Welcome to mirror list, hosted at ThFree Co, Russian Federation.

github.com/zabbix/zabbix.git - Unnamed repository; edit this file 'description' to name the repository.
summaryrefslogtreecommitdiff
diff options
context:
space:
mode:
Diffstat (limited to 'templates/power/apc/apc_ups_symmetra_rx_snmp/template_power_apc_ups_symmetra_rx_snmp.yaml')
-rw-r--r--templates/power/apc/apc_ups_symmetra_rx_snmp/template_power_apc_ups_symmetra_rx_snmp.yaml216
1 files changed, 172 insertions, 44 deletions
diff --git a/templates/power/apc/apc_ups_symmetra_rx_snmp/template_power_apc_ups_symmetra_rx_snmp.yaml b/templates/power/apc/apc_ups_symmetra_rx_snmp/template_power_apc_ups_symmetra_rx_snmp.yaml
index d8fa66a22b5..23305e2eb26 100644
--- a/templates/power/apc/apc_ups_symmetra_rx_snmp/template_power_apc_ups_symmetra_rx_snmp.yaml
+++ b/templates/power/apc/apc_ups_symmetra_rx_snmp/template_power_apc_ups_symmetra_rx_snmp.yaml
@@ -1,6 +1,6 @@
zabbix_export:
version: '6.4'
- date: '2022-08-16T10:57:01Z'
+ date: '2022-10-27T14:24:44Z'
template_groups:
-
uuid: 3dcd5bbe90534f9e8eb5c2d53756af63
@@ -8,8 +8,8 @@ zabbix_export:
templates:
-
uuid: 4ffb0f9103084384a98379ed533865e9
- template: 'APC UPS Symmetra RX SNMP'
- name: 'APC UPS Symmetra RX SNMP'
+ template: 'APC UPS Symmetra RX by SNMP'
+ name: 'APC UPS Symmetra RX by SNMP'
description: |
Template Power APC UPS Symmetra RX
@@ -54,7 +54,7 @@ zabbix_export:
triggers:
-
uuid: 5626e87891ec4c28a17a6b5965b47e46
- expression: 'last(/APC UPS Symmetra RX SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}'
+ expression: 'last(/APC UPS Symmetra RX by SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}'
name: 'Battery has low capacity'
event_name: 'Battery has low capacity (below {$BATTERY.CAPACITY.MIN.WARN}%)'
opdata: 'Current capacity: {ITEM.LASTVALUE1}'
@@ -135,7 +135,7 @@ zabbix_export:
triggers:
-
uuid: a74eccd4442c401a98ac3c80dd3baa13
- expression: 'last(/APC UPS Symmetra RX SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2'
+ expression: 'last(/APC UPS Symmetra RX by SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2'
name: 'Battery needs replacement'
priority: HIGH
description: 'A battery installed has an internal error condition.'
@@ -202,7 +202,7 @@ zabbix_export:
triggers:
-
uuid: 107454c372cb413bad4d4a807c254ae0
- expression: 'last(/APC UPS Symmetra RX SNMP/battery.status[upsBasicBatteryStatus])=4'
+ expression: 'last(/APC UPS Symmetra RX by SNMP/battery.status[upsBasicBatteryStatus])=4'
name: 'Battery has an internal error condition'
priority: AVERAGE
description: 'A battery installed has an internal error condition.'
@@ -212,7 +212,7 @@ zabbix_export:
value: notice
-
uuid: 4a410279dba04d37924eade4bb927228
- expression: 'last(/APC UPS Symmetra RX SNMP/battery.status[upsBasicBatteryStatus])=3'
+ expression: 'last(/APC UPS Symmetra RX by SNMP/battery.status[upsBasicBatteryStatus])=3'
name: 'Battery is Low'
priority: AVERAGE
description: 'The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.'
