Welcome to mirror list, hosted at ThFree Co, Russian Federation.

README.md « morningstar_prostar_mppt_snmp « morningstar « net « templates - github.com/zabbix/zabbix.git - Unnamed repository; edit this file 'description' to name the repository.
summaryrefslogtreecommitdiff
blob: 5865408c7fef733fd407720f6bfe243afd9774fc (plain)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143

# Morningstar ProStar MPPT by SNMP

## Overview

For Zabbix version: 6.4 and higher.

## Setup

> See [Zabbix template operation](https://www.zabbix.com/documentation/6.4/manual/config/templates_out_of_the_box/zabbix_agent) for basic instructions.

Refer to the vendor documentation.

## Zabbix configuration

No specific Zabbix configuration is required.

### Macros used

|Name|Description|Default|
|----|-----------|-------|
|{$BATTERY.TEMP.MAX.CRIT} |<p>Battery high temperature critical value</p> |`60` |
|{$BATTERY.TEMP.MAX.WARN} |<p>Battery high temperature warning value</p> |`45` |
|{$BATTERY.TEMP.MIN.CRIT} |<p>Battery low temperature critical value</p> |`-20` |
|{$BATTERY.TEMP.MIN.WARN} |<p>Battery low temperature warning value</p> |`0` |
|{$CHARGE.STATE.CRIT} |<p>fault</p> |`4` |
|{$CHARGE.STATE.WARN} |<p>disconnect</p> |`2` |
|{$LOAD.STATE.CRIT:"fault"} |<p>fault</p> |`4` |
|{$LOAD.STATE.CRIT:"lvd"} |<p>lvd</p> |`3` |
|{$LOAD.STATE.WARN:"disconnect"} |<p>disconnect</p> |`5` |
|{$LOAD.STATE.WARN:"lvdWarning"} |<p>lvdWarning</p> |`2` |
|{$LOAD.STATE.WARN:"override"} |<p>override</p> |`7` |
|{$VOLTAGE.MAX.CRIT} |<p>-</p> |`` |
|{$VOLTAGE.MAX.WARN} |<p>-</p> |`` |
|{$VOLTAGE.MIN.CRIT} |<p>-</p> |`` |
|{$VOLTAGE.MIN.WARN} |<p>-</p> |`` |

## Template links

There are no template links in this template.

## Discovery rules

|Name|Description|Type|Key and additional info|
|----|-----------|----|----|
|Battery voltage discovery |<p>Discovery for battery voltage triggers</p> |DEPENDENT |battery.voltage.discovery<p>**Preprocessing**:</p><p>- JAVASCRIPT: `The text is too long. Please see the template.`</p> |

