diff --git a/templates/power/apc/apc_ups_smart_3000_xlm_snmp/template_power_apc_ups_smart_3000_xlm_snmp.yaml b/templates/power/apc/apc_ups_smart_3000_xlm_snmp/template_power_apc_ups_smart_3000_xlm_snmp.yaml
index 03f45c0b2d8..220d71bb397 100644
--- a/templates/power/apc/apc_ups_smart_3000_xlm_snmp/template_power_apc_ups_smart_3000_xlm_snmp.yaml
+++ b/templates/power/apc/apc_ups_smart_3000_xlm_snmp/template_power_apc_ups_smart_3000_xlm_snmp.yaml
@@ -1,6 +1,6 @@
zabbix_export:
version: '6.4'
- date: '2022-08-16T10:56:53Z'
+ date: '2022-10-27T14:24:41Z'
template_groups:
-
uuid: 3dcd5bbe90534f9e8eb5c2d53756af63
@@ -8,8 +8,8 @@ zabbix_export:
templates:
-
uuid: eafd78764fde4110b9e46ae184f327ba
- template: 'APC Smart-UPS 3000 XLM SNMP'
- name: 'APC Smart-UPS 3000 XLM SNMP'
+ template: 'APC Smart-UPS 3000 XLM by SNMP'
+ name: 'APC Smart-UPS 3000 XLM by SNMP'
description: |
Template Power APC Smart-UPS 3000 XLM
@@ -54,7 +54,7 @@ zabbix_export:
triggers:
-
uuid: 13fe1336e40c4bafb8dbd409497abf8f
- expression: 'last(/APC Smart-UPS 3000 XLM SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}'
+ expression: 'last(/APC Smart-UPS 3000 XLM by SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}'
name: 'Battery has low capacity'
event_name: 'Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%)'
opdata: 'Current capacity: {ITEM.LASTVALUE1}'
@@ -135,7 +135,7 @@ zabbix_export:
triggers:
-
uuid: 4590ac935e044c19978fe01d117e2995
- expression: 'last(/APC Smart-UPS 3000 XLM SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2'
+ expression: 'last(/APC Smart-UPS 3000 XLM by SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2'
name: 'Battery needs replacement'
priority: HIGH
description: 'A battery installed has an internal error condition.'
@@ -202,7 +202,7 @@ zabbix_export:
triggers:
-
uuid: e98ba83e63d246408aeeda76da62d5a4
- expression: 'last(/APC Smart-UPS 3000 XLM SNMP/battery.status[upsBasicBatteryStatus])=4'
+ expression: 'last(/APC Smart-UPS 3000 XLM by SNMP/battery.status[upsBasicBatteryStatus])=4'
name: 'Battery has an internal error condition'
priority: AVERAGE
description: 'A battery installed has an internal error condition.'
@@ -212,7 +212,7 @@ zabbix_export:
value: notice
-
uuid: 51e3281c49454cf997561c857a34a803
- expression: 'last(/APC Smart-UPS 3000 XLM SNMP/battery.status[upsBasicBatteryStatus])=3'
+ expression: 'last(/APC Smart-UPS 3000 XLM by SNMP/battery.status[upsBasicBatteryStatus])=3'
name: 'Battery is Low'
priority: AVERAGE
description: 'The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.'