@@ -249,7 +249,7 @@ zabbix_export:
triggers:
-
uuid: 225ccc34992f4c718277b436bfecdc72
- expression: 'min(/APC UPS Symmetra RX SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}'
+ expression: 'min(/APC UPS Symmetra RX by SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}'
name: 'Battery has high temperature'
event_name: 'Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD})'
opdata: 'Current temperature: {ITEM.LASTVALUE1}'
@@ -355,7 +355,7 @@ zabbix_export:
triggers:
-
uuid: 03b674d215604dc8acc3449610b05878
- expression: 'min(/APC UPS Symmetra RX SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC UPS Symmetra RX SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC UPS Symmetra RX SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})'
+ expression: 'min(/APC UPS Symmetra RX by SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC UPS Symmetra RX by SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC UPS Symmetra RX by SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})'
name: 'Unacceptable input frequency'
event_name: 'Unacceptable input frequency (out of range {$UPS.INPUT_FREQ.MIN.WARN}-{$UPS.INPUT_FREQ.MAX.WARN}Hz for {$TIME.PERIOD})'
opdata: 'Current frequency: {ITEM.LASTVALUE1}'
@@ -392,7 +392,7 @@ zabbix_export:
triggers:
-
uuid: bf495f3ffefd4e65af488d91b360539c
- expression: 'min(/APC UPS Symmetra RX SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC UPS Symmetra RX SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra RX SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})'
+ expression: 'min(/APC UPS Symmetra RX by SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC UPS Symmetra RX by SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra RX by SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})'
name: 'Unacceptable input voltage'
event_name: 'Unacceptable input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})'
opdata: 'Current voltage: {ITEM.LASTVALUE1}'
@@ -455,7 +455,7 @@ zabbix_export:
triggers:
-
uuid: f2790aa869724c5bbeff6031561f2ca4
- expression: 'min(/APC UPS Symmetra RX SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}'
+ expression: 'min(/APC UPS Symmetra RX by SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}'
name: 'Output load is high'
event_name: 'Output load is high (over {$UPS.OUTPUT.MAX.WARN}% for {$TIME.PERIOD})'
opdata: 'Current load: {ITEM.LASTVALUE1}'
@@ -498,7 +498,7 @@ zabbix_export:
triggers:
-
uuid: 48a2bee152664ede98bed55c05cc437d
- expression: 'last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=16'
+ expression: 'last(/APC UPS Symmetra RX by SNMP/output.status[upsBasicOutputStatus])=16'
name: 'UPS is Emergency Static Bypass'
priority: AVERAGE
tags:
@@ -507,7 +507,7 @@ zabbix_export:
value: notice
-
uuid: ccd80d5877e0401b8f56f22ca2da2f94
- expression: 'last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=10'
+ expression: 'last(/APC UPS Symmetra RX by SNMP/output.status[upsBasicOutputStatus])=10'
name: 'UPS is Hardware Failure Bypass'
priority: AVERAGE
tags:
@@ -516,7 +516,7 @@ zabbix_export:
value: notice
-
uuid: e54fd69ac4354716a107d4d094b387f0
- expression: 'last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=7'
+ expression: 'last(/APC UPS Symmetra RX by SNMP/output.status[upsBasicOutputStatus])=7'
name: 'UPS is Off'
priority: AVERAGE
tags:
@@ -525,7 +525,7 @@ zabbix_export:
value: notice
-
uuid: 92df44ef170d471394f4cf8ff6882c39
- expression: 'last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=3'
+ expression: 'last(/APC UPS Symmetra RX by SNMP/output.status[upsBasicOutputStatus])=3'
name: 'UPS is on battery'
priority: AVERAGE
tags:
@@ -534,7 +534,7 @@ zabbix_export:
value: notice
-
uuid: b6f6c160466e43d8b7f210b2efdd8ca3
