less than 10 minutes' manual_close: 'YES' dependencies: - name: 'No SNMP data collection' expression: 'max(/APC UPS Symmetra RM SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0' tags: - tag: scope value: notice - uuid: d69889a19b564ed384fc96e8a70971a5 name: 'SNMP agent availability' type: INTERNAL key: 'zabbix[host,snmp,available]' history: 7d description: | Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list. Possible value: 0 - not available 1 - available 2 - unknown valuemap: name: zabbix.host.available preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: health - tag: component value: network triggers: - uuid: 56f25581382a43efbddd4aba44aa86b3 expression: 'max(/APC UPS Symmetra RM SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0' name: 'No SNMP data collection' opdata: 'Current state: {ITEM.LASTVALUE1}' priority: WARNING description: 'SNMP is not available for polling. Please check device connectivity and SNMP settings.' tags: - tag: scope value: availability discovery_rules: - uuid: 82e8f10c883546ef8196e071fdd8df91 name: 'External bad battery packs discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#EXTERNAL_PACKS},1.3.6.1.4.1.318.1.1.1.2.2.6]' key: battery.packs.bad.discovery delay: 1h description: 'Discovery of the number of external defective battery packs.' item_prototypes: - uuid: 7b7ef64f2c3f4c0abeff433279903426 name: '{#SNMPINDEX}: External battery packs bad' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.1.2.2.6.0 key: 'battery.external_packs_bad[upsAdvBatteryNumOfBadBattPacks.{#SNMPINDEX}]' delay: 15m history: 7d description: | MIB: PowerNet-MIB The number of external battery packs connected to the UPS that are defective. If the UPS does not use smart cells then the agent reports ERROR_NO_SUCH_NAME. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: inventory - uuid: b615a0d1ef1e49678daa4de77b47623e name: 'External battery packs discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#CARTRIDGE_STATUS},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.7,{#BATTERY_PACK},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.1,{#CARTRIDGE_INDEX},1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.2]' key: battery.packs.discovery delay: 1h filter: evaltype: AND conditions: - macro: '{#CARTRIDGE_STATUS}' value: ^$ operator: NOT_MATCHES_REGEX formulaid: A item_prototypes: - uuid: 28f43e10b50d4709a6790d2f7d0552c2 name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery estimated replace date' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.8.{#SNMPINDEX}' key: 'battery.estimated_replace_date[upsHighPrecBatteryPackCartridgeReplaceDate.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]' delay: 1h history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB The battery cartridge estimated battery replace date. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: inventory - tag: component value: power - uuid: ebaf443cd74f4be282939032a843dcef name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery pack cartridge health' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.7.{#SNMPINDEX}' key: 'battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]' history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB The battery cartridge health. bit 0 Battery lifetime okay bit 1 Battery lifetime near end, order replacement cartridge bit 2 Battery lifetime exceeded, replace battery bit 3 Battery lifetime near end acknowledged, order replacement cartridge bit 4 Battery lifetime exceeded acknowledged, replace battery bit 5 Battery measured lifetime near end, order replacement cartridge bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: health - tag: component value: power trigger_prototypes: - uuid: 002caa5fac72437187ab9711eb2fc7ad expression: 'find(/APC UPS Symmetra RM SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1' name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay' opdata: 'Current bit set: {ITEM.LASTVALUE1}' priority: WARNING description: | The battery cartridge health. bit 0 Battery lifetime okay bit 1 Battery lifetime near end, order replacement cartridge bit 2 Battery lifetime exceeded, replace battery bit 3 Battery lifetime near end acknowledged, order replacement cartridge bit 4 Battery lifetime exceeded acknowledged, replace battery bit 5 Battery measured lifetime near end, order replacement cartridge bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge tags: - tag: scope value: notice - uuid: a415a0d85a1146e6aadfd691fcc5da63 name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.10.