@@ -249,7 +249,7 @@ zabbix_export:
triggers:
-
uuid: 1c67af712882479bbf7143bd3e16ed77
- expression: 'min(/APC Smart-UPS 3000 XLM SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}'
+ expression: 'min(/APC Smart-UPS 3000 XLM by SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}'
name: 'Battery has high temperature'
event_name: 'Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD})'
opdata: 'Current temperature: {ITEM.LASTVALUE1}'
@@ -355,7 +355,7 @@ zabbix_export:
triggers:
-
uuid: 78e47553d4bb488991067f53cc8f8a01
- expression: 'min(/APC Smart-UPS 3000 XLM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS 3000 XLM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC Smart-UPS 3000 XLM SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})'
+ expression: 'min(/APC Smart-UPS 3000 XLM by SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS 3000 XLM by SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC Smart-UPS 3000 XLM by SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})'
name: 'Unacceptable input frequency'
event_name: 'Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD})'
opdata: 'Current frequency: {ITEM.LASTVALUE1}'
@@ -392,7 +392,7 @@ zabbix_export:
triggers:
-
uuid: 28ad85fa6035433f9a7ec45a8393b603
- expression: 'min(/APC Smart-UPS 3000 XLM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS 3000 XLM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS 3000 XLM SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})'
+ expression: 'min(/APC Smart-UPS 3000 XLM by SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS 3000 XLM by SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS 3000 XLM by SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})'
name: 'Unacceptable input voltage'
event_name: 'Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})'
opdata: 'Current voltage: {ITEM.LASTVALUE1}'
@@ -455,7 +455,7 @@ zabbix_export:
triggers:
-
uuid: f667172a5cf44ed6b98f2bb38a3f3806
- expression: 'min(/APC Smart-UPS 3000 XLM SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}'
+ expression: 'min(/APC Smart-UPS 3000 XLM by SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}'
name: 'Output load is high'
event_name: 'Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD})'
opdata: 'Current load: {ITEM.LASTVALUE1}'
@@ -498,7 +498,7 @@ zabbix_export:
triggers:
-
uuid: 80e30d37b1724c6ba1d58cedbcf6307f
- expression: 'last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=16'
+ expression: 'last(/APC Smart-UPS 3000 XLM by SNMP/output.status[upsBasicOutputStatus])=16'
name: 'UPS is Emergency Static Bypass'
priority: AVERAGE
tags:
@@ -507,7 +507,7 @@ zabbix_export:
value: notice
-
uuid: 9bb143ada4194c0084eb70af7bb2c5dc
- expression: 'last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=10'
+ expression: 'last(/APC Smart-UPS 3000 XLM by SNMP/output.status[upsBasicOutputStatus])=10'
name: 'UPS is Hardware Failure Bypass'
priority: AVERAGE
tags:
@@ -516,7 +516,7 @@ zabbix_export:
value: notice
-
uuid: 7132f256542540acadb0caf90144a29c
- expression: 'last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=7'
+ expression: 'last(/APC Smart-UPS 3000 XLM by SNMP/output.status[upsBasicOutputStatus])=7'
name: 'UPS is Off'
priority: AVERAGE
tags:
@@ -525,7 +525,7 @@ zabbix_export:
value: notice
-
uuid: 737693e5e4274823a9a21ff92a6ca98a
- expression: 'last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=3'
+ expression: 'last(/APC Smart-UPS 3000 XLM by SNMP/output.status[upsBasicOutputStatus])=3'
name: 'UPS is on battery'
priority: AVERAGE
tags:
@@ -534,7 +534,7 @@ zabbix_export:
value: notice
-
uuid: c2fd31cfe3b8474f80b52a2340108b6a
- expression: 'last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=4'
+ expression: 'last(/APC Smart-UPS 3000 XLM by SNMP/output.status[upsBasicOutputStatus])=4'
name: 'UPS is on Smart Boost'
priority: AVERAGE
tags:
@@ -543,7 +543,7 @@ zabbix_export:
value: notice
-
uuid: 2c3a2e962c1e45f6858e5c1aaecee4a3
- expression: 'last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=12'
+ expression: 'last(/APC Smart-UPS 3000 XLM by SNMP/output.status[upsBasicOutputStatus])=12'
name: 'UPS is On Smart Trim'
priority: AVERAGE
tags:
@@ -552,7 +552,7 @@ zabbix_export:
value: notice
-
uuid: 59d415b15bbf43de85453f5b2ffb73d7
- expression: 'last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=8'
+ expression: 'last(/APC Smart-UPS 3000 XLM by SNMP/output.status[upsBasicOutputStatus])=8'
name: 'UPS is Rebooting'
priority: AVERAGE
tags:
@@ -561,7 +561,7 @@ zabbix_export:
value: notice
-
uuid: 6811d34cec57401089af9accfd66ca8f
- expression: 'last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=11'
+ expression: 'last(/APC Smart-UPS 3000 XLM by SNMP/output.status[upsBasicOutputStatus])=11'
name: 'UPS is Sleeping Until Power Return'
priority: AVERAGE
tags:
@@ -570,7 +570,7 @@ zabbix_export:
value: notice
-
uuid: 3c96ce14f54a4a59a2568f1f62117e7b
- expression: 'last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=6'
+ expression: 'last(/APC Smart-UPS 3000 XLM by SNMP/output.status[upsBasicOutputStatus])=6'
