Welcome to mirror list, hosted at ThFree Co, Russian Federation.

README.md « morningstar_tristar_mppt_600V_snmp « morningstar « net « templates - github.com/zabbix/zabbix.git - Unnamed repository; edit this file 'description' to name the repository.
summaryrefslogtreecommitdiff
blob: 3b884ec3b71095e042b68325f303236827728f84 (plain)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149

# Morningstar TriStar MPPT 600V by SNMP

## Overview

For Zabbix version: 6.4 and higher.

## Setup

> See [Zabbix template operation](https://www.zabbix.com/documentation/6.4/manual/config/templates_out_of_the_box/zabbix_agent) for basic instructions.

Refer to the vendor documentation.

## Zabbix configuration

No specific Zabbix configuration is required.

### Macros used

|Name|Description|Default|
|----|-----------|-------|
|{$BATTERY.TEMP.MAX.CRIT} |<p>Battery high temperature critical value</p> |`60` |
|{$BATTERY.TEMP.MAX.WARN} |<p>Battery high temperature warning value</p> |`45` |
|{$BATTERY.TEMP.MIN.CRIT} |<p>Battery low temperature critical value</p> |`-20` |
|{$BATTERY.TEMP.MIN.WARN} |<p>Battery low temperature warning value</p> |`0` |
|{$CHARGE.STATE.CRIT} |<p>fault</p> |`4` |
|{$CHARGE.STATE.WARN} |<p>disconnect</p> |`2` |
|{$LOAD.STATE.CRIT:"fault"} |<p>fault</p> |`4` |
|{$LOAD.STATE.CRIT:"lvd"} |<p>lvd</p> |`3` |
|{$LOAD.STATE.WARN:"disconnect"} |<p>disconnect</p> |`5` |
|{$LOAD.STATE.WARN:"lvdWarning"} |<p>lvdWarning</p> |`2` |
|{$LOAD.STATE.WARN:"override"} |<p>override</p> |`7` |
|{$VOLTAGE.MAX.CRIT} |<p>-</p> |`` |
|{$VOLTAGE.MAX.WARN} |<p>-</p> |`` |
|{$VOLTAGE.MIN.CRIT} |<p>-</p> |`` |
|{$VOLTAGE.MIN.WARN} |<p>-</p> |`` |

## Template links

There are no template links in this template.

## Discovery rules

|Name|Description|Type|Key and additional info|
|----|-----------|----|----|
|Battery voltage discovery |<p>Discovery for battery voltage triggers</p> |DEPENDENT |battery.voltage.discovery<p>**Preprocessing**:</p><p>- JAVASCRIPT: `The text is too long. Please see the template.`</p> |