## Items collected

|Group|Name|Description|Type|Key and additional info|
|-----|----|-----------|----|---------------------|
|Array |Array: Voltage |<p>MIB: PROSTAR-MPPT</p><p>Array Voltage</p><p>  Description:Array Voltage</p><p>  Scaling Factor:1.0</p><p>  Units:V</p><p>  Range:[0, 80]</p><p>  Modbus address:0x0013</p> |SNMP |array.voltage[arrayVoltage.0] |
|Array |Array: Sweep Vmp |<p>MIB: PROSTAR-MPPT</p><p>Array Vmp</p><p>  Description:Array Max. Power Point Voltage</p><p>  Scaling Factor:1.0</p><p>  Units:V</p><p>  Range:[0.0, 5000.0]</p><p>  Modbus address:0x003D</p> |SNMP |array.sweep_vmp[arrayVmp.0] |
|Array |Array: Sweep Voc |<p>MIB: PROSTAR-MPPT</p><p>Array Voc</p><p> Description:Array Open Circuit Voltage</p><p> Scaling Factor:1.0</p><p> Units:V</p><p> Range:[0.0, 80.0]</p><p> Modbus address:0x003F</p> |SNMP |array.sweep_voc[arrayVoc.0] |
|Array |Array: Sweep Pmax |<p>MIB: PROSTAR-MPPT</p><p>Array Max. Power (sweep)</p><p> Description:Array Max. Power (last sweep)</p><p> Scaling Factor:1.0</p><p> Units:W</p><p> Range:[0.0, 500]</p><p> Modbus address:0x003E</p> |SNMP |array.sweep_pmax[arrayMaxPowerSweep.0] |
|Battery |Battery: Charge State |<p>MIB: PROSTAR-MPPT</p><p>Charge State</p><p>  Description:Control State</p><p>  Modbus address:0x0021</p><p>  0: Start</p><p>  1: NightCheck</p><p>  2: Disconnect</p><p>  3: Night</p><p>  4: Fault</p><p>  5: BulkMppt</p><p>  6: Absorption</p><p>  7: Float</p><p>  8: Equalize</p><p>  9: Slave</p><p>  10: Fixed</p> |SNMP |charge.state[chargeState.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `1h`</p> |
|Battery |Battery: Target Voltage |<p>MIB: PROSTAR-MPPT</p><p>Target Voltage</p><p> Description:Target Regulation Voltage</p><p> Scaling Factor:1.0</p><p> Units:V</p><p> Range:[0.0, 80.0]</p><p> Modbus address:0x0024</p> |SNMP |target.voltage[targetVoltage.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `1h`</p> |
|Battery |Battery: Charge Current |<p>MIB: PROSTAR-MPPT</p><p>Charge Current</p><p>  Description:Charge Current</p><p>  Scaling Factor:1.0</p><p>  Units:A</p><p>  Range:[0, 40]</p><p>  Modbus address:0x0010</p> |SNMP |charge.current[chargeCurrent.0] |
|Battery |Battery: Voltage{#SINGLETON} |<p>MIB: PROSTAR-MPPT</p><p>Battery Terminal Voltage</p><p>Description:Battery  Terminal Voltage</p><p>Scaling Factor:1.0</p><p>Units:V</p><p>Range:[0.0, 80.0]</p><p>Modbus address:0x0012</p> |SNMP |battery.voltage[batteryTerminalVoltage.0{#SINGLETON}] |
|Counter |Counter: Charge Amp-hours |<p>MIB: PROSTAR-MPPT</p><p>Ah Charge (Resettable)</p><p> Description:Ah Charge (Resettable)</p><p> Scaling Factor:0.1</p><p> Units:Ah</p><p> Range:[0.0, 4294967294]</p><p> Modbus addresses:H=0x0026 L=0x0027</p> |SNMP |counter.charge_amp_hours[ahChargeResettable.0]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p> |
|Counter |Counter: Charge KW-hours |<p>MIB: PROSTAR-MPPT</p><p>kWh Charge (Resettable)</p><p>Description:Kilowatt Hours Charge (Resettable)</p><p>Scaling Factor:1.0</p><p>Units:kWh</p><p>Range:[0.0, 65535]</p><p>Modbus address:0x002A</p> |SNMP |counter.charge_kw_hours[kwhChargeResettable.0] |
|Counter |Counter: Load Amp-hours |<p>MIB: PROSTAR-MPPT</p><p>Description:Ah Load (Resettable)</p><p>Scaling Factor:0.1</p><p>Units:Ah</p><p>Range:[0.0, 4294967294]</p><p>Modbus addresses:H=0x0032 L=0x0033</p> |SNMP |counter.load_amp_hours[ahLoadResettable.0]<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.1`</p> |