name: 'UPS is Software Bypass'
priority: AVERAGE
tags:
@@ -579,7 +579,7 @@ zabbix_export:
value: notice
-
uuid: 60e83c77157741cbb3d24920e87d7d59
- expression: 'last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=9'
+ expression: 'last(/APC Smart-UPS 3000 XLM by SNMP/output.status[upsBasicOutputStatus])=9'
name: 'UPS is Switched Bypass'
priority: AVERAGE
tags:
@@ -588,7 +588,7 @@ zabbix_export:
value: notice
-
uuid: da442de0e8874736aaab88f009aabe76
- expression: 'last(/APC Smart-UPS 3000 XLM SNMP/output.status[upsBasicOutputStatus])=5'
+ expression: 'last(/APC Smart-UPS 3000 XLM by SNMP/output.status[upsBasicOutputStatus])=5'
name: 'UPS is Timed Sleeping'
priority: AVERAGE
tags:
@@ -788,7 +788,7 @@ zabbix_export:
triggers:
-
uuid: c9b1f69a882148a180ec1e2600068671
- expression: 'last(/APC Smart-UPS 3000 XLM SNMP/system.name[sysName.0],#1)<>last(/APC Smart-UPS 3000 XLM SNMP/system.name[sysName.0],#2) and length(last(/APC Smart-UPS 3000 XLM SNMP/system.name[sysName.0]))>0'
+ expression: 'last(/APC Smart-UPS 3000 XLM by SNMP/system.name[sysName.0],#1)<>last(/APC Smart-UPS 3000 XLM by SNMP/system.name[sysName.0],#2) and length(last(/APC Smart-UPS 3000 XLM by SNMP/system.name[sysName.0]))>0'
name: 'System name has changed'
event_name: 'System name has changed (new name: {ITEM.VALUE})'
priority: INFO
@@ -905,7 +905,7 @@ zabbix_export:
triggers:
-
uuid: 71994587c45546bfb0950606d7f69936
- expression: 'max(/APC Smart-UPS 3000 XLM SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0'
+ expression: 'max(/APC Smart-UPS 3000 XLM by SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0'
name: 'No SNMP data collection'
opdata: 'Current state: {ITEM.LASTVALUE1}'
priority: WARNING
@@ -1021,7 +1021,7 @@ zabbix_export:
trigger_prototypes:
-
uuid: 400987be93b34a78865685fedb72a5ee
- expression: 'find(/APC Smart-UPS 3000 XLM SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1'
+ expression: 'find(/APC Smart-UPS 3000 XLM by SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1'
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay'
opdata: 'Current bit set: {ITEM.LASTVALUE1}'
priority: WARNING
@@ -1077,7 +1077,7 @@ zabbix_export:
trigger_prototypes:
-
uuid: 03a100c0bb8d457690e2467c502fcadb
- expression: 'find(/APC Smart-UPS 3000 XLM SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0'
+ expression: 'find(/APC Smart-UPS 3000 XLM by SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0'
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay'
opdata: 'Current bit set: {ITEM.LASTVALUE1}'
priority: WARNING
@@ -1127,7 +1127,7 @@ zabbix_export:
trigger_prototypes:
-
uuid: 9760f6a951a64e3fa6c67a9dd751f79a
- expression: 'min(/APC Smart-UPS 3000 XLM SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}'
+ expression: 'min(/APC Smart-UPS 3000 XLM by SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}'
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature'
event_name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD})'
opdata: 'Current temperature: {ITEM.LASTVALUE1}'
@@ -1224,7 +1224,7 @@ zabbix_export:
trigger_prototypes:
-
uuid: 9ba51ee0398444e1bd12cb805c1f7452
- expression: 'last(/APC Smart-UPS 3000 XLM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=3'
+ expression: 'last(/APC Smart-UPS 3000 XLM by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=3'
name: '{#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical'
priority: HIGH
description: 'The external sensor has returned a value greater than the critical threshold.'
@@ -1234,7 +1234,7 @@ zabbix_export:
value: notice
-
uuid: 490e952dfac944afb23eb0e72e081db3
- expression: 'last(/APC Smart-UPS 3000 XLM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4'
+ expression: 'last(/APC Smart-UPS 3000 XLM by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4'
name: '{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable'
priority: INFO
description: 'The external sensor does not work or is not connected.'
@@ -1244,7 +1244,7 @@ zabbix_export:
value: notice
-
uuid: 8b740b88389b457eaa4d1d6c768ec8ae
- expression: 'last(/APC Smart-UPS 3000 XLM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2'
+ expression: 'last(/APC Smart-UPS 3000 XLM by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2'
name: '{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning'
priority: AVERAGE
description: 'The external sensor has returned a value greater than the warning threshold.'
@@ -1292,7 +1292,6 @@ zabbix_export:
operationobject: ITEM_PROTOTYPE
operator: LIKE
value: Humidity
- status: ENABLED
discover: NO_DISCOVER
-
uuid: c64b5cb02dec4873a2e041359da3cdf7
@@ -1360,7 +1359,7 @@ zabbix_export:
trigger_prototypes:
-
uuid: 944fd36a2ad14fd29dd063ad03197cd7
- expression: 'last(/APC Smart-UPS 3000 XLM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=3'
+ expression: 'last(/APC Smart-UPS 3000 XLM by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=3'
name: '{#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical'
priority: HIGH
description: 'The external sensor has returned a value greater than the critical threshold.'