## Items collected

|Group|Name|Description|Type|Key and additional info|
|-----|----|-----------|----|---------------------|
|Array |Array: Voltage |<p>MIB: TRISTAR-MPPT</p><p>Description:Array Voltage</p><p>Scaling Factor:1.0</p><p>Units:V</p><p>Range:[-10, 650]</p><p>Modbus address:0x001b</p> |SNMP |array.voltage[arrayVoltage.0] |
|Array |Array: Array Current |<p>MIB: TRISTAR-MPPT</p><p>Description:Array Current</p><p>Scaling Factor:1.0</p><p>Units:A</p><p>Range:[-10, 80]</p><p>Modbus address:0x001d</p> |SNMP |array.current[arrayCurrent.0] |
|Array |Array: Sweep Vmp |<p>MIB: TRISTAR-MPPT</p><p>Description:Vmp (last sweep)</p><p>Scaling Factor:1.0</p><p>Units:V</p><p>Range:[-10, 650.0]</p><p>Modbus address:0x003d</p> |SNMP |array.sweep_vmp[arrayVmpLastSweep.0] |
|Array |Array: Sweep Voc |<p>MIB: TRISTAR-MPPT</p><p>Description:Voc (last sweep)</p><p>Scaling Factor:1.0</p><p>Units:V</p><p>Range:[-10, 650.0]</p><p>Modbus address:0x003e</p> |SNMP |array.sweep_voc[arrayVocLastSweep.0] |
|Array |Array: Sweep Pmax |<p>MIB: TRISTAR-MPPT</p><p>Description:Pmax (last sweep)</p><p>Scaling Factor:1.0</p><p>Units:W</p><p>Range:[-10, 5000]</p><p>Modbus address:0x003c</p> |SNMP |array.sweep_pmax[arrayPmaxLastSweep.0] |
|Battery |Battery: Charge State |<p>MIB: TRISTAR-MPPT</p><p>Description:Charge State</p><p>Modbus address:0x0032</p><p>0: Start</p><p>1: NightCheck</p><p>2: Disconnect</p><p>3: Night</p><p>4: Fault</p><p>5: Mppt</p><p>6: Absorption</p><p>7: Float</p><p>8: Equalize</p><p>9: Slave</p><p>10: Fixed</p> |SNMP |charge.state[chargeState.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `1h`</p> |
|Battery |Battery: Target Voltage |<p>MIB: TRISTAR-MPPT</p><p>Description:Target Voltage</p><p>Scaling Factor:1.0</p><p>Units:V</p><p>Range:[-10, 650.0]</p><p>Modbus address:0x0033</p> |SNMP |target.voltage[targetRegulationVoltage.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `1h`</p> |
|Battery |Battery: Charge Current |<p>MIB: TRISTAR-MPPT</p><p>Description:Battery Current</p><p>Scaling Factor:1.0</p><p>Units:A</p><p>Range:[-10, 80]</p><p>Modbus address:0x001c</p> |SNMP |charge.current[batteryCurrent.0] |
|Battery |Battery: Output Power |<p>MIB: TRISTAR-MPPT</p><p>Description:Output Power</p><p>Scaling Factor:1.0</p><p>Units:W</p><p>Range:[-10, 4000]</p><p>Modbus address:0x003a</p> |SNMP |charge.output_power[ outputPower.0] |
|Battery |Battery: Voltage{#SINGLETON} |<p>MIB: TRISTAR-MPPT</p><p>Description:Battery voltage</p><p>Scaling Factor:1.0</p><p>Units:V</p><p>Range:[-10, 80]</p><p>Modbus address:0x0018</p> |SNMP |battery.voltage[batteryVoltage.0{#SINGLETON}] |
|Counter |Counter: Charge Amp-hours |<p>MIB: TRISTAR-MPPT</p><p>Description:Ah Charge Resettable</p><p>Scaling Factor:1.0</p><p>Units:Ah</p><p>Range:[0.0, 5000]</p><p>Modbus addresses:H=0x0034 L=0x0035</p> |SNMP |counter.charge_amp_hours[ahChargeResetable.0] |
|Counter |Counter: Charge KW-hours |<p>MIB: TRISTAR-MPPT</p><p>Description:kWh Charge Resettable</p><p>Scaling Factor:1.0</p><p>Units:kWh</p><p>Range:[0.0, 65535.0]</p><p>Modbus address:0x0038</p> |SNMP |counter.charge_kw_hours[kwhChargeResetable.0] |
|Status |Status: Uptime (network) |<p>The time (in hundredths of a second) since the network management portion of the system was last re-initialized.</p> |SNMP |status.net.uptime<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.01`</p> |
|Status |Status: Uptime (hardware) |<p>The amount of time since this host was last initialized. Note that this is different from sysUpTime in the SNMPv2-MIB [RFC1907] because sysUpTime is the uptime of the network management portion of the system.</p> |SNMP |status.hw.uptime<p>**Preprocessing**:</p><p>- CHECK_NOT_SUPPORTED</p><p>⛔️ON_FAIL: `CUSTOM_VALUE -> 0`</p><p>- MULTIPLIER: `0.01`</p> |
|Status |Status: Faults |<p>MIB: TRISTAR-MPPT</p><p>Description:Faults</p><p>Modbus addresses:H=0x002c L=0x002d</p> |SNMP |status.faults[faults.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `1h`</p><p>- JAVASCRIPT: `The text is too long. Please see the template.`</p> |
|Status |Status: Alarms |<p>MIB: TRISTAR-MPPT</p><p>Description:Alarms</p><p>Modbus addresses:H=0x002e L=0x002f</p> |SNMP |status.alarms[alarms.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `1h`</p><p>- JAVASCRIPT: `The text is too long. Please see the template.`</p> |
|Temperature |Temperature: Battery |<p>MIB: TRISTAR-MPPT</p><p>Description:Batt. Temp</p><p>Scaling Factor:1.0</p><p>Units:C</p><p>Range:[-40, 80]</p><p>Modbus address:0x0025</p> |SNMP |temp.battery[batteryTemperature.0] |
|Temperature |Temperature: Heatsink |<p>MIB: TRISTAR-MPPT</p><p>Description:HS Temp</p><p>Scaling Factor:1.0</p><p>Units:C</p><p>Range:[-40, 80]</p><p>Modbus address:0x0023</p> |SNMP |temp.heatsink[heatsinkTemperature.0] |
|Zabbix raw items |Battery: Battery Voltage discovery |<p>MIB: TRISTAR-MPPT</p><p>Description:Battery voltage</p><p>Scaling Factor:1.0</p><p>Units:V</p><p>Range:[-10, 80]</p><p>Modbus address:0x0018</p> |SNMP |battery.voltage.discovery[batteryVoltage.0] |