|Load |Load: State |<p>MIB: PROSTAR-MPPT</p><p>Load State</p><p> Description:Load State</p><p> Modbus address:0x002E</p><p> 0: Start</p><p>1: Normal</p><p>2: LvdWarning</p><p>3: Lvd</p><p>4: Fault</p><p>5: Disconnect</p><p>6: NormalOff</p><p>7: Override</p><p>8: NotUsed</p> |SNMP |load.state[loadState.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `1h`</p> |
|Load |Load: Voltage |<p>MIB: PROSTAR-MPPT</p><p>Load Voltage</p><p> Description:Load Voltage</p><p> Scaling Factor:1.0</p><p> Units:V</p><p> Range:[0, 80]</p><p> Modbus address:0x0014</p> |SNMP |load.voltage[loadVoltage.0] |
|Load |Load: Current |<p>MIB: PROSTAR-MPPT</p><p>Load Current</p><p> Description:Load Current</p><p> Scaling Factor:1.0</p><p> Units:A</p><p> Range:[0, 60]</p><p> Modbus address:0x0016</p> |SNMP |load.current[loadCurrent.0] |
|Status |Status: Uptime (network) |<p>The time (in hundredths of a second) since the network management portion of the system was last re-initialized.</p> |SNMP |status.net.uptime<p>**Preprocessing**:</p><p>- MULTIPLIER: `0.01`</p> |
|Status |Status: Uptime (hardware) |<p>The amount of time since this host was last initialized. Note that this is different from sysUpTime in the SNMPv2-MIB [RFC1907] because sysUpTime is the uptime of the network management portion of the system.</p> |SNMP |status.hw.uptime<p>**Preprocessing**:</p><p>- CHECK_NOT_SUPPORTED</p><p>⛔️ON_FAIL: `CUSTOM_VALUE -> 0`</p><p>- MULTIPLIER: `0.01`</p> |
|Status |Status: Array Faults |<p>MIB: PROSTAR-MPPT</p><p>Description:Array Faults</p><p>Modbus address:0x0022</p> |SNMP |status.array_faults[arrayFaults.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `1h`</p><p>- JAVASCRIPT: `The text is too long. Please see the template.`</p> |
|Status |Status: Load Faults |<p>MIB: PROSTAR-MPPT</p><p>Description:Array Faults</p><p>Modbus address:0x0022</p> |SNMP |status.load_faults[loadFaults.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `1h`</p><p>- JAVASCRIPT: `The text is too long. Please see the template.`</p> |
|Status |Status: Alarms |<p>MIB: PROSTAR-MPPT</p><p>Description:Alarms</p><p>Modbus addresses:H=0x0038 L=0x0039</p> |SNMP |status.alarms[alarms.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT: `1h`</p><p>- JAVASCRIPT: `The text is too long. Please see the template.`</p> |
|Temperature |Temperature: Ambient |<p>MIB: PROSTAR-MPPT</p><p>Ambient Temperature</p><p> Description:Ambient Temperature</p><p> Scaling Factor:1.0</p><p> Units:deg C</p><p> Range:[-128, 127]</p><p> Modbus address:0x001C</p> |SNMP |temp.ambient[ambientTemperature.0] |
|Temperature |Temperature: Battery |<p>MIB: PROSTAR-MPPT</p><p>Battery Temperature</p><p>  Description:Battery Temperature</p><p>  Scaling Factor:1.0</p><p>  Units:deg C</p><p>  Range:[-128, 127]</p><p>  Modbus address:0x001B</p> |SNMP |temp.battery[batteryTemperature.0] |
|Temperature |Temperature: Heatsink |<p>MIB: PROSTAR-MPPT</p><p>Heatsink Temperature</p><p> Description:Heatsink Temperature</p><p> Scaling Factor:1.0</p><p> Units:deg C</p><p> Range:[-128, 127]</p><p> Modbus address:0x001A</p> |SNMP |temp.heatsink[heatsinkTemperature.0] |
|Zabbix raw items |Battery: Battery Voltage discovery |<p>MIB: PROSTAR-MPPT</p> |SNMP |battery.voltage.discovery[batteryTerminalVoltage.0] |