@@ -1370,7 +1369,7 @@ zabbix_export:
value: notice
-
uuid: 1a4473a5e1bf4fbbb5761fdb141769c0
- expression: 'last(/APC Smart-UPS 3000 XLM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=4'
+ expression: 'last(/APC Smart-UPS 3000 XLM by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=4'
name: '{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable'
priority: INFO
description: 'The external sensor does not work or is not connected.'
@@ -1380,7 +1379,7 @@ zabbix_export:
value: notice
-
uuid: af8e01a221b84c73a3f67ab84ed9cfa0
- expression: 'last(/APC Smart-UPS 3000 XLM SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=2'
+ expression: 'last(/APC Smart-UPS 3000 XLM by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=2'
name: '{#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning'
priority: AVERAGE
description: 'The external sensor has returned a value greater than the warning threshold.'
@@ -1428,7 +1427,6 @@ zabbix_export:
operationobject: ITEM_PROTOTYPE
operator: LIKE
value: Humidity
- status: ENABLED
discover: NO_DISCOVER
-
uuid: ecca1791b7744f30bfcc1018a10cf1fa
@@ -1490,7 +1488,7 @@ zabbix_export:
trigger_prototypes:
-
uuid: 709ad3894aca49f0be051d338d4ffaed
- expression: 'min(/APC Smart-UPS 3000 XLM SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS 3000 XLM SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}'
+ expression: 'min(/APC Smart-UPS 3000 XLM by SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS 3000 XLM by SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}'
name: '{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage'
event_name: '{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})'
opdata: 'Current phase {#PHASEINDEX} voltage: {ITEM.LASTVALUE1}'
@@ -1583,7 +1581,7 @@ zabbix_export:
trigger_prototypes:
-
uuid: dbdf66b61dce4b6dbf49371e9b1f8146
- expression: 'min(/APC Smart-UPS 3000 XLM SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS 3000 XLM SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}'
+ expression: 'min(/APC Smart-UPS 3000 XLM by SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS 3000 XLM by SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}'
name: '{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage'
event_name: '{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})'
opdata: 'Current phase {#PHASEINDEX} voltage: {ITEM.LASTVALUE1}'
@@ -1639,6 +1637,136 @@ zabbix_export:
macro: '{$UPS.OUTPUT.MAX.WARN}'
value: '80'
description: 'Maximum output load in % for trigger expression.'
+ dashboards:
+ -
+ uuid: 829373d305ce44cc9441714fc9d828a5
+ name: 'UPS Summary'
+ pages:
+ -
+ widgets:
+ -
+ type: PLAIN_TEXT
+ width: '8'
+ height: '5'
+ fields:
+ -
+ type: ITEM
+ name: itemids
+ value:
+ host: 'APC Smart-UPS 3000 XLM by SNMP'
+ key: 'system.net.uptime[sysUpTime.0]'
+ -
+ type: PLAIN_TEXT
+ x: '8'
+ width: '8'
+ height: '5'
+ fields:
+ -
+ type: ITEM
+ name: itemids
+ value:
+ host: 'APC Smart-UPS 3000 XLM by SNMP'
+ key: 'input.fail[upsAdvInputLineFailCause]'
+ -
+ type: PLAIN_TEXT
+ x: '16'
+ width: '8'
+ height: '5'
+ fields:
+ -
+ type: ITEM
+ name: itemids
+ value:
+ host: 'APC Smart-UPS 3000 XLM by SNMP'
+ key: 'output.status[upsBasicOutputStatus]'
+ -
+ type: PLAIN_TEXT
+ 'y': '5'
+ width: '8'
+ height: '5'
+ fields:
+ -
+ type: ITEM
+ name: itemids
+ value:
+ host: 'APC Smart-UPS 3000 XLM by SNMP'
+ key: 'battery.status[upsBasicBatteryStatus]'