## Triggers

|Name|Description|Expression|Severity|Dependencies and additional info|
|----|-----------|----|----|----|
|Battery: Device charge in warning state |<p>-</p> |`last(/Morningstar TriStar MPPT 600V by SNMP/charge.state[chargeState.0])={$CHARGE.STATE.WARN}` |WARNING |<p>**Depends on**:</p><p>- Battery: Device charge in critical state</p> |
|Battery: Device charge in critical state |<p>-</p> |`last(/Morningstar TriStar MPPT 600V by SNMP/charge.state[chargeState.0])={$CHARGE.STATE.CRIT}` |HIGH | |
|Battery: Low battery voltage |<p>-</p> |`max(/Morningstar TriStar MPPT 600V by SNMP/battery.voltage[batteryVoltage.0{#SINGLETON}],5m)<{#VOLTAGE.MIN.WARN}` |WARNING |<p>**Depends on**:</p><p>- Battery: Critically low battery voltage</p> |
|Battery: Critically low battery voltage |<p>-</p> |`max(/Morningstar TriStar MPPT 600V by SNMP/battery.voltage[batteryVoltage.0{#SINGLETON}],5m)<{#VOLTAGE.MIN.CRIT}` |HIGH | |
|Battery: High battery voltage |<p>-</p> |`min(/Morningstar TriStar MPPT 600V by SNMP/battery.voltage[batteryVoltage.0{#SINGLETON}],5m)>{#VOLTAGE.MAX.WARN}` |WARNING |<p>**Depends on**:</p><p>- Battery: Critically high battery voltage</p> |
|Battery: Critically high battery voltage |<p>-</p> |`min(/Morningstar TriStar MPPT 600V by SNMP/battery.voltage[batteryVoltage.0{#SINGLETON}],5m)>{#VOLTAGE.MAX.CRIT}` |HIGH | |
|Status: Device has been restarted |<p>Uptime is less than 10 minutes.</p> |`(last(/Morningstar TriStar MPPT 600V by SNMP/status.hw.uptime)>0 and last(/Morningstar TriStar MPPT 600V by SNMP/status.hw.uptime)<10m) or (last(/Morningstar TriStar MPPT 600V by SNMP/status.hw.uptime)=0 and last(/Morningstar TriStar MPPT 600V by SNMP/status.net.uptime)<10m)` |INFO |<p>Manual close: YES</p> |
|Status: Failed to fetch data |<p>Zabbix has not received data for items for the last 5 minutes.</p> |`nodata(/Morningstar TriStar MPPT 600V by SNMP/status.net.uptime,5m)=1` |WARNING |<p>Manual close: YES</p> |
|Status: Device has "overcurrent" faults flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.faults[faults.0],#3,"like","overcurrent")=2` |HIGH | |
|Status: Device has "fetShort" faults flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.faults[faults.0],#3,"like","fetShort")=2` |HIGH | |
|Status: Device has "softwareFault" faults flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.faults[faults.0],#3,"like","softwareFault")=2` |HIGH | |
|Status: Device has "batteryHvd" faults flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.faults[faults.0],#3,"like","batteryHvd")=2` |HIGH | |
|Status: Device has "arrayHvd" faults flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.faults[faults.0],#3,"like","arrayHvd")=2` |HIGH | |
|Status: Device has "dipSwitchChange" faults flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.faults[faults.0],#3,"like","dipSwitchChange")=2` |HIGH | |
|Status: Device has "customSettingsEdit" faults flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.faults[faults.0],#3,"like","customSettingsEdit")=2` |HIGH | |
|Status: Device has "rtsShorted" faults flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.faults[faults.0],#3,"like","rtsShorted")=2` |HIGH | |
|Status: Device has "rtsDisconnected" faults flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.faults[faults.0],#3,"like","rtsDisconnected")=2` |HIGH | |
|Status: Device has "eepromRetryLimit" faults flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.faults[faults.0],#3,"like","eepromRetryLimit")=2` |HIGH | |
|Status: Device has "controllerWasReset" faults flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.faults[faults.0],#3,"like","controllerWasReset")=2` |HIGH | |
|Status: Device has "chargeSlaveControlTimeout" faults flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.faults[faults.0],#3,"like","chargeSlaveControlTimeout")=2` |HIGH | |
|Status: Device has "rs232SerialToMeterBridge" faults flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.faults[faults.0],#3,"like","rs232SerialToMeterBridge")=2` |HIGH | |