- expression: 'last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=4'
+ expression: 'last(/APC UPS Symmetra RX by SNMP/output.status[upsBasicOutputStatus])=4'
name: 'UPS is on Smart Boost'
priority: AVERAGE
tags:
@@ -543,7 +543,7 @@ zabbix_export:
value: notice
-
uuid: 7d6323e1a03a48efb9f349ecd7e10153
- expression: 'last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=12'
+ expression: 'last(/APC UPS Symmetra RX by SNMP/output.status[upsBasicOutputStatus])=12'
name: 'UPS is On Smart Trim'
priority: AVERAGE
tags:
@@ -552,7 +552,7 @@ zabbix_export:
value: notice
-
uuid: 18a31f11313b47c8ab9e9cd4791c1532
- expression: 'last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=8'
+ expression: 'last(/APC UPS Symmetra RX by SNMP/output.status[upsBasicOutputStatus])=8'
name: 'UPS is Rebooting'
priority: AVERAGE
tags:
@@ -561,7 +561,7 @@ zabbix_export:
value: notice
-
uuid: 142e25b05d1547f0a683f6caee773ef5
- expression: 'last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=11'
+ expression: 'last(/APC UPS Symmetra RX by SNMP/output.status[upsBasicOutputStatus])=11'
name: 'UPS is Sleeping Until Power Return'
priority: AVERAGE
tags:
@@ -570,7 +570,7 @@ zabbix_export:
value: notice
-
uuid: b6e22e8295c84fbebb8061c96ddd75f9
- expression: 'last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=6'
+ expression: 'last(/APC UPS Symmetra RX by SNMP/output.status[upsBasicOutputStatus])=6'
name: 'UPS is Software Bypass'
priority: AVERAGE
tags:
@@ -579,7 +579,7 @@ zabbix_export:
value: notice
-
uuid: 1c97c8ca6d6640fe829bf896f989bd91
- expression: 'last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=9'
+ expression: 'last(/APC UPS Symmetra RX by SNMP/output.status[upsBasicOutputStatus])=9'
name: 'UPS is Switched Bypass'
priority: AVERAGE
tags:
@@ -588,7 +588,7 @@ zabbix_export:
value: notice
-
uuid: 0683dbba9f4b4480ba15e040b8b83211
- expression: 'last(/APC UPS Symmetra RX SNMP/output.status[upsBasicOutputStatus])=5'
+ expression: 'last(/APC UPS Symmetra RX by SNMP/output.status[upsBasicOutputStatus])=5'
name: 'UPS is Timed Sleeping'
priority: AVERAGE
tags:
@@ -788,7 +788,7 @@ zabbix_export:
triggers:
-
uuid: 5224767a1bee42738c49361ddabfed4b
- expression: 'last(/APC UPS Symmetra RX SNMP/system.name[sysName.0],#1)<>last(/APC UPS Symmetra RX SNMP/system.name[sysName.0],#2) and length(last(/APC UPS Symmetra RX SNMP/system.name[sysName.0]))>0'
+ expression: 'last(/APC UPS Symmetra RX by SNMP/system.name[sysName.0],#1)<>last(/APC UPS Symmetra RX by SNMP/system.name[sysName.0],#2) and length(last(/APC UPS Symmetra RX by SNMP/system.name[sysName.0]))>0'
name: 'System name has changed'
event_name: 'System name has changed (new name: {ITEM.VALUE})'
priority: INFO
@@ -905,7 +905,7 @@ zabbix_export:
triggers:
-
uuid: c0ad0941746546aeb6de2fee087c8252
- expression: 'max(/APC UPS Symmetra RX SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0'
+ expression: 'max(/APC UPS Symmetra RX by SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0'
name: 'No SNMP data collection'
opdata: 'Current state: {ITEM.LASTVALUE1}'
priority: WARNING
@@ -1021,7 +1021,7 @@ zabbix_export:
trigger_prototypes:
-
uuid: 3a48257337a84a2296db92410a8aed8c
- expression: 'find(/APC UPS Symmetra RX SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1'
+ expression: 'find(/APC UPS Symmetra RX by SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1'
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay'
opdata: 'Current bit set: {ITEM.LASTVALUE1}'
priority: WARNING
@@ -1077,7 +1077,7 @@ zabbix_export:
trigger_prototypes:
-
uuid: 4498d376328e405bad7da5f1832cde8a
- expression: 'find(/APC UPS Symmetra RX SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0'