{#SNMPINDEX}' key: 'battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]' history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB The battery cartridge status. bit 0 Disconnected bit 1 Overvoltage bit 2 NeedsReplacement bit 3 OvertemperatureCritical bit 4 Charger bit 5 TemperatureSensor bit 6 BusSoftStart bit 7 OvertemperatureWarning bit 8 GeneralError bit 9 Communication bit 10 DisconnectedFrame bit 11 FirmwareMismatch preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: health - tag: component value: power trigger_prototypes: - uuid: 9ca2e1e1a81e4e2388f735c03f9bc1de expression: 'find(/APC UPS Symmetra RM SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0' name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay' opdata: 'Current bit set: {ITEM.LASTVALUE1}' priority: WARNING description: | The battery cartridge status: bit 0 Disconnected bit 1 Overvoltage bit 2 NeedsReplacement bit 3 OvertemperatureCritical bit 4 Charger bit 5 TemperatureSensor bit 6 BusSoftStart bit 7 OvertemperatureWarning bit 8 GeneralError bit 9 Communication bit 10 DisconnectedFrame bit 11 FirmwareMismatch tags: - tag: scope value: notice - uuid: 8d1317fc38034fd78b5cff3b04dce7f1 name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery temperature' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.5.{#SNMPINDEX}' key: 'battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]' history: 7d value_type: FLOAT units: ℃ description: | MIB: PowerNet-MIB The battery pack temperature in Celsius. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: temperature trigger_prototypes: - uuid: b9a868a2f4a0410e9a03744eef9a5515 expression: 'min(/APC UPS Symmetra RM SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}' name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature' event_name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD})' opdata: 'Current temperature: {ITEM.LASTVALUE1}' priority: HIGH tags: - tag: scope value: notice - uuid: 2694e29b9287464898684b711040d75a name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Serial number' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.4.{#SNMPINDEX}' key: 'system.sn[upsHighPrecBatteryPackSerialNumber.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]' delay: 15m history: 7d trends: '0' value_type: CHAR description: | MIB: PowerNet-MIB The battery pack serial number. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: inventory - uuid: 3adfddb03546462a9bcfdc5b059a29cc name: 'External sensor port 1 discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#EXTERNAL_SENSOR1_NAME},1.3.6.1.4.1.318.1.1.25.1.2.1.3]' key: external.sensor1.discovery delay: 1h description: uioSensorStatusTable item_prototypes: - uuid: fe2eb706e52849f79781b746db05e753 name: '{#EXTERNAL_SENSOR1_NAME}: Humidity sensor' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.1.7.1.1 key: 'external.sensor.humidity[uioSensorStatusHumidity.1.{#SNMPINDEX}]' history: 7d value_type: FLOAT units: '%' description: | MIB: PowerNet-MIB The sensor's current humidity reading - a relative humidity percentage. -1 indicates an invalid reading due to either a sensor that doesn't read humidity or lost communications. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: humidity - tag: component value: power - uuid: e80af415f8384d0fa54c6954594b5794 name: '{#EXTERNAL_SENSOR1_NAME}: Sensor alarm status' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.1.9.1.1 key: 'external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}]' history: 7d description: | MIB: PowerNet-MIB The alarm status of the sensor. Possible values: uioNormal (1), uioWarning (2), uioCritical (3), sensorStatusNotApplicable (4) valuemap: name: 'PowerNet-MIB::uioSensorStatusAlarmStatus' preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: health - tag: component value: power trigger_prototypes: - uuid: 1e6fa00989994e6f885c9ce2fde6ab24 expression: 'last(/APC UPS Symmetra RM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=3' name: '{#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical' priority: HIGH description: 'The external sensor has returned a value greater than the critical threshold.' tags: - tag: scope value: notice - uuid: b8b78dcb3f6d47e583565b7588cf9f4c expression: 'last(/APC UPS Symmetra RM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4' name: '{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable' priority: INFO description: 'The external sensor does not work or is not connected.' tags: - tag: scope value: notice - uuid: ba421cf1871a4bcabb06f92be0a983dc expression: 'last(/APC UPS Symmetra RM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2' name: '{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning' priority: AVERAGE description: 'The external sensor has returned a value greater than the warning threshold.' tags: - tag: scope value: notice - uuid: c2e3e2ea6df84a609acdc3e05d4ea036 name: '{#EXTERNAL_SENSOR1_NAME}: Temperature sensor' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.1.6.1.1 key: 'external.sensor.temperature[uioSensorStatusTemperatureDegC.1.{#SNMPINDEX}]' history: 7d value_type: FLOAT units: ℃ description: | MIB: PowerNet-MIB The sensor's current temperature reading in Celsius. -1 indicates an invalid reading due to lost communications. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - tag: component value: temperature overrides: - name: Temp step: '1' filter: conditions: - macro: '{#EXTERNAL_SENSOR1_NAME}' value: Temp formulaid: A operations: - operationobject: ITEM_PROTOTYPE operator: LIKE value: Humidity status: ENABLED discover: NO_DISCOVER - uuid: 8243825c5bbc42639f8796d1082a4a05 name: 'External sensor port 2 discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#EXTERNAL_SENSOR2_NAME},1.3.6.1.4.1.318.1.1.25.1.2.2.3]' key: external.sensor2.discovery delay: 1h description: uioSensorStatusTable item_prototypes: - uuid: 22227cb4aa284d9392015e3a2fe20912 name: '{#EXTERNAL_SENSOR2_NAME}: Humidity sensor' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.2.7.1.1 key: 'external.sensor.humidity[uioSensorStatusHumidity.2.{#SNMPINDEX}]' history: 7d value_type: FLOAT units: '%' description: | MIB: PowerNet-MIB The sensor's current humidity reading - a relative humidity percentage. -1 indicates an invalid reading due to either a sensor that doesn't read humidity or lost communications. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: humidity - tag: component value: power - uuid: a140c9eaef4049278bc5f2bfd28d0339 name: '{#EXTERNAL_SENSOR2_NAME}: Sensor alarm status' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.2.9.1.1 key: 'external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}]' history: 7d description: | MIB: PowerNet-MIB The alarm status of the sensor. Possible values: uioNormal (1), uioWarning (2), uioCritical (3), sensorStatusNotApplicable (4) valuemap: name: 'PowerNet-MIB::uioSensorStatusAlarmStatus' preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: health - tag: component value: power trigger_prototypes: - uuid: 97ef6f2fc4374174912b16db90b615a8 expression: 'last(/APC UPS Symmetra RM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=3' name: '{#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical' priority: HIGH description: 'The external sensor has returned a value greater than the critical threshold.' tags: - tag: scope value: notice - uuid: 