+ -
+ type: PLAIN_TEXT
+ x: '8'
+ 'y': '5'
+ width: '8'
+ height: '5'
+ fields:
+ -
+ type: ITEM
+ name: itemids
+ value:
+ host: 'APC Smart-UPS 3000 XLM by SNMP'
+ key: 'battery.runtime_remaining[upsAdvBatteryRunTimeRemaining]'
+ -
+ type: PLAIN_TEXT
+ x: '16'
+ 'y': '5'
+ width: '8'
+ height: '5'
+ fields:
+ -
+ type: ITEM
+ name: itemids
+ value:
+ host: 'APC Smart-UPS 3000 XLM by SNMP'
+ key: 'battery.last_replace_date[upsBasicBatteryLastReplaceDate]'
+ -
+ type: GRAPH_CLASSIC
+ 'y': '10'
+ width: '8'
+ height: '5'
+ fields:
+ -
+ type: INTEGER
+ name: source_type
+ value: '0'
+ -
+ type: GRAPH
+ name: graphid
+ value:
+ host: 'APC Smart-UPS 3000 XLM by SNMP'
+ name: 'Capacity of the UPS batteries'
+ -
+ type: GRAPH_CLASSIC
+ x: '8'
+ 'y': '10'
+ width: '8'
+ height: '5'
+ fields:
+ -
+ type: INTEGER
+ name: source_type
+ value: '0'
+ -
+ type: GRAPH
+ name: graphid
+ value:
+ host: 'APC Smart-UPS 3000 XLM by SNMP'
+ name: Voltage
+ -
+ type: GRAPH_CLASSIC
+ x: '16'
+ 'y': '10'
+ width: '8'
+ height: '5'
+ fields:
+ -
+ type: INTEGER
+ name: source_type
+ value: '0'
+ -
+ type: GRAPH
+ name: graphid
+ value:
+ host: 'APC Smart-UPS 3000 XLM by SNMP'
+ name: Output
valuemaps:
-
uuid: 55fecbd639c44c328b4199569a7305ef
@@ -1814,7 +1942,7 @@ zabbix_export:
triggers:
-
uuid: 15764a5819174d3fadc75436f42650fb
- expression: '(last(/APC Smart-UPS 3000 XLM SNMP/system.hw.uptime[hrSystemUptime.0])>0 and last(/APC Smart-UPS 3000 XLM SNMP/system.hw.uptime[hrSystemUptime.0])<10m) or (last(/APC Smart-UPS 3000 XLM SNMP/system.hw.uptime[hrSystemUptime.0])=0 and last(/APC Smart-UPS 3000 XLM SNMP/system.net.uptime[sysUpTime.0])<10m)'
+ expression: '(last(/APC Smart-UPS 3000 XLM by SNMP/system.hw.uptime[hrSystemUptime.0])>0 and last(/APC Smart-UPS 3000 XLM by SNMP/system.hw.uptime[hrSystemUptime.0])<10m) or (last(/APC Smart-UPS 3000 XLM by SNMP/system.hw.uptime[hrSystemUptime.0])=0 and last(/APC Smart-UPS 3000 XLM by SNMP/system.net.uptime[sysUpTime.0])<10m)'
name: 'Host has been restarted'
event_name: '{HOST.NAME} has been restarted (uptime < 10m)'
priority: WARNING
@@ -1823,7 +1951,7 @@ zabbix_export:
dependencies:
-
name: 'No SNMP data collection'
- expression: 'max(/APC Smart-UPS 3000 XLM SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0'
+ expression: 'max(/APC Smart-UPS 3000 XLM by SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0'
tags:
-
tag: scope
@@ -1837,7 +1965,7 @@ zabbix_export:
-
color: 1A7C11
item:
- host: 'APC Smart-UPS 3000 XLM SNMP'
+ host: 'APC Smart-UPS 3000 XLM by SNMP'
key: 'battery.capacity[upsHighPrecBatteryCapacity]'
-
uuid: 3c778f0c837d4979abb39aabe0cb321e
@@ -1846,13 +1974,13 @@ zabbix_export:
-
color: 1A7C11
item:
- host: 'APC Smart-UPS 3000 XLM SNMP'
+ host: 'APC Smart-UPS 3000 XLM by SNMP'
key: 'output.current[upsHighPrecOutputCurrent]'
-
sortorder: '1'
color: 2774A4
item:
- host: 'APC Smart-UPS 3000 XLM SNMP'
+ host: 'APC Smart-UPS 3000 XLM by SNMP'
key: 'output.load[upsHighPrecOutputLoad]'
-
uuid: 5f44db14cfc94ae7adf98f8cf1f4b647
@@ -1861,11 +1989,11 @@ zabbix_export:
-
color: 1A7C11
item:
- host: 'APC Smart-UPS 3000 XLM SNMP'
+ host: 'APC Smart-UPS 3000 XLM by SNMP'
key: 'input.voltage[upsHighPrecInputLineVoltage]'
-
sortorder: '1'
color: 2774A4
item:
- host: 'APC Smart-UPS 3000 XLM SNMP'
+ host: 'APC Smart-UPS 3000 XLM by SNMP'
key: 'output.voltage[upsHighPrecOutputVoltage]'