+ expression: 'find(/APC UPS Symmetra RX by SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0'
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay'
opdata: 'Current bit set: {ITEM.LASTVALUE1}'
priority: WARNING
@@ -1127,7 +1127,7 @@ zabbix_export:
trigger_prototypes:
-
uuid: f710e2b952054f35ab6e3e8e90ab7f83
- expression: 'min(/APC UPS Symmetra RX SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}'
+ expression: 'min(/APC UPS Symmetra RX by SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}'
name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature'
event_name: '{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature (over {$BATTERY.TEMP.MAX.WARN}℃ for {$TIME.PERIOD})'
opdata: 'Current temperature: {ITEM.LASTVALUE1}'
@@ -1224,7 +1224,7 @@ zabbix_export:
trigger_prototypes:
-
uuid: 0de21ba7495d41f4834170122620c37d
- expression: 'last(/APC UPS Symmetra RX SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=3'
+ expression: 'last(/APC UPS Symmetra RX by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=3'
name: '{#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical'
priority: HIGH
description: 'The external sensor has returned a value greater than the critical threshold.'
@@ -1234,7 +1234,7 @@ zabbix_export:
value: notice
-
uuid: 69fbc11262f74fdfb49da43bb59c1810
- expression: 'last(/APC UPS Symmetra RX SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4'
+ expression: 'last(/APC UPS Symmetra RX by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4'
name: '{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable'
priority: INFO
description: 'The external sensor does not work or is not connected.'
@@ -1244,7 +1244,7 @@ zabbix_export:
value: notice
-
uuid: 0ce46cad353c4299ad5540a831b5c467
- expression: 'last(/APC UPS Symmetra RX SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2'
+ expression: 'last(/APC UPS Symmetra RX by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2'
name: '{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning'
priority: AVERAGE
description: 'The external sensor has returned a value greater than the warning threshold.'
@@ -1292,7 +1292,6 @@ zabbix_export:
operationobject: ITEM_PROTOTYPE
operator: LIKE
value: Humidity
- status: ENABLED
discover: NO_DISCOVER
-
uuid: 7cd4c33584004a6d811478e8a83e0898
@@ -1360,7 +1359,7 @@ zabbix_export:
trigger_prototypes:
-
uuid: f27f80f391a04927bb138ba66d48d364
- expression: 'last(/APC UPS Symmetra RX SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=3'
+ expression: 'last(/APC UPS Symmetra RX by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=3'
name: '{#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical'
priority: HIGH
description: 'The external sensor has returned a value greater than the critical threshold.'
@@ -1370,7 +1369,7 @@ zabbix_export:
value: notice
-
uuid: a84e1b5140b643ad8bee020d74821255
- expression: 'last(/APC UPS Symmetra RX SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=4'
+ expression: 'last(/APC UPS Symmetra RX by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=4'
name: '{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable'
priority: INFO
description: 'The external sensor does not work or is not connected.'
@@ -1380,7 +1379,7 @@ zabbix_export:
value: notice
-
uuid: b67ed4a3ce5a49e4ac4079e258d7fe7c
- expression: 'last(/APC UPS Symmetra RX SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=2'
+ expression: 'last(/APC UPS Symmetra RX by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=2'
name: '{#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning'
priority: AVERAGE
description: 'The external sensor has returned a value greater than the warning threshold.'