39db14da83714689b6bac140a9347c64 expression: 'last(/APC UPS Symmetra RM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=4' name: '{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable' priority: INFO description: 'The external sensor does not work or is not connected.' tags: - tag: scope value: notice - uuid: d318122e192a401c95f24ad17d3bda93 expression: 'last(/APC UPS Symmetra RM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=2' name: '{#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning' priority: AVERAGE description: 'The external sensor has returned a value greater than the warning threshold.' tags: - tag: scope value: notice - uuid: 69ca20795352489b9efc0a0c0cc1b27f name: '{#EXTERNAL_SENSOR2_NAME}: Temperature sensor' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.318.1.1.25.1.2.2.6.1.1 key: 'external.sensor.temperature[uioSensorStatusTemperatureDegC.2.{#SNMPINDEX}]' history: 7d value_type: FLOAT units: ℃ description: | MIB: PowerNet-MIB The sensor's current temperature reading in Celsius. -1 indicates an invalid reading due to lost communications. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - tag: component value: temperature overrides: - name: Temp step: '1' filter: conditions: - macro: '{#EXTERNAL_SENSOR2_NAME}' value: Temp formulaid: A operations: - operationobject: ITEM_PROTOTYPE operator: LIKE value: Humidity status: ENABLED discover: NO_DISCOVER - uuid: 6d6d6b6a71434315a0bbc38b56d47f49 name: 'Input phases discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#PHASEINDEX},1.3.6.1.4.1.318.1.1.1.9.2.3.1.2.1.1]' key: input.phases.discovery delay: 1h description: 'The input phase identifier. OID upsPhaseInputPhaseIndex.1.1' item_prototypes: - uuid: 45def82313f74727826a0db8aa18eecc name: '{#PHASEINDEX}: Phase input current' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.9.2.3.1.6.1.1.{#PHASEINDEX}' key: 'phase.input.current[upsPhaseInputCurrent.1.1.{#PHASEINDEX}]' history: 7d value_type: FLOAT units: A description: | MIB: PowerNet-MIB The input current in 0.1 amperes, or -0.1 if it's unsupported by this UPS. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - uuid: e6d933f8a79248539fa9b5ce447813b5 name: '{#PHASEINDEX}: Phase input voltage' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.9.2.3.1.3.1.1.{#PHASEINDEX}' key: 'phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}]' history: 7d value_type: FLOAT units: V description: | MIB: PowerNet-MIB The input voltage in VAC, or -1 if it's unsupported by this UPS. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power trigger_prototypes: - uuid: 341c10188b984ce7aac7bb995847b69e expression: 'min(/APC UPS Symmetra RM SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra RM SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}' name: '{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage' event_name: '{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})' opdata: 'Current phase {#PHASEINDEX} voltage: {ITEM.LASTVALUE1}' priority: HIGH tags: - tag: scope value: notice - uuid: a2da2392f78b4b5ea97370ef0f276973 name: 'Output phases discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#PHASEINDEX},1.3.6.1.4.1.318.1.1.1.9.3.3.1.2.1.1]' key: output.phases.discovery delay: 1h description: 'The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1' item_prototypes: - uuid: 16117cb258304fb8bc2660ff4b80cc1c name: '{#PHASEINDEX}: Phase output current' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.9.3.3.1.4.1.1.{#PHASEINDEX}' key: 'phase.output.current[upsPhaseOutputCurrent.1.1.{#PHASEINDEX}]' history: 7d value_type: FLOAT units: A description: | MIB: PowerNet-MIB The output current in 0.1 amperes drawn by the load on the UPS, or -1 if it's unsupported by this UPS. preprocessing: - type: MULTIPLIER parameters: - '0.1' - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - uuid: 177f5c2dcfac4bb997f778dcd58ba638 name: '{#PHASEINDEX}: Phase output load, %' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.9.3.3.1.10.1.1.