## Triggers

|Name|Description|Expression|Severity|Dependencies and additional info|
|----|-----------|----|----|----|
|Battery: Device charge in warning state |<p>-</p> |`last(/Morningstar ProStar MPPT by SNMP/charge.state[chargeState.0])={$CHARGE.STATE.WARN}` |WARNING |<p>**Depends on**:</p><p>- Battery: Device charge in critical state</p> |
|Battery: Device charge in critical state |<p>-</p> |`last(/Morningstar ProStar MPPT by SNMP/charge.state[chargeState.0])={$CHARGE.STATE.CRIT}` |HIGH | |
|Battery: Low battery voltage |<p>-</p> |`max(/Morningstar ProStar MPPT by SNMP/battery.voltage[batteryTerminalVoltage.0{#SINGLETON}],5m)<{#VOLTAGE.MIN.WARN}` |WARNING |<p>**Depends on**:</p><p>- Battery: Critically low battery voltage</p> |
|Battery: Critically low battery voltage |<p>-</p> |`max(/Morningstar ProStar MPPT by SNMP/battery.voltage[batteryTerminalVoltage.0{#SINGLETON}],5m)<{#VOLTAGE.MIN.CRIT}` |HIGH | |
|Battery: High battery voltage |<p>-</p> |`min(/Morningstar ProStar MPPT by SNMP/battery.voltage[batteryTerminalVoltage.0{#SINGLETON}],5m)>{#VOLTAGE.MAX.WARN}` |WARNING |<p>**Depends on**:</p><p>- Battery: Critically high battery voltage</p> |
|Battery: Critically high battery voltage |<p>-</p> |`min(/Morningstar ProStar MPPT by SNMP/battery.voltage[batteryTerminalVoltage.0{#SINGLETON}],5m)>{#VOLTAGE.MAX.CRIT}` |HIGH | |
|Load: Device load in warning state |<p>-</p> |`last(/Morningstar ProStar MPPT by SNMP/load.state[loadState.0])={$LOAD.STATE.WARN:"lvdWarning"}  or last(/Morningstar ProStar MPPT by SNMP/load.state[loadState.0])={$LOAD.STATE.WARN:"override"}` |WARNING |<p>**Depends on**:</p><p>- Load: Device load in critical state</p> |
|Load: Device load in critical state |<p>-</p> |`last(/Morningstar ProStar MPPT by SNMP/load.state[loadState.0])={$LOAD.STATE.CRIT:"lvd"} or last(/Morningstar ProStar MPPT by SNMP/load.state[loadState.0])={$LOAD.STATE.CRIT:"fault"}` |HIGH | |
|Status: Device has been restarted |<p>Uptime is less than 10 minutes.</p> |`(last(/Morningstar ProStar MPPT by SNMP/status.hw.uptime)>0 and last(/Morningstar ProStar MPPT by SNMP/status.hw.uptime)<10m) or (last(/Morningstar ProStar MPPT by SNMP/status.hw.uptime)=0 and last(/Morningstar ProStar MPPT by SNMP/status.net.uptime)<10m)` |INFO |<p>Manual close: YES</p> |
|Status: Failed to fetch data |<p>Zabbix has not received data for items for the last 5 minutes.</p> |`nodata(/Morningstar ProStar MPPT by SNMP/status.net.uptime,5m)=1` |WARNING |<p>Manual close: YES</p> |
|Status: Device has "overcurrent" array faults flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","overcurrent")=2` |HIGH | |
|Status: Device has "mosfetSShorted" array faults flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","mosfetSShorted")=2` |HIGH | |
|Status: Device has "software" array faults flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","software")=2` |HIGH | |
|Status: Device has "batteryHvd" array faults flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","batteryHvd")=2` |HIGH | |
|Status: Device has "arrayHvd" array faults flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","arrayHvd")=2` |HIGH | |
|Status: Device has "customSettingsEdit" array faults flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","customSettingsEdit")=2` |HIGH | |
|Status: Device has "rtsShorted" array faults flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","rtsShorted")=2` |HIGH | |
|Status: Device has "rtsNoLongerValid" array faults flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","rtsNoLongerValid")=2` |HIGH | |
|Status: Device has "localTempSensorDamaged" array faults flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","localTempSensorDamaged")=2` |HIGH | |
|Status: Device has "batteryLowVoltageDisconnect" array faults flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","batteryLowVoltageDisconnect")=2` |HIGH | |
|Status: Device has "slaveTimeout" array faults flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","slaveTimeout")=2` |HIGH | |
|Status: Device has "dipSwitchChanged" array faults flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.array_faults[arrayFaults.0],#3,"like","dipSwitchChanged")=2` |HIGH | |
|Status: Device has "externalShortCircuit" load faults flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.load_faults[loadFaults.0],#3,"like","externalShortCircuit")=2` |HIGH | |
|Status: Device has "overcurrent" load faults flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.load_faults[loadFaults.0],#3,"like","overcurrent")=2` |HIGH | |
|Status: Device has "mosfetShorted" load faults flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.load_faults[loadFaults.0],#3,"like","mosfetShorted")=2` |HIGH | |
|Status: Device has "software" load faults flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.load_faults[loadFaults.0],#3,"like","software")=2` |HIGH | |
|Status: Device has "loadHvd" load faults flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.load_faults[loadFaults.0],#3,"like","loadHvd")=2` |HIGH | |