@@ -1428,7 +1427,6 @@ zabbix_export:
operationobject: ITEM_PROTOTYPE
operator: LIKE
value: Humidity
- status: ENABLED
discover: NO_DISCOVER
-
uuid: 88032aa9a832464ca2a077271113e7c9
@@ -1490,7 +1488,7 @@ zabbix_export:
trigger_prototypes:
-
uuid: 212cf86650fc4c189115da565111f5d3
- expression: 'min(/APC UPS Symmetra RX SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra RX SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}'
+ expression: 'min(/APC UPS Symmetra RX by SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra RX by SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}'
name: '{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage'
event_name: '{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})'
opdata: 'Current phase {#PHASEINDEX} voltage: {ITEM.LASTVALUE1}'
@@ -1583,7 +1581,7 @@ zabbix_export:
trigger_prototypes:
-
uuid: 47069f8d431f45d490674d7ba01d2bb2
- expression: 'min(/APC UPS Symmetra RX SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra RX SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}'
+ expression: 'min(/APC UPS Symmetra RX by SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Symmetra RX by SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}'
name: '{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage'
event_name: '{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage (out of range {$UPS.INPUT_VOLT.MIN.WARN}-{$UPS.INPUT_VOLT.MAX.WARN}V for {$TIME.PERIOD})'
opdata: 'Current phase {#PHASEINDEX} voltage: {ITEM.LASTVALUE1}'
@@ -1639,6 +1637,136 @@ zabbix_export:
macro: '{$UPS.OUTPUT.MAX.WARN}'
value: '80'
description: 'Maximum output load in % for trigger expression.'
+ dashboards:
+ -
+ uuid: 6819b4e7963340438675de6c3f72bb4f
+ name: 'UPS Summary'
+ pages:
+ -
+ widgets:
+ -
+ type: PLAIN_TEXT
+ width: '8'
+ height: '5'
+ fields:
+ -
+ type: ITEM
+ name: itemids
+ value:
+ host: 'APC UPS Symmetra RX by SNMP'
+ key: 'system.net.uptime[sysUpTime.0]'
+ -
+ type: PLAIN_TEXT
+ x: '8'
+ width: '8'
+ height: '5'
+ fields:
+ -
+ type: ITEM
+ name: itemids
+ value:
+ host: 'APC UPS Symmetra RX by SNMP'
+ key: 'input.fail[upsAdvInputLineFailCause]'
+ -
+ type: PLAIN_TEXT
+ x: '16'
+ width: '8'
+ height: '5'
+ fields:
+ -
+ type: ITEM
+ name: itemids
+ value:
+ host: 'APC UPS Symmetra RX by SNMP'
+ key: 'output.status[upsBasicOutputStatus]'
+ -
+ type: PLAIN_TEXT
+ 'y': '5'
+ width: '8'
+ height: '5'
+ fields:
+ -
+ type: ITEM
+ name: itemids
+ value:
+ host: 'APC UPS Symmetra RX by SNMP'
+ key: 'battery.status[upsBasicBatteryStatus]'
+ -
+ type: PLAIN_TEXT
+ x: '8'
+ 'y': '5'
+ width: '8'
+ height: '5'
+ fields:
+ -
+ type: ITEM
+ name: itemids
+ value:
+ host: 'APC UPS Symmetra RX by SNMP'
+ key: 'battery.runtime_remaining[upsAdvBatteryRunTimeRemaining]'
+ -
+ type: PLAIN_TEXT
+ x: '16'
+ 'y': '5'
+ width: '8'
+ height: '5'
+ fields:
+ -
+ type: ITEM
+ name: itemids
+ value:
+ host: 'APC UPS Symmetra RX by SNMP'