|Status: Device has "batteryLvd" faults flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.faults[faults.0],#3,"like","batteryLvd")=2` |HIGH | |
|Status: Device has "powerboardCommunicationFault" faults flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.faults[faults.0],#3,"like","powerboardCommunicationFault")=2` |HIGH | |
|Status: Device has "fault16Software" faults flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.faults[faults.0],#3,"like","fault16Software")=2` |HIGH | |
|Status: Device has "fault17Software" faults flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.faults[faults.0],#3,"like","fault17Software")=2` |HIGH | |
|Status: Device has "fault18Software" faults flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.faults[faults.0],#3,"like","fault18Software")=2` |HIGH | |
|Status: Device has "fault19Software" faults flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.faults[faults.0],#3,"like","fault19Software")=2` |HIGH | |
|Status: Device has "fault20Software" faults flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.faults[faults.0],#3,"like","fault20Software")=2` |HIGH | |
|Status: Device has "fault21Software" faults flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.faults[faults.0],#3,"like","fault21Software")=2` |HIGH | |
|Status: Device has "fpgaVersion" faults flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.faults[faults.0],#3,"like","fpgaVersion")=2` |HIGH | |
|Status: Device has "currentSensorReferenceOutOfRange" faults flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.faults[faults.0],#3,"like","currentSensorReferenceOutOfRange")=2` |HIGH | |
|Status: Device has "ia-refSlaveModeTimeout" faults flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.faults[faults.0],#3,"like","ia-refSlaveModeTimeout")=2` |HIGH | |
|Status: Device has "blockbusBoot" faults flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.faults[faults.0],#3,"like","blockbusBoot")=2` |HIGH | |
|Status: Device has "hscommMaster" faults flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.faults[faults.0],#3,"like","hscommMaster")=2` |HIGH | |
|Status: Device has "hscomm" faults flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.faults[faults.0],#3,"like","hscomm")=2` |HIGH | |
|Status: Device has "slave" faults flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.faults[faults.0],#3,"like","slave")=2` |HIGH | |
|Status: Device has "rtsShorted" alarm flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.alarms[alarms.0],#3,"like","rtsShorted")=2` |WARNING | |
|Status: Device has "rtsDisconnected" alarm flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.alarms[alarms.0],#3,"like","rtsDisconnected")=2` |WARNING | |
|Status: Device has "heatsinkTempSensorOpen" alarm flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.alarms[alarms.0],#3,"like","heatsinkTempSensorOpen")=2` |WARNING | |
|Status: Device has "heatsinkTempSensorShorted" alarm flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.alarms[alarms.0],#3,"like","heatsinkTempSensorShorted")=2` |WARNING | |
|Status: Device has "highTemperatureCurrentLimit" alarm flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.alarms[alarms.0],#3,"like","highTemperatureCurrentLimit")=2` |WARNING | |
|Status: Device has "currentLimit" alarm flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.alarms[alarms.0],#3,"like","currentLimit")=2` |WARNING | |
|Status: Device has "currentOffset" alarm flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.alarms[alarms.0],#3,"like","currentOffset")=2` |WARNING | |
|Status: Device has "batterySense" alarm flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.alarms[alarms.0],#3,"like","batterySense")=2` |WARNING | |
|Status: Device has "batterySenseDisconnected" alarm flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.alarms[alarms.0],#3,"like","batterySenseDisconnected")=2` |WARNING | |
|Status: Device has "uncalibrated" alarm flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.alarms[alarms.0],#3,"like","uncalibrated")=2` |WARNING | |