|Status: Device has "highTempDisconnect" load faults flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.load_faults[loadFaults.0],#3,"like","highTempDisconnect")=2` |HIGH | |
|Status: Device has "dipSwitchChanged" load faults flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.load_faults[loadFaults.0],#3,"like","dipSwitchChanged")=2` |HIGH | |
|Status: Device has "customSettingsEdit" load faults flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.load_faults[loadFaults.0],#3,"like","customSettingsEdit")=2` |HIGH | |
|Status: Device has "rtsShorted" alarm flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","rtsShorted")=2` |WARNING | |
|Status: Device has "rtsDisconnected" alarm flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","rtsDisconnected")=2` |WARNING | |
|Status: Device has "heatsinkTempSensorOpen" alarm flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","heatsinkTempSensorOpen")=2` |WARNING | |
|Status: Device has "heatsinkTempSensorShorted" alarm flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","heatsinkTempSensorShorted")=2` |WARNING | |
|Status: Device has "heatsinkTempLimit" alarm flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","heatsinkTempLimit")=2` |WARNING | |
|Status: Device has "inductorTempSensorOpen" alarm flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","inductorTempSensorOpen")=2` |WARNING | |
|Status: Device has "inductorTempSensorShorted" alarm flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","inductorTempSensorShorted")=2` |WARNING | |
|Status: Device has "inductorTempLimit" alarm flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","inductorTempLimit")=2` |WARNING | |
|Status: Device has "currentLimit" alarm flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","currentLimit")=2` |WARNING | |
|Status: Device has "currentMeasurementError" alarm flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","currentMeasurementError")=2` |WARNING | |
|Status: Device has "batterySenseOutOfRange" alarm flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","batterySenseOutOfRange")=2` |WARNING | |
|Status: Device has "batterySenseDisconnected" alarm flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","batterySenseDisconnected")=2` |WARNING | |
|Status: Device has "uncalibrated" alarm flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","uncalibrated")=2` |WARNING | |
|Status: Device has "tb5v" alarm flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","tb5v")=2` |WARNING | |
|Status: Device has "fp10SupplyOutOfRange" alarm flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","fp10SupplyOutOfRange")=2` |WARNING | |
|Status: Device has "mosfetOpen" alarm flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","mosfetOpen")=2` |WARNING | |
|Status: Device has "arrayCurrentOffset" alarm flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","arrayCurrentOffset")=2` |WARNING | |
|Status: Device has "loadCurrentOffset" alarm flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","loadCurrentOffset")=2` |WARNING | |
|Status: Device has "p33SupplyOutOfRange" alarm flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","p33SupplyOutOfRange")=2` |WARNING | |
|Status: Device has "p12SupplyOutOfRange" alarm flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","p12SupplyOutOfRange")=2` |WARNING | |
|Status: Device has "hightInputVoltageLimit" alarm flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","hightInputVoltageLimit")=2` |WARNING | |
|Status: Device has "controllerReset" alarm flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","controllerReset")=2` |WARNING | |
|Status: Device has "loadLvd" alarm flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","loadLvd")=2` |WARNING | |
|Status: Device has "logTimeout" alarm flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","logTimeout")=2` |WARNING | |
|Status: Device has "eepromAccessFailure" alarm flag |<p>-</p> |`count(/Morningstar ProStar MPPT by SNMP/status.alarms[alarms.0],#3,"like","eepromAccessFailure")=2` |WARNING | |
|Temperature: Low battery temperature |<p>-</p> |`max(/Morningstar ProStar MPPT by SNMP/temp.battery[batteryTemperature.0],5m)<{$BATTERY.TEMP.MIN.WARN}` |WARNING |<p>**Depends on**:</p><p>- Temperature: Critically low battery temperature</p> |
|Temperature: Critically low battery temperature |<p>-</p> |`max(/Morningstar ProStar MPPT by SNMP/temp.battery[batteryTemperature.0],5m)<{$BATTERY.TEMP.MIN.CRIT}` |HIGH | |
|Temperature: High battery temperature |<p>-</p> |`min(/Morningstar ProStar MPPT by SNMP/temp.battery[batteryTemperature.0],5m)>{$BATTERY.TEMP.MAX.WARN}` |WARNING |<p>**Depends on**:</p><p>- Temperature: Critically high battery temperature</p> |
|Temperature: Critically high battery temperature |<p>-</p> |`min(/Morningstar ProStar MPPT by SNMP/temp.battery[batteryTemperature.0],5m)>{$BATTERY.TEMP.MAX.CRIT}` |HIGH | |

## Feedback