+ key: 'battery.last_replace_date[upsBasicBatteryLastReplaceDate]'
+ -
+ type: GRAPH_CLASSIC
+ 'y': '10'
+ width: '8'
+ height: '5'
+ fields:
+ -
+ type: INTEGER
+ name: source_type
+ value: '0'
+ -
+ type: GRAPH
+ name: graphid
+ value:
+ host: 'APC UPS Symmetra RX by SNMP'
+ name: 'Capacity of the UPS batteries'
+ -
+ type: GRAPH_CLASSIC
+ x: '8'
+ 'y': '10'
+ width: '8'
+ height: '5'
+ fields:
+ -
+ type: INTEGER
+ name: source_type
+ value: '0'
+ -
+ type: GRAPH
+ name: graphid
+ value:
+ host: 'APC UPS Symmetra RX by SNMP'
+ name: Voltage
+ -
+ type: GRAPH_CLASSIC
+ x: '16'
+ 'y': '10'
+ width: '8'
+ height: '5'
+ fields:
+ -
+ type: INTEGER
+ name: source_type
+ value: '0'
+ -
+ type: GRAPH
+ name: graphid
+ value:
+ host: 'APC UPS Symmetra RX by SNMP'
+ name: Output
valuemaps:
-
uuid: e2877a188bd24918992f8c7878550924
@@ -1814,7 +1942,7 @@ zabbix_export:
triggers:
-
uuid: 990c0545543c42a78022589838a8a1ff
- expression: '(last(/APC UPS Symmetra RX SNMP/system.hw.uptime[hrSystemUptime.0])>0 and last(/APC UPS Symmetra RX SNMP/system.hw.uptime[hrSystemUptime.0])<10m) or (last(/APC UPS Symmetra RX SNMP/system.hw.uptime[hrSystemUptime.0])=0 and last(/APC UPS Symmetra RX SNMP/system.net.uptime[sysUpTime.0])<10m)'
+ expression: '(last(/APC UPS Symmetra RX by SNMP/system.hw.uptime[hrSystemUptime.0])>0 and last(/APC UPS Symmetra RX by SNMP/system.hw.uptime[hrSystemUptime.0])<10m) or (last(/APC UPS Symmetra RX by SNMP/system.hw.uptime[hrSystemUptime.0])=0 and last(/APC UPS Symmetra RX by SNMP/system.net.uptime[sysUpTime.0])<10m)'
name: 'Host has been restarted'
event_name: '{HOST.NAME} has been restarted (uptime < 10m)'
priority: WARNING
@@ -1823,7 +1951,7 @@ zabbix_export:
dependencies:
-
name: 'No SNMP data collection'
- expression: 'max(/APC UPS Symmetra RX SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0'
+ expression: 'max(/APC UPS Symmetra RX by SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0'
tags:
-
tag: scope
@@ -1837,7 +1965,7 @@ zabbix_export:
-
color: 1A7C11
item:
- host: 'APC UPS Symmetra RX SNMP'
+ host: 'APC UPS Symmetra RX by SNMP'
key: 'battery.capacity[upsHighPrecBatteryCapacity]'
-
uuid: 782c8a349b7f4f93a65aeaa058454b14
@@ -1846,13 +1974,13 @@ zabbix_export:
-
color: 1A7C11
item:
- host: 'APC UPS Symmetra RX SNMP'
+ host: 'APC UPS Symmetra RX by SNMP'
key: 'output.current[upsHighPrecOutputCurrent]'
-
sortorder: '1'
color: 2774A4
item:
- host: 'APC UPS Symmetra RX SNMP'
+ host: 'APC UPS Symmetra RX by SNMP'
key: 'output.load[upsHighPrecOutputLoad]'
-
uuid: 8bc9d8e4bb284134b67498daccb85d5e
@@ -1861,11 +1989,11 @@ zabbix_export:
-
color: 1A7C11
item:
- host: 'APC UPS Symmetra RX SNMP'
+ host: 'APC UPS Symmetra RX by SNMP'
key: 'input.voltage[upsHighPrecInputLineVoltage]'
-
sortorder: '1'
color: 2774A4
item:
- host: 'APC UPS Symmetra RX SNMP'
+ host: 'APC UPS Symmetra RX by SNMP'
key: 'output.voltage[upsHighPrecOutputVoltage]'