{#PHASEINDEX}' key: 'phase.output.load.percent[upsPhaseOutputPercentLoad.1.1.{#PHASEINDEX}]' history: 7d value_type: FLOAT units: '%' description: | MIB: PowerNet-MIB The percentage of the UPS load capacity in VA at redundancy @ (n + x) presently being used on this output phase, or -1 if it's unsupported by this UPS. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power - uuid: cc7c08b1bf924507b6d15cd9105926a5 name: '{#PHASEINDEX}: Phase output voltage' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.318.1.1.1.9.3.3.1.3.1.1.{#PHASEINDEX}' key: 'phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}]' history: 7d value_type: FLOAT units: V description: | MIB: PowerNet-MIB The output voltage in VAC, or -1 if it's unsupported by this UPS. preprocessing: - type: DISCARD_UNCHANGED_HEARTBEAT parameters: - 6h tags: - tag: component value: power trigger_prototypes: - uuid: 85551dd4ca0b4ef6994348891ad77b57 expression: 'min(/APC UPS Symmetra RM SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra RM SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}' name: '{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage' event_name: '{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})' opdata: 'Current phase {#PHASEINDEX} voltage: {ITEM.LASTVALUE1}' priority: HIGH tags: - tag: scope value: notice tags: - tag: class value: power - tag: target value: apc - tag: target value: apc-ups-symmetra-rm macros: - macro: '{$BATTERY.CAPACITY.MIN.WARN}' value: '50' description: 'Minimum battery capacity percentage for trigger expression.' - macro: '{$BATTERY.TEMP.MAX.WARN}' value: '55' description: 'Maximum battery temperature for trigger expression.' - macro: '{$SNMP.TIMEOUT}' value: 5m description: 'The time interval for SNMP agent availability trigger expression.' - macro: '{$TIME.PERIOD}' value: 15m description: 'Time period for trigger expression.' - macro: '{$UPS.INPUT_FREQ.MAX.WARN}' value: '50.3' description: 'Maximum input frequency for trigger expression.' - macro: '{$UPS.INPUT_FREQ.MIN.WARN}' value: '49.7' description: 'Minimum input frequency for trigger expression.' - macro: '{$UPS.INPUT_VOLT.MAX.WARN}' value: '243' description: 'Maximum input voltage for trigger expression.' - macro: '{$UPS.INPUT_VOLT.MIN.WARN}' value: '197' description: 'Minimum input voltage for trigger expression.' - macro: '{$UPS.OUTPUT.MAX.WARN}' value: '80' description: 'Maximum output load in % for trigger expression.' dashboards: - uuid: 3d8fa7f93f9f4a0bbc0b9f70282aa5cd name: 'UPS Summary' pages: - widgets: - type: PLAIN_TEXT width: '8' fields: - type: INTEGER name: show_as_html value: '0' - type: INTEGER name: show_lines value: '1' - type: ITEM name: itemids value: key: 'system.uptime[sysUpTime.0]' host: 'APC UPS Symmetra RM SNMP' - type: PLAIN_TEXT x: '8' width: '8' fields: - type: INTEGER name: show_as_html value: '0' - type: INTEGER name: show_lines value: '1' - type: ITEM name: itemids value: key: 'input.fail[upsAdvInputLineFailCause]' host: 'APC UPS Symmetra RM SNMP' - type: PLAIN_TEXT x: '16' width: '8' fields: - type: INTEGER name: show_as_html value: '0' - type: INTEGER name: show_lines value: '1' - type: ITEM name: itemids value: key: 'output.status[upsBasicOutputStatus]' host: 'APC UPS Symmetra RM SNMP' - type: PLAIN_TEXT 'y': '2' width: '8' fields: - type: INTEGER name: show_as_html value: '0' - type: INTEGER name: show_lines value: '1' - type: ITEM name: itemids value: key: 'battery.status[upsBasicBatteryStatus]' host: 'APC UPS Symmetra RM SNMP' - type: PLAIN_TEXT x: '8' 'y': '2' width: '8' fields: - type: INTEGER name: show_as_html value: '0' - type: INTEGER name: show_lines value: '1' - type: ITEM name: itemids value: key: 'battery.runtime_remaining[upsAdvBatteryRunTimeRemaining]' host: 'APC UPS Symmetra RM SNMP' - type: PLAIN_TEXT x: '16' 'y': '2' width: '8' fields: - type: INTEGER name: show_as_html value: '0' - type: INTEGER name: show_lines value: '1' - type: ITEM name: itemids value: key: 