|Status: Device has "rtsMiswire" alarm flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.alarms[alarms.0],#3,"like","rtsMiswire")=2` |WARNING | |
|Status: Device has "highVoltageDisconnect" alarm flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.alarms[alarms.0],#3,"like","highVoltageDisconnect")=2` |WARNING | |
|Status: Device has "systemMiswire" alarm flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.alarms[alarms.0],#3,"like","systemMiswire")=2` |WARNING | |
|Status: Device has "mosfetSOpen" alarm flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.alarms[alarms.0],#3,"like","mosfetSOpen")=2` |WARNING | |
|Status: Device has "p12VoltageOutOfRange" alarm flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.alarms[alarms.0],#3,"like","p12VoltageOutOfRange")=2` |WARNING | |
|Status: Device has "highArrayVCurrentLimit" alarm flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.alarms[alarms.0],#3,"like","highArrayVCurrentLimit")=2` |WARNING | |
|Status: Device has "maxAdcValueReached" alarm flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.alarms[alarms.0],#3,"like","maxAdcValueReached")=2` |WARNING | |
|Status: Device has "controllerWasReset" alarm flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.alarms[alarms.0],#3,"like","controllerWasReset")=2` |WARNING | |
|Status: Device has "alarm21Internal" alarm flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.alarms[alarms.0],#3,"like","alarm21Internal")=2` |WARNING | |
|Status: Device has "p3VoltageOutOfRange" alarm flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.alarms[alarms.0],#3,"like","p3VoltageOutOfRange")=2` |WARNING | |
|Status: Device has "derateLimit" alarm flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.alarms[alarms.0],#3,"like","derateLimit")=2` |WARNING | |
|Status: Device has "arrayCurrentOffset" alarm flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.alarms[alarms.0],#3,"like","arrayCurrentOffset")=2` |WARNING | |
|Status: Device has "ee-i2cRetryLimit" alarm flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.alarms[alarms.0],#3,"like","ee-i2cRetryLimit")=2` |WARNING | |
|Status: Device has "ethernetAlarm" alarm flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.alarms[alarms.0],#3,"like","ethernetAlarm")=2` |WARNING | |
|Status: Device has "lvd" alarm flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.alarms[alarms.0],#3,"like","lvd")=2` |WARNING | |
|Status: Device has "software" alarm flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.alarms[alarms.0],#3,"like","software")=2` |WARNING | |
|Status: Device has "fp12VoltageOutOfRange" alarm flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.alarms[alarms.0],#3,"like","fp12VoltageOutOfRange")=2` |WARNING | |
|Status: Device has "extflashFault" alarm flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.alarms[alarms.0],#3,"like","extflashFault")=2` |WARNING | |
|Status: Device has "slaveControlFault" alarm flag |<p>-</p> |`count(/Morningstar TriStar MPPT 600V by SNMP/status.alarms[alarms.0],#3,"like","slaveControlFault")=2` |WARNING | |
|Temperature: Low battery temperature |<p>-</p> |`max(/Morningstar TriStar MPPT 600V by SNMP/temp.battery[batteryTemperature.0],5m)<{$BATTERY.TEMP.MIN.WARN}` |WARNING |<p>**Depends on**:</p><p>- Temperature: Critically low battery temperature</p> |
|Temperature: Critically low battery temperature |<p>-</p> |`max(/Morningstar TriStar MPPT 600V by SNMP/temp.battery[batteryTemperature.0],5m)<{$BATTERY.TEMP.MIN.CRIT}` |HIGH | |
|Temperature: High battery temperature |<p>-</p> |`min(/Morningstar TriStar MPPT 600V by SNMP/temp.battery[batteryTemperature.0],5m)>{$BATTERY.TEMP.MAX.WARN}` |WARNING |<p>**Depends on**:</p><p>- Temperature: Critically high battery temperature</p> |
|Temperature: Critically high battery temperature |<p>-</p> |`min(/Morningstar TriStar MPPT 600V by SNMP/temp.battery[batteryTemperature.0],5m)>{$BATTERY.TEMP.MAX.CRIT}` |HIGH | |

## Feedback

Please report any issues with the template at https://support.zabbix.com.