'battery.last_replace_date[upsBasicBatteryLastReplaceDate]' host: 'APC UPS Symmetra RM SNMP' - type: GRAPH_CLASSIC 'y': '4' width: '8' height: '7' fields: - type: INTEGER name: source_type value: '0' - type: GRAPH name: graphid value: name: 'Capacity of the UPS batteries' host: 'APC UPS Symmetra RM SNMP' - type: GRAPH_CLASSIC x: '8' 'y': '4' width: '8' height: '7' fields: - type: INTEGER name: source_type value: '0' - type: GRAPH name: graphid value: name: Voltage host: 'APC UPS Symmetra RM SNMP' - type: GRAPH_CLASSIC x: '16' 'y': '4' width: '8' height: '7' fields: - type: INTEGER name: source_type value: '0' - type: GRAPH name: graphid value: name: Output host: 'APC UPS Symmetra RM SNMP' valuemaps: - uuid: 8516e97893ed4f2ebe70766d17eeacde name: 'PowerNet-MIB::uioSensorStatusAlarmStatus' mappings: - value: '1' newvalue: Normal - value: '2' newvalue: Warning - value: '3' newvalue: Critical - value: '4' newvalue: 'Not applicable' - uuid: 84387eb0a5ef4523ac5d990eb4a6a796 name: 'PowerNet-MIB::upsAdvBatteryReplaceIndicator' mappings: - value: '1' newvalue: 'no Battery Needs Replacing' - value: '2' newvalue: 'battery Needs Replacing' - uuid: 58104ecf15d34fe38922f3fe5fa25027 name: 'PowerNet-MIB::upsAdvInputLineFailCause' mappings: - value: '1' newvalue: 'no Transfer' - value: '2' newvalue: 'High Line Voltage' - value: '3' newvalue: Brownout - value: '4' newvalue: Blackout - value: '5' newvalue: 'Small Momentary Sag' - value: '6' newvalue: 'Deep Momentary Sag' - value: '7' newvalue: 'Small Momentary Spike' - value: '8' newvalue: 'Large Momentary Spike' - value: '9' newvalue: 'Self Test' - value: '10' newvalue: 'Rate of Voltage Change' - uuid: 43715c15fed840fc8e188d062c0ef2da name: 'PowerNet-MIB::upsBasicBatteryStatus' mappings: - value: '1' newvalue: Unknown - value: '2' newvalue: Normal - value: '3' newvalue: Low - value: '4' newvalue: 'In Fault Condition' - uuid: d9b5340729684dd0a450b6de6b14b590 name: 'PowerNet-MIB::upsBasicOutputStatus' mappings: - value: '1' newvalue: Unknown - value: '2' newvalue: Online - value: '3' newvalue: 'On Battery' - value: '4' newvalue: 'On Smart Boost' - value: '5' newvalue: 'Timed Sleeping' - value: '6' newvalue: 'Software Bypass' - value: '7' newvalue: 'Off' - value: '8' newvalue: Rebooting - value: '9' newvalue: 'Switched Bypass' - value: '10' newvalue: 'Hardware Failure Bypass' - value: '11' newvalue: 'Sleeping Until Power Return' - value: '12' newvalue: 'On Smart Trim' - value: '13' newvalue: 'Eco Mode' - value: '14' newvalue: 'Hot Standby' - value: '15' newvalue: 'On Battery Test' - value: '16' newvalue: 'Emergency Static Bypass' - value: '17' newvalue: 'Static Bypass Standby' - value: '18' newvalue: 'Power Saving Mode' - value: '19' newvalue: 'Spot Mode' - value: '20' newvalue: E-Conversion - value: '21' newvalue: 'Charger Spotmode' - value: '22' newvalue: 'Inverter Spotmode' - value: '23' newvalue: 'Active Load' - value: '24' newvalue: 'Battery Discharge Spotmode' - value: '25' newvalue: 'Inverter Standby' - value: '26' newvalue: 'Charger Only' - uuid: cdf3578a66db4cfda6c36b4bbb295173 name: zabbix.host.available mappings: - value: '0' newvalue: 'not available' - value: '1' newvalue: available - value: '2' newvalue: unknown graphs: - uuid: ea7ef2682549402eb23b0d9df313ee25 name: 'Capacity of the UPS batteries' type: PIE graph_items: - color: 1A7C11 item: host: 'APC UPS Symmetra RM SNMP' key: 'battery.capacity[upsHighPrecBatteryCapacity]' - uuid: d340e1d477bc4bc4b099c94b1fe6d2da name: Output graph_items: - color: 1A7C11 item: host: 'APC UPS Symmetra RM SNMP' key: 'output.current[upsHighPrecOutputCurrent]' - sortorder: '1' color: 2774A4 item: host: 'APC UPS Symmetra RM SNMP' key: 'output.load[upsHighPrecOutputLoad]' - uuid: 42f5e7154634464fabafe352508b50db name: Voltage graph_items: - color: 1A7C11 item: host: 'APC UPS Symmetra RM SNMP' key: 'input.voltage[upsHighPrecInputLineVoltage]' - sortorder: '1' color: 2774A4 item: host: 'APC UPS Symmetra RM SNMP' key: 'output.voltage[upsHighPrecOutputVoltage]'